Assembly Instructions, Converting the Power Supply 7 Converting the power supply on the HS-60 / D4 / D1/D2 machine
12/2013 Edition 7.5 Converting the power supply from 3 x 400 VAC to 3 x 208 VAC
235
Fig. 7 - 5 Releasing the yellow locking tab
Fig. 7 - 6 Removing the motor protection trip block MS1A
Use the screwdriver to push up the yellow locking tab (3)
Pull out the motor protection
trip block (4)
7 Converting the power supply on the HS-60 / D4 / D1/D2 machine Assembly Instructions, Converting the Power Supply
7.5 Converting the power supply from 3 x 400 VAC to 3 x 208 VAC 12/2013 Edition
236
7.5.2.2 Inserting the motor protection trip block
Check the type of motor protection trip block before you insert it. The type depends on the op-
erating voltage.
Tab. 7 - 2 Motor protection trip block for 3x208 VAC, 3x230 VAC
7
Check the overcurrent and short-circuit current trip threshold settings.
Adjustment of the Motor protection trip block at 110/208V 7
Tab. 7 - 3 Overcurrent and short-circuit current trip thresholds
Fig. 7 - 7 Checking the overcurrent and short-circuit current trip thresholds
7
Insert the motor protection trip block (3).
Push the yellow locking tab (4) down.
Close the gray protective flap (5).
Turn the rotary switch (6) clockwise as far as the stop.
Main power voltages HS-60 / D4 D1 / D2
3x208 VAC ± 5% ZM-32-PKZ2 ZM-16-PKZ2
3x230 VAC ± 5% ZM-32-PKZ2 ZM-16-PKZ2
Motor protection
trip block
Yellow dial (1) for setting
the overcurrent trip
threshold
Red dial (2) for setting the
short circuit current trip
threshold
HS-60 / D4 ZM-32-PKZ2 24 A 375 A
D1 / D2 ZM-16-PKZ2 16 A 200 A
Check the overcurrent trip
threshold (yellow dial (1))
Check the short-circuit cur-
rent trip threshold
(red dial (2))
Assembly Instructions, Converting the Power Supply 7 Converting the power supply on the HS-60 / D4 / D1/D2 machine
12/2013 Edition 7.5 Converting the power supply from 3 x 400 VAC to 3 x 208 VAC
237
7.5.3 Securing the socket with earthing contact using the socket guard
Insert the Teddy socket guard, series 6310, white (item no.: 00357871-01) into the socket
guard with earthing contact.
7
7.5.4 Replacing the main power cable
CAUTION
The electrical cables to each individual placement machine must be clearly identified and easy to
allocate without doubt. The regulations of the country in which the machine is operated apply.
The main power cable is connected to the U, V, W, N and PE terminals on terminal strip X1 (see
item X1 in Fig 7 - 2
, page 233).
Detach the wires of the main power cable from the U, V, W, N and PE terminals.
Detach the cable clamp from the cable holder.
Pull the cable out of the cable holder.
Push the main power cable (6 mm²) through the cable holder as far as the terminals on X1.
Socket with socket guard