3 Converting the power supply on HF machines A ssembly Instructions, Converting the Power Supply 3.4 Modules to be converted 12/2013 Edition 154 3.3.2 Conversion kit for SIPLACE HF , international (3 x 400 V AC) The conv…

Assembly Instructions, Converting the Power Supply 3 Converting the power supply on HF machines
12/2013 Edition 3.1 Tools and equipment
153
3 Converting the power supply on HF machines
This section describes how to convert the power supply units on HF placement machines in order
to adapt them to the supply networks in individual countries.
3.1 Tools and equipment
– Set of DIN 911 Allen keys
– Set of slotted-head screwdrivers
–Multimeter
3.2 Circuit diagrams
– Conversion kit, USA (208 VAC), SIPLACE HF,
drawing no. 00119605-020101LD4, 2 sheets (see page 176
and 177)
– Conversion kit, international, SIPLACE HF,
drawing no. 00354626-060301LD4, 2 sheets (see page 178
and 179)
3.3 Parts
3.3.1 Conversion kit, USA (3 x 208 VAC) for SIPLACE HF, item no. 00119605-02
The conversion kit consists of the following parts:
– ZM-32-PKZ2 motor protection trip block Item no. 00342496-01
– HF cable: machine power supply (USA), Item no. 00345937-01
– Teddy socket guard, 6310 series, white Item no. 00357871-01
– Power supply conversion instructions
for SIPLACE HF/X/D/Di/MTC2/S-27HM/MTC/HS-60 Item no. 00193437-xx
12/2013 Edition, German and English

3 Converting the power supply on HF machines Assembly Instructions, Converting the Power Supply
3.4 Modules to be converted 12/2013 Edition
154
3.3.2 Conversion kit for SIPLACE HF, international (3 x 400 VAC)
The conversion kit consists of the following parts:
– ZM-16-PKZ2 motor protection trip block Item no. 00342495-01
– Power supply conversion instructions
for SIPLACE HF/X/D/Di/MTC2/S-27HM/MTC/HS-60 Item no. 00193437-xx
12/2013 Edition, German and English
3.4 Modules to be converted
The following table lists those modules that have to be converted in order to adapt them to the
power supply network.
The connections for the station computer, LCD screens, uninterruptible power supply and compo-
nent tables need not be changed since they are connected to the placement machine's own 230
VAC system.
Module Sub-module Ratings
Power supply
00354626-xx
Transformer T1
00354630-xx
3 x 415 VAC ± 5%
3 x 400 VAC ± 5%
3 x 380 VAC ± 5%
3 x 230 VAC ± 5%
3 x 208 VAC ± 5%
Inrush current limiter
BRW3TT13084-01
03003056-xx
3 x 415 VAC ± 5%
3 x 400 VAC ± 5%
3 x 380 VAC ± 5%
3 x 230 VAC ± 5%
3 x 208 VAC ± 5%
Motor protection trip block
ZM-16-PKZ2
00342495-xx
3 x 415 VAC ± 5%
3 x 400 VAC ± 5%
3 x 380 VAC ± 5%
Motor protection trip block
ZM-32-PKZ2, USA option
00342496-xx
3 x 230 VAC ± 5%
3 x 208 VAC ± 5%
X102 service socket
Teddy socket guard, 6310 series,
white,
00357871-01
1 x 115 VAC (USA)
Main power cable, 4 mm²
3 x 415 VAC ± 5%
3 x 400 VAC ± 5%
3 x 380 VAC ± 5%
Main power cable (USA), 6 mm²
00345937-xx
3 x 230 VAC ± 5%
3 x 208 VAC ± 5%
Tab. 3 - 1 Modules to be converted

Assembly Instructions, Converting the Power Supply 3 Converting the power supply on HF machines
12/2013 Edition 3.5 Converting the power supply from 3 x 400 VAC to 3 x 208 VAC
155
3.5 Converting the power supply from 3 x 400 VAC to 3 x 208 VAC
RISK OF DEATH 3
Disconnect the machine correctly as described in section 1, page 145.
Disconnect the machine from the main power supply.
Take suitable action to ensure that the machine cannot be connected to the power supply dur-
ing the conversion work.
Put up warning signs to indicate that work is being carried out on the electrical system.
3
3
3