Page 80 Vision XP+ VAC
3 Setup Instructions
3.3 Conveyor
Operating Instructions
Version 1.5
3.3.3 Chain Lubricator
Fig. 3-8 Chain Lubricator
Always when the Chain Lubricator is activated (impulse duration valve), the
pump pistons are moved once. A constant defined ejection volume is
ejected at the outlet.
If the electric solenoid is de-energized (impulse pause valve), the pump pis-
tons are put into the initial stae through spring force and suck chain oil for
the next ejection.
A) Start the Chain Lubricator manually
The Chain Lubricator is started independently of pause must value.
B) Indication Chain Lubricator active
C) Duration set value
Number of impulses from the conveyor chain for which the Chain Lubri-
cator is active after the pause.
D) Duration actual
Indication of the counted impulses so far.
E) Pause set value
Number of impulses from the conveyor chain for which the Chain Lubri-
cator is not active after the pause.
F) Pause actual value
Indication of the counted impulses so far.
G) Impulse duration valve (time)
Here it can be specified for which time the Chain Lubricator is controlled
with voltage. The default value is 4.
H) Impulse pause valve (pulses)
Here the break between the ejections of the Automatic Chain Lubrication
can be indicated. The entry is in impulses of the conveyor system. The
default value is 60.
G
F
H
B
A
C
D
E

Vision XP+ VAC Page 81
3 Setup Instructions
3.4 Alarm Configuration
Operating Instructions
Version 1.5
3.4 Alarm Configuration
Fig. 3-9 Alarm Configuration
A) Type
Default values are displayed here for the entry of alarm types. Deviations
are machine-specific.
B) t1 (warning time)
Warning time is the delay time which elapses from the point in time at
which an alarm event occurs until the alarm message appears at the
display. The setpoint is entered in seconds.
C) t2 (response time)
Delay time from the point in time at which the alarm message is displayed
(warning time t1) until the alarm is triggered (response time t2) can be
entered under alarm time. Time is entered in seconds.
D) Selection display for Kick Off relay function
If the system ist loaded and an alarm is released when the kick off relay
function ist activated, the system locks the inlet interface an transports
the remaining boards outward which are still in the heating chamber. Dur-
ing the elimination a signal is sent to the subsequent system. Through
this signal the subsequent system is informed which parts are moved out-
ward for exact checking. When all boards are outside of the system, the
inlet
interface is released again an the production run on as usual.
In the alarm mask you can select by which alarms the kick off relay
should release.
A
B
C
D

Page 82 Vision XP+ VAC
3 Setup Instructions
3.4 Alarm Configuration
Operating Instructions
Version 1.5
3.4.1 Possible Alarm Types
Response After Warning Time (t1) or
Response Time (t2)
Response Type
Heat
Drive Unit
Red lamp
Horn
Yellow lamp
Display
Comment
0
-- -- -- -- -- -- Alarm and display deactivated
1
-- -- -- -- -- t1 Alarm message after t1, self-acknowledging, no
action after t2
2
-- -- -- -- t1 t1 Type 1 + yellow after t1, self-acknowledging, no
action after t2
3
-- -- -- t1 t1 t1 Type 2 + horn after t1, self-acknowledging, no
action after t2
4
-- -- t1 t1 t1 t1 Type 3 + red after t1, self-acknowledging, no
action after t2
5 + service
-- -- -- t1 t1 t1 Same as type 2
5 + automatic
t2 -- t1 t1 t1 t1 Type 4 + heat off after t2
11
-- -- -- -- -- t1 Alarm message after t1, self-acknowledging,
can be acknowledged with reset after t2
12
-- -- -- -- t1 t1 Type 11 + yellow after t1, self-acknowledging,
can be acknowledged with reset after t2
13
-- -- -- t1 t1 t1 Type 12 + horn after t1, self-acknowledging, can
be acknowledged with reset after t2
14
-- -- t1 t1 t1 t1 Type 13 + red after t1, self-acknowledging, can
be acknowledged with reset after t2
15 + service
-- -- -- t1 t1 t1 Same as type 12
15 + automatic
t2 -- t1 t1 t1 t1 Same as type 16
16
t2 -- t1 t1 t1 t1 Type 14 + heat off after t2
17
t2 t2 t1 t1 t1 t1 Type 16 + heat and conveyor off after t2
23
-- -- -- t1 t1 t1 Type 12 + horn after t1
Can be acknowledged manually after t1 has
elapsed, and the error must be eliminated after
t2 has elapsed.