Samsung Component Placer CP45FV Series Maintenance Guide Caution Regenerative resistor which is built in the amplifi er of 15A or 30A does not have a thermostat. Alarm Code 55H (External error) Checking The Selection of …

Inspection of the Controller
Alarm Code 53H (DB overheat)
Operating state when alarm occurred
Possible
causes
When control power supply is turned on High
High
1 Faulty amplifier internal circuit
DB operating frequency is too high.
Use the dynamic brake without
exceeding its allowable frequency by
referring to 9.1.8.
Possible causes
Operating state
3
When control power supply is turned on
During operation Low
Corrective measures
Cause
1 Faulty amplifier internal circuit Replace servo amplifier
2
Operate under the condition that
regenerative electric power is
below the specified capacity.
Use an external regenerative
resistor.
Caution
Operating state
1 2
During operation Low
Corrective measures
Cause Corrective measures
Replace servo amplifier
2
Alarm Code 54H (Internal overheat)
Operating state when alarm occurred
1 2
Low High
High High
Corrective measures
Confirm the specified capacity of
internal regenerative resistor.
Regenerative power is too large.
Faulty wiring of built-in regenerative
resistor
Check wrong wiring and correct it.
3
When using regenerative resistor built in Servo Amplifier,
as Regenerative Resistor type set “built-in regenerative
resistor” to the amplifier exactly.
With this setting, it is decided that overheat protecting
detection of built-in regenerative resistor is effective or
ineffective. In case no regenerative resistor connection or
external regenerative resistor is selected, overheat
detection of built-in regenerative resistor will not function.
7-39

Samsung Component Placer CP45FV Series Maintenance Guide
Caution
Regenerative resistor which is built in the amplifier of 15A
or 30A does not have a thermostat.
Alarm Code 55H (External error)
Checking The Selection of Active Condition under the external trip function, confirm
if the external trip function is active, and also which input is used. Confirm what
function is used for the general purpose input terminal in validity when external trip
is activated
When connect external regenerative thermal
1
When control power supply is turned on High
High Low
Corrective measures
Cause Corrective measures
1
2
External thermal terminal
(external regenerative resistor)
operated.
3
Faulty servo amplifier control
board
Replace servo amplifier
Remove alarm causes in upper system.
Alarm Code 61H (Over voltage)
1
When control power supply is turned on High
When main circuit power supply is turned on High
When motor is started or stopped
High
Detect the error by estimating from regenerative load ratio.
Operating state when alarm occurred
Possible causes
Operating state
2 3
Low
After operating for a short period
Incorrect wiring of external
regenerative resistor.
Check wrong wiring and correct it.
Review operational conditions.
Increase capacity of external
regenerative resistor
When connect output terminal of upper system
Operating state when alarm occurred
Possible causes
Operating state
2 3 4
High
Low High
7-40

Inspection of the Controller
Corrective measures
Cause
1 Faulty amplifier control board Replace servo amplifier.
Reduce voltage to within allowable
range.
3
4
Faulty wiring of connector CND, or
Inner regenerative circuit does not
function.
Wiring regenerative resistor correctly:
Connect regenerative resistor wires to P
and Y terminals of connector CND.
When external regenerative resistor is
used, check wiring and resistance
value. Replace Servo Amplifier if
malfunction persists.
Operating state when alarm occurred
Possible causes
Operating state
2 3 4
After main circuit power supply is turned on High High
During motor operation (alarm can be reset)
Low
During motor operation (alarm can not be
reset)
Corrective measures
1
2 Main circuit rectifier is broken Replace servo amplifier.
Check main power supply not to occur
momentary interruption or power drop.
4
5
Faulty internal circuit of servo
amplifier
Replace servo amplifier
Corrective measures
Power voltage of main circuit is
exceeding allowable voltage
2
Reduce load inertia to within allowable
range.
Load inertia is too large.
Alarm Code 62H (Main circuit short voltage)
1 5
When control power supply is turned on High Low
High
High
Corrective measures
Cause
Power supply voltage is below
specified range
Set power supply to proper voltage
within specified range.
Input voltage dropped. Or
momentary interruption occurred.
3
Check main circuit voltage not to supply
around power from other to R. S. T
when main circuit OFF.
Low voltage without specification is
supplying to main circuit (R.S.T)