7 Power Supply 7.10 I / O Control Unit Distributor Technical Training FSE SIPLACE TX-Series 01/2018 107 7.10 I / O Control Unit Distributor X 3 Data Input DI0 to DI7: DI_0 Safety_Loop_OK "High", when safety loo…

100%1 / 168
7 Power Supply
7.9 Cable harness interface
106 Technical Training FSE SIPLACE TX-Series 01/2018
1. -X23 Mini-Mate.-N-Look 15pol Control elements 1
2. -X24 Mini-Mate.-N-Look 15pol Control elements 2
3. -X26 Mini-Mate.-N-Look 12pol Control elements Hood 1
4. -X27 Mini-Mate.-N-Look 12pol Control elements Hood 2
5. -X28 Mini-Mate.-N-Look 15pol COT-insert 1 Signaling & Safety
6. -X29 Mini-Mate.-N-Look 15pol COT-insert 2 Signaling & Safety
7. -X30 Mini-Mate.-N-Look 12pol Control Vacuum_Pump Control Interior light
8. -X31 Mini-Mate.-N-Look 12pol Pneumatic_Main_System
9. -X32 Mini-Mate.-N-Look 9pol Control Vacuum_Pump Control Interior light
10. -X33 Mini-Mate.-N-Look 12pol Reserve I/O & Optional
11. -X34 Mini-Mate.-N-Look 9pol Fan control & monitoring 1
12. -X35 Mini-Mate.-N-Look 9pol Fan control & monitoring 2
13. -X36 Mini-Mate.-N-Look 12pol Security Loop Flap Extension Conveyor
14. -X37 Mini-Mate.-N-Look 15pol Reserve I/O & V3-Connection
15. -X19 Mini-Mate.-N-Look 4pol RS485 FU
7 Power Supply
7.10 I / O Control Unit Distributor
Technical Training FSE SIPLACE TX-Series 01/2018 107
7.10 I / O Control Unit Distributor
X 3 Data Input DI0 to DI7:
DI_0 Safety_Loop_OK "High", when safety loop is closed (all covers,
all tables connected and E-Stop not engaged)
(X22-A3)
DI_1 Reserve (X33-3)
DI_2 E-Stop 2 "Low", when E-Stop 2 is engaged "High", E-Stop not
engaged
(X24-12)
DI_3 Reserve (X31-4)
DI_4 PresSens_PV1Signal from incoming air valve_1. "High": pres-
sure ok.; "Low": pressure too low (<4,5 bar)
(X31-5)
DI_5 PresSens MainValve"High", when the adjusted air pressure
reached
(X31-6)
DI_6 Reserve (X30-4)
DI_7 Reserve
X 4 Data Input DI8 to DI15:
DI_8 Start_Button_1"High" when pressing Start Button 1. (X23-7 / X25-7)
DI_9 Stop_Button_1“High" when pressing Stop Button 1 (X23-8 / X25-8)
DI_10 24V_S "High" when 24V switched status is reached changes from
"Low" to "High when the CSB has the operating voltage and SSK
is activated
(X22-B4 / X25-13
DI_11 Start_Button_2 "High" when pressing Start Button 2 (X24-7)
DI_12 Stop_Button_2 “High" when pressing Stop Button 2 (X24-8)
DI_13 PWR_enabled "High", when the E-Stop circuit is closed, the SSK
is activated and when the safety breakers have been activated
(X22-B3)
DI_14 EMG_Stop_1"Low", when the E-Stop_1 is pressed. Also "High",
E-Stop1 is released
(X23-12)
DI_15 EMG_Stop_Ext option MTC / WPC
X 5 Data Input DI16 to DI23:
DI_16 Button_COTi_2 Signal from Button "COT-Insert"; Location 2.
"High": Button pressed
(X24-9)
DI_17 Hood_2 "High", when the Machine cover _2 is closed "Low",
when Machine cover _2 is open
(K2-A1+ / X25-12
DI_18 Comp_Table_2 "High" when the COT 2 is docked, "Low" when
COT is missing
(X36-2 / X37-13)
DI_19 Hood2_Lock_on "High" Safety switch Hood 2 activated => Cover
cannot be opened
Low": Safety switch Hood 2 not activated => Cover can be
opened
(X27-7)
DI_20 Reserved
DI_21 Reserved
DI_22 Reserved
DI_23 Reserved
7 Power Supply
7.10 I / O Control Unit Distributor
108 Technical Training FSE SIPLACE TX-Series 01/2018
X 6 Data Input DI25 to DI31:
DI_24 Button_COTi_1 Signal from Button "COT-Insert"; Location 1.
"High": Button pressed
(X23-9)
DI_25 Hood_1 "High", when the Machine cover _1 is closed "Low",
when Machine cover _1 is open
(K1-A1+ / X26-6)
DI_25 Comp_Table_1 "High" when the COT 1 is docked, "Low" when
COT is missing
(X36-2 / X37-13)
DI_27 Hood 1_Lock_on "High" Safety switch Hood 1 activated =>
Cover cannot be opened
Low": Safety switch Hood 2 not activated => Cover can be
opened
(X26-7)
DI_28 Reserved
DI_29 S_Flap EXCo option external conveyor
DI_30 Flap lock on option external conveyor
DI_31 ID EX Co option external conveyor
X 18 Data Input DI32 to DI39:
DI_32 Fan_G1 Loc.1 Input for Fan Control: "Low": Fan Revolution is ok;
"High": Fan Revolution is below the threshold value
(X34-1)
DI_33 Fan_G2 Cover-1 Input for Fan Control: "Low": is ok; "High": Fan
Revolution is below the threshold value
(X34-2)
DI_34 Fan_G3 Loc.2 Input for Fan Control: "Low": Fan Revolution is ok;
"High": Fan Revolution is below the threshold value
(X34-3)
DI_35 Fan_G4 Loc.2 Input for Fan Control: "Low": Fan Revolution is ok;
"High": Fan Revolution is below the threshold value
(X34-4)
DI_36 Reserved
DI_37 Fan Power Supply
DI_38 Reserved
DI_39 Reserved
X 7 Data Output DO0 to DO7:
DO_0 Reserved (X37-11)
DO_1 SW_Ctrl_On ("Software release") The machine can only start
when this signal is "High"-Signal (24V OK)
(X23-2 / X24-2
DO_2 Reserved (X31-8)
DO_3 Pressure_PV1 Signal an proportional valve_1. "High": Valve
switches air pressure on; "Low" Valve is not switched
(X31-7 (via R15K))
DO_3 Hood_Lock2 "High" Safety switch locking device an Cover 2 (X27-2)
DO_5 Hood_Lock1 "High" Safety switch locking device an Cover 1 (X26-2)
DO_6 Reserved
DO_7 Interior_light "High"-Interior light ”on” "Low"-Interior light ”off” (X30-7)