Appendix 2. Compliance to EC Directives
A2 - 2
Appendix 2-1 Compliance to EC Directives
Appendix 2-1-1 European EC Directives
In the EU Community, the attachment of a CE mark (CE marking) is mandatory to indicate that the basic
safety conditions of the Machine Directives (issued Jan. 1995), EMC Directives (issued Jan. 1996) and
the Low-voltage Directives (issued Jan. 1997) are satisfied. The machines and devices in which the
servo and spindle drive are assembled are the targets for CE marking.
(1) Compliance to EMC Directives
The servo and spindle drive are components designed to be used in combination with a machine or
device. These are not directly targeted by the Directives, but a CE mark must be attached to
machines and devices in which these components are assembled. The next section "EMC
Installation Guidelines", which explains the unit installation and control panel manufacturing
method, etc., has been prepared to make compliance to the EMC Directives easier.
(2) Compliance to Low-voltage Directives
The MDS-C1 Series units are targeted for the Low-voltage Directives. An excerpt of the precautions
given in this specification is given below. Please read this section thoroughly before starting use.
A Self-Declaration Document has been prepared for the EMC Directives and Low-voltage
Directives. Contact Mitsubishi or your dealer when required.
Appendix 2-1-2 Cautions for EC Directive compliance
Use the Low-voltage Directive compatible parts for the servo/spindle drive and servo/spindle motor. In
addition to the items described in this instruction manual, observe the items described below.
(1) Configuration
Use a type B (AC/DC detectable type) breaker
Isolating
transformer
Circuit breaker
AC reactor
Electromagnetic
contactor
Drive unit
CB
MC
M
(2) Environment
Use the units under an Overvoltage Protection Category III and Pollution Class of 2 or less
environment as stipulated in IEC60664.
Install the servo/spindle drive unit in a control panel having a structure (IP54 or higher) in which
water, oil, carbon or dust cannot enter.
Drive unit Motor
During
operation
Storage
During
transportation
During
operation
Storage
During
transportation
Ambient
temperature
0°C to 55°C
-15°C to
70°C
-15°C to 70°C
Ambient
temperature
0°C to 40°C -15°C to 70°C -15°C to 70°C
Humidity
90%RH or
less
90%RH or
less
90%RH or less Humidity
80%RH or
less
90%RH or
less
90%RH or
less
Altitude
1000m or
less
1000m or
less
10000m or
less
Altitude
1000m or
less
1000m or
less
10000m or
less
Appendix 2. Compliance to EC Directives
A2 - 3
(3) Power supply
[1] If a control power supply of the drive unit is 200V, use the power supply under an Overvoltage
Protection Category II as stipulated in IEC60664. In that case, insert a star-connection
isolation transformer that is compliant with EN or IEC Standard into the primary input power
supply of the drive unit.
[2] Do not omit the circuit breaker and electromagnetic contactor.
(4) Earthing
[1] To prevent electric shocks, always connect the servo/spindle drive unit protective earth (PE)
terminal (terminal with
mark) to the protective earth (PE) on the control panel.
[2] When connecting the earthing wire to the protective earth (PE) terminal, do not tighten the
wire terminals together. Always connect one wire to one terminal.
PE terminal
PE terminal
(5) Wiring
[1] Always use crimp terminals with insulation tubes so that the connected wire does not contact
the neighboring terminals.
Crim p termi nal
Insul ation tube
Wire
[2] Do not connect the wires directly.
Appendix 2. Compliance to EC Directives
A2 - 4
(6) Selecting the wire size for EC Directive compliance
To comply with the EC Directives, select the wire size from the following table using each drive
unit's capacity as a reference.
The wire types are as follow.
PVC : Polyvinyl chloride
EPR : Ethylene polypropylene
SIR : Silicon rubber
[1] MDS-C1-CV (L1, L2, L3, PE) (The unit sizes are all mm
2
)
Type (MDS-C1-) CV-37 CV-55 CV-75 CV-110 CV-150 CV-185 CV-220 CV-260 CV-300 CV-370
PVC 2.5 2.5 4 6 10 16 25 35 50 70
EPR 1.5 2.5 4 6 10 16 25 35 35 50
Wire
SIR
1.0 1.5 2.5 4 6 10 16 16 25 25
Terminal screw size M4 M5 M8
[2] MDS-C1-SP (U, V, W, PE)
Type (MDS-C1-)
SP-04 SP-075 SP-15 SP-22 SP-37 SP-55 SP-75 SP-110 SP-150 SP-185 SP-220 SP-260 SP-300
PVC 1.0 1.0 1.0 1.0 1.5 2.5 4 6 10 16 25 35 70
EPR 1.0 1.0 1.0 1.0 1.5 2.5 4 6 10 16 25 35 50
Wire
SIR
1.0 1.0 1.0 1.0 1.0 1.0 2.5 4 6 10 10 16 25
Terminal screw size M4 M5 M8
[3] MDS-C1-V1/V2 (U, V, W, PE)
Type (MDS-C1-) V1-01 V1-03 V1-05 V1-10 V1-20 V1-35 V1-45 V1-70 V1-90 V1-110 V1-150
PVC 1.0 1.0 1.0 1.0 1.5 2.5 4 6 10 25 35
EPR 1.0 1.0 1.0 1.0 1.0 1.5 4 6 10 16 25
Wire
SIR
1.0 1.0 1.0 1.0 1.0 1.0 2.5 2.5 4 10 16
Terminal screw size M4 M5 M8
[4] Wire size for L11 and L21 link bar
Select a 1.5mm
2
wire or larger regardless of the capacity. (This also applies to the wire
between NFB-L11 and L21.)
[5] Wire size for L+ and L- link bar (For unified sizes)
Type (MDS-C1-) CV-37 CV-55 CV-75 CV-110 CV-150 CV-185 CV-220 CV-260 CV-300 CV-370
PVC 2.5 2.5 6 10 16 25 35 50 70 -
EPR 1.5 2.5 4 10 16 25 35 35 70 70
Wire
SIR
1.0 1.5 2.5 4 10 10 16 25 35 35
Terminal screw size M6
* The wire sizes in the above table comply with EN60204 under the following conditions.
Ambient temperature 40°C
Wire laid along wall or in open cable tray
When using under other conditions, refer to EN60204 Appendix 5 and Appended Material C.