UV-9+Cure+Module+7269348_B+Manual.pdf - 第43页

Table 3-2 Electrical Specifications Characteristic Voltage 400Vac Installed Power Top lamp (kW) 7 Installed Power Top and B ottom Lam p (kW) 14 Mode N+EARTH, TT or TN CAUTION! The UV - 9 Cure Module is not compatibl e wi…

100%1 / 142
3.8 Connecting the Power
CAUTION! This procedure should only be performed by a trained service technician.
Tools and Materials Needed:
Facility Main Power and Ground Cables
Key to Electronics Enclosure
To connect the power cables:
NOTE The main power inlet must be directly connected to the main switch inside the electrical
cabinet.
1. Ensure the facility power switch is locked out and tagged out. See 2.12 Lockout/Tagout of
Electrical Energy.
2. Turn the Main Power Switch located at the back of the UV Cure Module to the
OFF (0)
position.
Figure 3-6 Main Power Switch
3. If necessary, unlock the electronics enclosure door (Figure 1-1) using the key provided.
4. Install a circuit breaker on the main power inlet to isolate the oven during maintenance.
Table 3-1 Circuit Breaker Specifications
Circuit
Breaker
Recommended
Cable Section
Recommended
Cable Length
Differential
One UV module 20A 4mm² / AWG10 10 meters + GFCI over 100 mA
Two UV modules 32A 6mm² / AWG8 10 meters + GFCI over 100 mA
CAUTION! The UV-9 Cure Module and Upstream/Downstream equipment must be properly
grounded.
3-6 Installation
Table 3-2 Electrical Specifications
Characteristic
Voltage 400Vac
Installed Power Top lamp (kW) 7
Installed Power Top and Bottom Lamp (kW) 14
Mode N+EARTH, TT or TN
CAUTION! The UV-9 Cure Module is not compatible with Neutral IT.
5. Feed the facility power cable through the main power inlet on the rear panel of the UV-9.
6. Locate and connect facility power cable leads to the Main Circuit Breaker and the green
ground lead to the ground terminal.
7. Close and lock the electronics enclosure door.
8. Turn the Main Power Switch to the
ON (I) position.
9. Remove all locks and tags from facility power and turn the power ON.
3.9 Connecting SMEMA Cables
To connect the SMEMA cables:
1. Locate the upstream and downstream SMEMA communication cables and connect them to
the SMEMA communication ports on the rear panel of the UV-9 Cure Module.
2. Connect the other end of the cables to the SMEMA communications ports on the upstream
and downstream machines.
3.10 Connecting the PLC to Upstream Equipment
It is necessary (unless the UV-9 Cure Module has a touch screen) to connect the PLC to the computer of
the upstream equipment. An Ethernet cable is provided with the UV-9 for this purpose. See Figure 3-7.
Figure 3-7 PLC Connection
Installation 3-7
3.11 Connecting the Exhaust
Tools and Materials Needed
254 mm (10 in.) Duct
Exhaust Blower
Auxiliary Fan (if duct is over 5 meters in length)
To connect the exhaust duct:
NOTE The customer must provide the exhaust blower and associated ductwork.
1. Install the facility ventilation duct on the UV-9 Cure Module exhaust port and clamp in place.
The UV-9 Cure Module has one internal blower per module. The internal blower is
sufficient if the duct length from the UV-9 toward the outside is under 5 meters.
2. If the duct is over 5 meters in length, install an auxiliary fan.
Table 3-3 lists internal and extraction exhaust flow rates.
Table 3-3 Exhaust Flow Rates
Exhaust
1 lamp (m
3
/h)
Exhaust
2 lamps (m
3
/H)
UV-9 Cure Module
(internal blowers)
0-450
± 15%
0-900
± 15%
Extraction flow rate in UV-9
facility exhaust duct
550
± 5%
1100
± 5%
NOTE The extraction flow rate must be measured in the UV-9 exhaust duct with the UV-9 Cure
Module on and at full power.
Sufficient exhaust flow is required to cool the UV lamp. The internal blowers are driven by an inverter to
adjust the cooling. Two flaps, mounted next to the exhaust port, operate as a differential to ensure proper
cooling to the UV source. Make sure not to block the flaps. They must move freely.
Figure 3-8 Exhaust Port
WARNING! CAUTION!
An external dry contact is required. This dry contact must be positive for
extraction and negative when it is turned off. An insufficient extraction flow rate
can cause a lamp default and components to overheat. If an external contact is not
used, the warranty is null and void.
3-8 Installation