Page 82 Vision XP+ V AC 3 Setup Instructions 3.4 Alarm Configuration Operating Instructions V ersion 1.5 3.4.1 Possible Alarm T ypes Response After W arning T ime (t1) o r Response T ime (t2) Response T ype Heat Drive Un…

100%1 / 142
Vision XP+ VAC Page 81
3 Setup Instructions
3.4 Alarm Configuration
Operating Instructions
Version 1.5
3.4 Alarm Configuration
Fig. 3-9 Alarm Configuration
A) Type
Default values are displayed here for the entry of alarm types. Deviations
are machine-specific.
B) t1 (warning time)
Warning time is the delay time which elapses from the point in time at
which an alarm event occurs until the alarm message appears at the
display. The setpoint is entered in seconds.
C) t2 (response time)
Delay time from the point in time at which the alarm message is displayed
(warning time t1) until the alarm is triggered (response time t2) can be
entered under alarm time. Time is entered in seconds.
D) Selection display for Kick Off relay function
If the system ist loaded and an alarm is released when the kick off relay
function ist activated, the system locks the inlet interface an transports
the remaining boards outward which are still in the heating chamber. Dur-
ing the elimination a signal is sent to the subsequent system. Through
this signal the subsequent system is informed which parts are moved out-
ward for exact checking. When all boards are outside of the system, the
inlet
interface is released again an the production run on as usual.
In the alarm mask you can select by which alarms the kick off relay
should release.
A
B
C
D
Page 82 Vision XP+ VAC
3 Setup Instructions
3.4 Alarm Configuration
Operating Instructions
Version 1.5
3.4.1 Possible Alarm Types
Response After Warning Time (t1) or
Response Time (t2)
Response Type
Heat
Drive Unit
Red lamp
Horn
Yellow lamp
Display
Comment
0
-- -- -- -- -- -- Alarm and display deactivated
1
-- -- -- -- -- t1 Alarm message after t1, self-acknowledging, no
action after t2
2
-- -- -- -- t1 t1 Type 1 + yellow after t1, self-acknowledging, no
action after t2
3
-- -- -- t1 t1 t1 Type 2 + horn after t1, self-acknowledging, no
action after t2
4
-- -- t1 t1 t1 t1 Type 3 + red after t1, self-acknowledging, no
action after t2
5 + service
-- -- -- t1 t1 t1 Same as type 2
5 + automatic
t2 -- t1 t1 t1 t1 Type 4 + heat off after t2
11
-- -- -- -- -- t1 Alarm message after t1, self-acknowledging,
can be acknowledged with reset after t2
12
-- -- -- -- t1 t1 Type 11 + yellow after t1, self-acknowledging,
can be acknowledged with reset after t2
13
-- -- -- t1 t1 t1 Type 12 + horn after t1, self-acknowledging, can
be acknowledged with reset after t2
14
-- -- t1 t1 t1 t1 Type 13 + red after t1, self-acknowledging, can
be acknowledged with reset after t2
15 + service
-- -- -- t1 t1 t1 Same as type 12
15 + automatic
t2 -- t1 t1 t1 t1 Same as type 16
16
t2 -- t1 t1 t1 t1 Type 14 + heat off after t2
17
t2 t2 t1 t1 t1 t1 Type 16 + heat and conveyor off after t2
23
-- -- -- t1 t1 t1 Type 12 + horn after t1
Can be acknowledged manually after t1 has
elapsed, and the error must be eliminated after
t2 has elapsed.
Vision XP+ VAC Page 83
3 Setup Instructions
3.4 Alarm Configuration
Operating Instructions
Version 1.5
Tab. 3-1 Alarm Types
24
-- -- t1 t1 t1 t1 Type 23 + red after t1
Can be acknowledged manually after t1 has
elapsed, and the error must be eliminated after
t2 has elapsed.
26
t2 -- t1 t1 t1 t1 Type 24 + heat off after t2
Can be acknowledged manually after t1 has
elapsed, and the error must be eliminated after
t2 has elapsed.
27
t2 t2 t1 t1 t1 t1 Type 26 + heat and conveyor off after t2
Can be acknowledged manually after t1 has
elapsed, and the error must be eliminated after
t2 has elapsed.
33 -- -- -- t1 t1 t1 Type 3
Can be acknowledged manually after t1 has elapsed
no action after t2
Seconds are entered for t1 and t2. Minutes are only entered for t2 in the case of alarm types 23,
24, 26 and 27.
If the horn is acknowledged during t2, it sounds once again after t2 has elapsed. With an alarm type 33 never
enter Zero in t2.
Two-digit response types must be acknowledged in any event after t2 has elapsed and the error
has been eliminated, even if the horn has been previously acknowledged.
If response types other than those shown above are entered, the same response is triggered as
for response type 17!
Response After Warning Time (t1) or
Response Time (t2)
Response Type
Heat
Drive Unit
Red lamp
Horn
Yellow lamp
Display
Comment