Option ‑ 126 ‑ containing a PE conductor. The shield of the shielded cable consists of coaxial cooper braids to suppress radio frequency interference. The braided density of the cooper braid should be greater than 90% to…

Option
‑125‑
Table 12–19 Dimensions of the magnetic ring
Model
Dimensions (OD × ID × HT) (mm)
DY644020H 64 × 40 × 20
DY805020H 80 × 50 × 20
DY1207030H 120 × 70 × 30
Figure 12‑15 Dimensions of the ferrite clamp (unit: mm)
12.9 Cable
12.9.1Main circuit cable
Power cable selection requirements
For selection of power cables, follow national or regional regulations. Select IEC cables
according to the following requirements:
● Compliant with EN 60204-1 and IEC 60364-5-52 standards
● PVC insulated cables with copper conductors
● Heat resistance: maximum cable surface temperature not exceeding 70°C at an
ambient temperature of 40°C (Note: Contact the manufacturer when the ambient
temperature exceeds 40°C.)
● Symmetric cable with copper-braided shield
If the recommended cables for peripheral equipment or options are not suitable for the
product, contact Inovance.
To comply with the EMC standards, use shielded cables. Shielded cables are classified
into the three-conductor cables and four-conductor cables, as shown in the following
figure. If a three-conductor cable is used but its shield cannot provide sufficient
conductivity, add an independent PE cable. Alternatively, use a four-conductor cable

Option
‑126‑
containing a PE conductor. The shield of the shielded cable consists of coaxial cooper
braids to suppress radio frequency interference. The braided density of the cooper braid
should be greater than 90% to enhance the shielding efficiency and conductivity.
Figure 12‑16 Recommended power cable types
Recommended cable
Table 12–20 Cable selection (single-phase 200 V to 240 V, compliant with CE certification)
Single-phase 200 V to 240 V
AC drive model Power
(kW)
Rated
input
cur
rent
(A)
Rated
out
put
cur
rent
Braking
current
(A)
RST/UVW Grounding cable Braking terminal
Recom
mended
cable
type
(mm
2
)
[1]
Rec
om
mend
ed
termi
nal
model
Recom
mended
cable
type
(mm
2
)
[1]
Recom
mended
termi
nal
model
Recom
mended
cable
type
(mm
2
)
[1]
Recom
mended
terminal
model
MD600S/A-2S2R8(B) 0.37 6.2 2.8 0.71 3x0.75 E7510 0.75 E7510 0.75 E7510
MD600S/A-2S2R8 0.37 6.2 2.8 No
braking
3x0.75 E7510 0.75 E7510 / /
MD600S/A-2S4R6(B) 0.75 10.2 4.6 1.43 3x1 E1010 1 E1010 0.75 E7510
MD600S/A-2S4R6 0.75 10.2 4.6 No
braking
3x1 E1010 1 E1010 / /
MD600S/A-2S7R5(B) 1.5 16.6 7.5 2.87 3x2.5 E2510 2.5 E2510 0.75 E7510
MD600S/A-2S7R5 1.5 16.6 7.5 No
braking
3x2.5 E2510 2.5 E2510 / /
MD600S/A-2S010(B) 2.2 22.2 10 4.2 3x4 E4012 4 E4012 0.75 E7510
MD600S/A-2S010 2.2 22.2 10 No
braking
3x4 E4012 4 E4012 / /
Notes:
[1]: Chinese standards applicable; 3 x 4: one three-conductor cable with a cross sectional area of 4 mm
2
. It is
recommended to use the tube pre-insulated lugs (TG-JT type) produced by Zhejiang KISE Terminal Co., Ltd.
1. Observe the local regulations during selection. The cables recommended in the preceding table meet the following
conditions:PVC insulation and copper conductor. Heat resistance: maximum cable surface temperature not
exceeding 70°C at an ambient temperature of 40°C (Remark: When the ambient temperature exceeds 40°C, contact
Inovance.) Cable layout type E is adopted (see IEC 60204-1).
2. If the conditions vary, select the model according to actual conditions.

Option
‑127‑
Table 12–21 Cable selection (three-phase 380 V to 480 V, compliant with CE certification)
Three-phase 380 V to 480 V
AC drive model Power
(kW)
Rated
input
cur
rent
(A)
Rated
out
put
cur
rent
Braking
current
(A)
RST/UVW Grounding cable Braking terminal
Recom
mend
ed
cable
type
(m
m
2
)
[1]
Rec
om
mend
ed
termi
nal
model
Recom
mend
ed
cable
type
(m
m
2
)
[1]
Recom
mended
terminal
model
Recom
mended
cable type
(mm
2
)
[1]
Recom
mended
terminal
model
MD600S/A-4T1R6(B) 0.37 1.9 1.6 0.34 3x0.75 E7510 0.75 E7510 0.75 E7510
MD600S/A-4T1R6 0.37 1.9 1.6 No
braking
3x0.75 E7510 0.75 E7510 / /
MD600S/A-4T2R3(B) 0.75 2.8 2.3 0.7 3x0.75 E7510 0.75 E7510 0.75 E7510
MD600S/A-4T2R3 0.75 2.8 2.3 No
braking
3x0.75 E7510 0.75 E7510 / /
MD600S/A-4T4R8(B) 1.5 5.9 4.8 1.4 3x0.75 E7510 0.75 E7510 0.75 E7510
MD600S/A-4T4R8 1.5 5.9 4.8 No
braking
3x0.75 E7510 0.75 E7510 / /
MD600S/A-4T5R5(B) 2.2 6.7 5.5 2.05 3x0.75 E7510 0.75 E7510 0.75 E7510
MD600S/A-4T5R5 2.2 6.7 5.5 No
braking
3x0.75 E7510 0.75 E7510 / /
MD600S/A-4T9R5(B) 4 11.6 9.5 3.72 3x1.5 E1512 1.5 E1512 0.75 E7510
MD600S/A-4T9R5 4 11.6 9.5 No
braking
3x1.5 E1512 1.5 E1512 / /
MD600S/A-4T013(B) 5.5 15.8 13 5.12 3x2.5 E2512 2.5 E2512 0.75 E7510
MD600S/A-4T013 5.5 15.8 13 No
braking
3x2.5 E2512 2.5 E2512 / /
Notes:
[1]: Chinese standards applicable; 3 x 4: one three-conductor cable with a cross sectional area of 4 mm2. It is
recommended to use the tube pre-insulated lugs (TG-JT type) produced by Zhejiang KISE Terminal Co., Ltd.
1. Observe the local regulations during selection. The cables recommended in the preceding table meet the following
conditions:PVC insulation and copper conductor. Heat resistance: maximum cable surface temperature not
exceeding 70°C at an ambient temperature of 40°C (Remark: When the ambient temperature exceeds 40°C, contact
Inovance.) Cable layout type E is adopted (see IEC 60204-1).
2. If the conditions vary, select the model according to actual conditions.
12.9.2Control Circuit Cables
Note
Wire the control circuit cable according to EN 60204-1.