drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第106页

86 MEMO

100%1 / 199
Temperature Input Units GT1-TS04@ 85
Temperature Input Units
GT1-TS04@
Temperature Input Units for use with MULTIPLE I/O TERMINAL
Four inputs.
Thermocouples and platinum resistance thermometer models
are available.
Conversion time is only 250 ms for 4 inputs.
The Configurator can be used to calibrate temperatures.
The circuit section can be removed, so rewiring isn’t required
during maintenance.
DIN track mounting.
Dimensions (Unit: mm)
Ordering Information
General Specifications
Input Specifications
* K or T below -100°C: +2°C ±1 digit max. L: ±2°C ±1 digit max.
R or S below 200°C: ±3°C ±1 digit max. B below 400°C: No standard set
I/O classification I/O points
I/O
connections
Power supply
voltage
Input specification Model
Temperature inputs 4 inputs Terminal Block 24 VDC
Thermocouple GT1-TS04T
Platinum resistance
thermometer
GT1-TS04P
I/O power supply voltage 20.4 to 26.4 VDC (24 VDC -15%/+10%)
Current consumption
I/O Unit interface Internal power supply
50 mA max. 80 mA max.
Vibration resistance 10 to 150 Hz, 0.7-mm amplitude or 50 m/s
2
Shock resistance 150 m/s
2
Dielectric strength 500 VAC
Mounting method DIN 35 mm-track mounting
Ambient operating temperature -10°C to 55°C
Ambient operating humidity 25% to 85% (with no condensation)
Ambient storage temperature -25°C to 65°C
Accessories I/O Unit Connecting Cable (40 mm)
Item Model GT1-TS04T GT1-TS04P
Input type
R, S, K, J, T, L, or B
selectable
Pt100 or Jpt100 selectable
Indicator accuracy
(
±0.3% of
indication value or
±1°C, whichever is
larger) ±1 digit
max. *
-200.0 to 650.0
°C
input range:
(±0.3% of indication value or ±0.8°C, whichever is larger) ±1 digit max.
-200 to 200
°C
input range:
(±0.3% of indication value or ±0.5°C, whichever is larger) ±1 digit max.
Conversion cycle 250 ms/4 points
Temperature
conversion data
Binary data
Insulation method
Between input and communication lines: Photocoupler insulation
Between temperature input signals: Photocoupler insulation
Wiring Diagrams
GT1-TS04T
GT1-TS04P
Thermocouple input
24 VDC
internal circuit
power supply
NC
NC
Input 3
+
Input 3
NC
NC
Input 2
+
Input 2
NC
NC
Input 1
+
Input 1
NC
NC
Input 0
+
Input 0
+
Platinum resistance
thermometer input
24 VDC
internal circuit
power supply
NC
Input 3
A
Input 3
B
Input 3
B
NC
Input 2
A
Input 2
B
Input 2
B
NC
Input 1
A
Input 1
B
NC
Input 0
A
Input 0
B
Input 1
B
Input 0
B
GT1-TS04T
GT1-TS04P
GT1-TS04T
IN
80
65
4
80
60
4
65
12.6
35
(Example: GT1-TS04T)
Note: Accessory cable included.
86
MEMO
87
Intelligent Slaves (PLC Units)
Programmable Slaves ..................................................................................... 88