80S-15贴片机.pdf - 第240页

7 Components Table S IPLACE 80 S/F/G Servic e Manual Edition 04/97 7 - 58 7.7. 2.1 Checking with the External Power Supply ● Make s ure that th e clam ping cl ips (see F ig. 7.7.2 ) of the c ompress ed air supply m odule…

100%1 / 484
SIPLACE 80 S/F/G Service Manual 7 Components Table
Edition 04/97
7 - 57
7.7 Components Table Pneumatics, Components
Table Compressed Air Supply
7.7.1 Tools and Spare Parts Required
Tools
Screwdrivers for hexagon socket-head cap screws, set
Crosstip screwdrivers, set
Side-cutting pliers
Transparency marker
Auxiliary Measuring and Test Equipment
Service manometer, quick-release coupling from Item No. 00310152-01
(included in the SIPLACE 80 S service case)
Location tester SIPLACE 80, from Item No. 00304770-03
If required, external power supply, from Item No. 00142011-01
Spare Parts
Pressure control valve PWP-B1888, from Item No. 00309633-01
Sealing ring O-M5 PVC rigid, from Item No. 00201148-01
Plastic hose PL-4 PE blue, from Item No. 00047551-01
Cable lacings
Connector plug KS-PK-4-M5, from Item No. 00200243-01
Pneumatics adapter (including o-rings), from Item No. 00306678-01
O-ring 5*1 NBR 70 A, from Item No. 00305213-01
Pressure spring 0,63*5,63*18,5, from Item No. 00305239-01
clamping clip, from Item No. 00305210-01
7.7.2 Fault Location: Control / Functioning of the Compressed Air
Supply Module
NOTE
Error message No. 43 can point to a fault in the compressed air feeder module (= feeder module conveying
using compressed air), in the components table pneumatic system or in the components table compressed air
supply.
Start fault location by referring to the section 7.2 "Fault Characteristics".
Check on the basis of the fault situation - that is, when error No. 43 is displayed - whether the output signal is
present at the corresponding connection socket of the communications unit (= interface of the components
table and the components modules) or whether there is a fault in the module (for example, solenoid valves,
compressed air cylinder defective, electrical interruption in the module).
There are 2 possibilities for fault location:
Checking the module by connecting it to the (new) external power supply - if the customer has this, or
Using the location tester to test at the connection socket of the communications unit.
7 Components Table SIPLACE 80 S/F/G Service Manual
Edition 04/97
7 - 58
7.7.2.1 Checking with the External Power Supply
Make sure that the clamping clips (see Fig. 7.7.2) of the compressed air supply module which is not
transporting correctly is properly closed and the module thus being pressed correctly against the sup-
port strip.
Pull out the plug of the problematic compressed air supply module from the connections panel of the
communications unit. The module remains in place at the components table, the machine switched
on, the compressed air at the feeder module is on.
Connect the module to the external power supply using the 30 VDC socket.
Give the control signal for switching the solenoid valves (in the module) at the corresponding push-
button of the external power supply.
If the module now conveys properly (= solenoid valve in the module switches), continue location
of the electrical interruption in the communications unit (see the section 7.5 "Communications
Unit").
If the module does not now convey, carry out fault correction in the module as described in the
service manual for this module.
7.7.2.2 Testing with the Location Tester:
NOTE:
For a more precise check of locations 1 or 3, or of a particular track, use the SITEST program. Select for
example "BE table"
"Single function"
"Adr. or track "
"Output" and check the outputs at the location
tester which is connected (see text which follows) or test the entire location (tracks 1 to 120) by selecting "BE
table"
"Continuous loop CL"
"Output".
DANGER
OOO
The SITEST program may only be used by authorized persons who have been specially trained in its use at
Siemens AG (please observe the DANGER notes section 7.6.2 on page 7 - 34).
Pull the plug of the compressed air feed module which is not conveying out of the connection socket of the
communications unit. The module remains in place at the components table.
Connect the location tester to the connection socket of the communications unit which is now becoming
free. For detailed information on using the location tester, please refer to the section 7.5 "Communications
Unit".
You must now create the fault once again in order to set the output signal for the feed module.
The assumption here is that when the "Track empty" error message is displayed, the track is not actually
empty but that there is a pick-up error.
When the "Track empty" error message is displayed select: Component feed
Fill all (setter password)
Return. The corresponding track errors will be deleted.
Position the location tester so that you can read it easily. Start the placement sequence and by doing so
generate once more error No. 43. At the same time check the "A1" LED on the location tester:
SIPLACE 80 S/F/G Service Manual 7 Components Table
Edition 04/97
7 - 59
If the "A1" LED is not illuminated, this may indicate an interruption in the communications unit.
Proceed as described in the section 7.5 "Communications Unit".
If the "A1" LED of the location tester is on, this means the control signal is reaching the socket.
A fault in the compressed air feed module can be excluded by connecting it to the external power
supply (see section above), which will mean that there must be a fault in the 5 bar compressed air
branch. Continue work with the following section.
7.7.3 Fault Location and Corr.: Compr. Air Unit and Comp. Table
Pneum. System
If you have already determined that the fault is not in the module or in the communications unit (see pre-
ceding section), select "Abort placement" in order that all of the components are returned which were
picked up at the placement heads during the course of the ensuing reference run. The placement heads
move into the waiting position above the corresponding components loading point.
Remove the cover over the compressed air unit from the machine base (undo 2 special socket-head cap
screws using a size 3 socket spanner).
Check the 5.6 bar operating pressure (see User’s Manual, Section 9).
Check all of the screwed hose connections of the 5 bar compressed air branch which supplies the feed
module:
At the pressure regulating valve of the compressed air unit (see Fig. 7.7.1),
at the block, components table pneumatic system, on the right of the machine base (see Fig. 7.7.1)
and
at the components table compressed air supply (see Fig. 7.1.5 in the section 7.1 "Overview").
If the air is leaking at the block, switch off the machine and replaced the damaged sealing rung (see Fig.
7.7.1).
If there are no leaks at any point up to the connection to the components table compressed air supply,
switch off the machine at the main switch and then undo the threaded hose connection at the pressure
regulating valve of the compressed air unit (for components table pneumatic system connections, see Fig.
7.7.1).
Connect the service manometer by the threaded hose connection directly to the pressure regulating valve.
Switch on the machine at the main switch (the control system remains off). Compressed air is on.
The service manometer must show 5 bar precisely; if it does not, set the correct pressure using the adjust-
ment screw (screwdriver for socket-head screws):
If you cannot get the required 5 bar pressure, replace the pressure regulating valve (after disconnect-
ing the machine from the power supply and compressed air network!).
If the compressed air was at the correct pressure, check the pressure at the block of the components
table pneumatic system (service manometer). If you measure a different value here, switch off the
machine at the main switch and disconnect the machine from the power supply!
DANGER
QQQ
Switch the machine off at the main switch and disconnect it from the power supply.