drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第116页

96 DeviceNet-compliant Digital Indicators K3HB- @ -DRT DeviceNet-compli ant Digital Indicators K3HB- @ -DRT Digital Indicators Ideal for Measurement Displays and Judgment of Analog Levels, Such as Voltage Signals, Curren…

100%1 / 199
DeviceNet ID Slave V680-HAM42-DRT 95
DeviceNet ID Slave
V680-HAM42-DRT
DeviceNet-compliant ID System for
Reduced Wiring
• Read and write up to 58 bytes.
Addresses to access can be set from the Master.
Ordering Information
General Specifications
Performance Specifications
System Configuration
Dimensions (Unit: mm)
Name Model
DeviceNet ID Slave V680-HAM42-DRT
Item Model V680-HAM42-DRT
Power supply voltage 24 VDC (-15% to 10%) including 10% ripple (p-p)
Power consumption
4 W max. (Current consumption of 200 mA max. at
power supply voltage of 24 VDC)
Ambient operating
temperature
-10°C to 55°C (with no icing)
Ambient storage
temperature
25°C to 65°C (with no icing)
Ambient operating
humidity
25% to 85% (with no condensation; ambient operating
temperature is 40°C max. at humidity of 85%)
Insulation resistance
20 M min. (at 500 VDC) between all terminals
excluding the ground terminal and the case
Dielectric strength
1,000 VAC (50/60 Hz) for 1 minute between all terminals
excluding the ground terminal and the case
Vibration resistance
10 to 150 Hz, 0.2-mm double amplitude at 15 m/s
2
acceleration with 10 sweeps in X, Y and Z directions for
8 minutes each
Shock resistance
150 m/s
2
in X, Y, and Z directions 3 times each
(18 times in total)
Dimensions 65 x 65 x 65 mm (excluding protrusions)
Degree of protection IP20 (IEC 60529)
Materials Polycarbonate (PC) resin, ABS resin
Weight Approx. 150 g
Mounting method
DIN track mounting
Item Specifications
No. of connectable
antennas
One channel
Connectable Antennas V680-HS51,V680-HS52, V680-HS63, V680-HS65
Item Model V680-HAM42-DRT
DeviceNet Master Unit DeviceNet Master Unit
Programmable
Controller
Programmable
Controller
DeviceNet ID Slave
V680-HAM42-DRT
Antenna
V680-H@@
ID Tag
V680-D@@
Production
line
Operation indicator
Data indicator
5
7
5 23.
22 6.
).3(
21
65
20
10
5
5
16
4
1.5
65
Node address
switches
Node address switches
Antenna connector port
12
6
18
DeviceNet connector
Power supply connector
5.06
21.5
65
20.5
35
1 84.
28.5
V680-HAM42-DRT
96 DeviceNet-compliant Digital Indicators K3HB-@-DRT
DeviceNet-compliant Digital Indicators
K3HB-@-DRT
Digital Indicators Ideal for
Measurement Displays and
Judgment of Analog Levels, Such as
Voltage Signals, Current Signals, and
Temperatures
High-precision, high-speed sampling.
Measurement resolution of 0.01°C and sampling of 50 times per second.
High-visibility negative-transmissive LCD with bright backlight.
Present values and deviations are displayed using a bar graph.
Compliant with CE and UL standards as well as RoHS.
Ordering Information
Name Appearance Specifications Model
DeviceNet-compliant Digital Indicators
Process Indicator
K3HB-XVD-A-DRT1
K3HB-XAD-A-DRT1
K3HB-XVA-DRT1
K3HB-XAA-DRT1
Weighing Indicator
K3HB-VLC-B-DRT1
K3HB-VLC-E-DRT1
Temperature Indicator K3HB-HTA-DRT1
Linear Sensor Indicators K3HB-SSD-A-DRT1
Rotary Pulse Indicator K3HB-RNB-A-DRT1
Timer Interval Indicator K3HB-PNB-A-DRT1
Up/Down Counting Pulse Indicator K3HB-CNB-A-DRT1
DeviceNet-compliant Digital Indicators K3HB-@-DRT 97
Ratings
K3HB-X/V/H/S
* DeviceNet only.
Power supply voltage
100 to 240 VAC Models
100 to 240 VAC (50/60 Hz)
DeviceNet power supply: 24 VDC
Allowable power supply voltage range 85% to 110% of the rated power supply voltage
Power consumption 100 to 240 VAC Models: 18 VA max., 24 VAC/VDC Models: 11 VA, 7 W max.
Absolute maximum
rated input
S Model
0 to 5V ±10V
1 to 5V ±10V
±5 V ±10V
±10 V ±14.5V
0 to 20 mA 31 mA
4 to 20 mA 31 mA
XVD Model
±199.99 V Allowable instantaneous overload (30 s): ±400 V
±19.999 V Allowable instantaneous overload (30 s): ±200 V
±1.9999 V Allowable instantaneous overload (30 s): ±200 V
1.0000 to 5.0000V Allowable instantaneous overload (30 s): ±200 V
XVA Model
0.0 to 400.0 V Allowable instantaneous overload (30 s): 700 V
0.00 to 199.99 V Allowable instantaneous overload (30 s): 700 V
0.000 to 19.999 V Allowable instantaneous overload (30 s): 400 V
0.0000 to 1.9999 V Allowable instantaneous overload (30 s): 400 V
XAD Model
±199.99 mA Allowable instantaneous overload (30 s): ±400 V
±19.999 mA Allowable instantaneous overload (30 s): ±200 V
±1.9999 mA Allowable instantaneous overload (30 s): ±200 V
4.000 to 20.000 mA Allowable instantaneous overload (30 s): ±200 V
XAA Model
0.000 to 10.000 A Allowable instantaneous overload (30 s): 20 A
0.0000 to 1.9999 A Allowable instantaneous overload (30 s): 20 A
0.00 to 199.99 mA Allowable instantaneous overload (30 s): 2 A
0.000 to 19.999 mA Allowable instantaneous overload (30 s): 2 A
V Model
0.00 to 199.99 mV Allowable instantaneous overload (30 s): ±200 V
0.000 to 19.999 mV Allowable instantaneous overload (30 s): ±200 V
±100.00 mV Allowable instantaneous overload (30 s): ±200 V
±199.99 mV Allowable instantaneous overload (30 s): ±200 V
External power supply
12 VDC ±10%, 80 mA (only for models with external power supplies)
10 VDC ±5%, 100 mA (only for models with external power supplies)
5 VDC ±5%, 100 mA (only for models with external power supplies)
Input range
(measurement
range)
S Model DC voltages or currents (0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V, ±5 V, ±10 V), 2 channels
X Model
(measurement category
II)
DC voltage: ±199.99 V, ±19.999 V, ±1.999 V, 1.000 to 5.000 V
DC current: ±199.99 mA, ±19.999 mA, ±1.999 mA, 4.000 to 20.000 mA
AC voltage: 0.0 to 400.0 V, 0.00 to 199.99 V, 0.000 to 19.999 V, 0.000 to 1.9999 V
AC current: 0.000 to 10.000 A, 0.0000 to 1.9999 A, 0.00 to 199.99 mA, 0.000 to 19.999 mA
V Model Load cell: 0.00 to 199.99 mV, 0.000 to 19.999 mV, ±100.00 mV, ±199.99 mV
Input impedance
S Model Current range: 120 max., Voltage range: 1 M max.
X Model
DC voltage (±199.99 V): 10 M min./DC voltage (other ranges): 1 M min.
DC current (±199.99 mA): 1 max./(±19.999 mA and 4 to 20 mA): 10 max./(±1.9999 mA): 33 max.
AC voltage: 1 M min., DC current (0 to 10 A and 0 to 1.9999 A): 0.5 VAC/(0 to 199.99 mA): 1 max./(0 to 19.999 mA):
10 max.
V Model Load cell: 1 M min.
Event inputs
Timing input
NPN open collector or no-voltage contact signal
ON residual voltage: 3 V max.
ON current at 0 : 17 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 1.5 mA max.
Startup compensation
timer input
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0 : 4 mA max.
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
Hold input
Reset input
Forced-zero input
Bank input
A/D conversion
method
S Model Sequential comparison system
H/X/V Model Digital-sigma method
Output ratings
Relay output
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy: 100,000 operations
Transistor output Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current: 100 µA max.
Linear output
Linear output 0 to 20 mA DC, 4 to 20 mA:
Load: 500 max, Resolution: Approx. 10,000, Output error: ±0.5% FS
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
Load: 5 k max, Resolution: Approx. 10,000, Output error: ±0.5% FS
(1 V or less: ±0.15 V; not output for 0 V or less)
Display method
Negative LCD (backlit LED) display, 7-segment digital display (character heights: PV: 14.2 mm (switches between green and
red), SV: 4.9 mm (green))
Ambient operating temperature -10°C to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Storage temperature -25°C to 65°C (with no icing or condensation)
Altitude 2,000 m max.
Accessories
2 fixtures, unit stickers, instruction manual. watertight packing, terminal cover, DeviceNet connector * and crimp terminals
(Hirose HR31-SC-121) *