5. Spindle Adjustment 5 - 3 5-1-2 Setting the output data No. Abbr. Parameter name Explanation SP253 DA1NO D/A output channel 1 data No. Input the No. of the data to be output to each D/A output channel. SP254 DA2NO D/A …

5. Spindle Adjustment
5 - 2
5-1 D/A output specifications for spindle drive unit
The MDS-C1-SP/SPH/SPX/SPHX/SPM spindle drive unit has a function to D/A output each control
data. The spindle adjustment data requi red to set the spindle pa rameters match ing the machine ca n be
D/A output. The data can be measured with a hi-corder or oscilloscope, etc.
5-1-1 D/A output specifications
Item Explanation
No. of channels 2ch
Output cycle 444µs (min. value)
Output precision 8bit
Output voltage range
0V to +5V (zero) to +10V,
0V to +10V for meter output
Output magnification
setting
±1/256 to ±128-fold
Output pin
CN9 connector
MO1 = Pin 9
MO2 = Pin 19
GND = Pin 1
Function
Phase current feedback output function
U phase current FB : Pin 7
V phase current FB : Pin 17
MO19
Name
LG
UIFB
2
5
1
Pin
6
4
3
10
7
8
CN9 connector
MO2 19
Name
VIFB
12
15
11
Pin
16
14
13
20
17
18

5. Spindle Adjustment
5 - 3
5-1-2 Setting the output data
No. Abbr. Parameter name Explanation
SP253 DA1NO
D/A output channel 1 data No.
Input the No. of the data to be output to each D/A output channel.
SP254 DA2NO
D/A output channel 2 data No.
No. Output data Ori ginal data unit
Output magnification
standard setting value
(SP255, SP256)
Output unit for
standard setting
Output
cycle
ch1: Speedometer output 10V=max. speed (Zero=0V) 0
Depends on maximum
speed
3.55ms
0
ch2: Load meter output 10V=120% load (Zero=0V) 0 30-minute rating 12%/V 3.55ms
1 –
2 Current command Rated 100%=4096 8 30-minute rating 20%/V 3.55ms
3 Current feedback Rated 100%=4096 8 30-minute rating 20%/V 3.55ms
4 Speed feedback r/min 13 500rpm/V 3.55ms
5 –
6
Position droop
(lower order 16bit)
0.001deg=64 10 (10.24) 0.01deg/V 888µs
7
Position droop
(higher order 16bit)
1deg=(64000÷65536)
671 10deg/V 888µs
8
Feedrate (F∆T)
(lower order 16bit)
0.001deg=64
173
(at 3.5ms communication)
10deg/min/V 888µs
9
Feedrate (F∆T)
(higher order 16bit)
1deg=(64000÷65536)
629
(at 3.5ms communication)
500rpm/V 888µs
10
Position command
(lower order 16bit)
0.001deg=64 10 (10.24) 0.01deg/V 888µs
11
Position command
(higher order 16bit)
1deg=(64000÷65536)
19 (18.64) 360deg/V 888µs
12
Position FB
(lower order 16bit)
0.001deg=64 10 (10.24) 0.01deg/V 888µs
13
Position FB
(higher order 16bit)
1deg=(64000÷65536)
19 (18.64) 360deg/V 888µs
80 Control input 1
81 Control input 2
82 Control input 3
83 Control input 4
84 Control output 1
HEX Bit correspondence 3.55ms
85 Control output 2
86 Control output 3
87 Control output 4

5. Spindle Adjustment
5 - 4
5-1-3 Setting the output magnification
(1) Meter output (Data No. 0)
With meter output, the output channel is fixed, and the output voltage range is 0 to 10V in the
positive range. Set the magnification with the following parameters. Also, low path filter can be set
on the load meter output.
No. Abbr. Parameter name Details
Setting
range
Standard
SP017 TSP* Maximum motor
speed
Set the maximum spindle motor speed.
When SP249=0, the motor speed will be the motor rotation
speed at the speedometer 10V output.
1 to 32767
(r/min)
6000
SP094 LMAV* Load meter output
filter
Set the filter time constant of load meter output.
When "0" is set, a filter time constant is set to 100ms.
0 to 32767
(2ms)
0
SP249 SMO Speedometer speed Set the motor rotation speed when the speedometer 10V is
output.
When set to "0", this parameter becomes the same as SP017
(TSP).
0 to 32767
(r/min)
0
SP250 LMO Load meter voltage Set the voltage when the load meter 120% is output. When set
to "0", this becomes 10V.
0 to 10
(V)
0
(2) Internal data output (D at a No. 1 to 13)
Normally, the standard setting value is set for the output magnification (SP255, SP256). When
"0" is set, the magnification will be the same as "256".
DATA ×
SP255
256
×
10 [V]
256
(
8 bit
)
+ 5 [V] (offset) = Output voltage [V]
(Example) To output current FB at a 30-minute stall rating 20%/V unit (SP253=3, SP255=8)
819.2 ×
8
256
×
10
256
+ 5 = 6 [V]
No. Abbr. Parameter name Details
Setting
range
Standard
SP255 DA1MPY DA output channel 1
magnification
0
SP256 DA2MPY DA output channel 2
magnification
Set the output magnification with a 1/256 unit.
When "0" is set, the magnification will be the same as "256".
-32768 to
32767
(1/256-fold)
0