drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第23页
CS-series DeviceNet Unit CS1W-DRM21-V1 3 CS-series DeviceNet Unit CS1W-DRM21-V1 A DeviceNet Unit for the CS Series • Allows control of up to 32,000 points (2,000 words) per master, and ensures a hi gh degree of simultane…

2 CJ-series DeviceNet Unit CJ1W-DRM21
CJ-series DeviceNet Unit
CJ1W-DRM21
A DeviceNet Unit for the NJ/CJ Series
• Allows control of up to 32,000 points (2,000 words) per master, and ensures a high degree of
simultaneity between data.
• Can be used as both a master and a slave at the same time.
• Equipped with settings and monitor functions aimed at improving both design and startup efficiency.
Achieve maximum performance by using in combination with a Configurator.
• Files of master and slave settings can be uploaded and downloaded using memory cards, allowing
effective debugging and easier setup.
Ordering Information
Master/Slave Specifications
*1. Refer to the DeviceNet Operation Manual (W267) for the communications power supply specifications.
*2. The Device Unit uses a node, and so connection is possible to 63 slaves only.
*3. When the DeviceNet is used as a slave, “input” and “output” respectively refer to input from the slave to the master and output from the master to the slave.
*4. The maximum message length includes the command code when using the CMND instruction. (SendCmd instruction with NJ-series controller)
Note: When using with the Machine Automation Controller NJ Series, note the following points:
• Simple backup function cannot be used.
• DeviceNet configurator cannot be used. Use CX-Integrator.
General Specifications
The specifications conform to the CJ Series. Refer to the CJ Series
Catalog (P052) for details on CJ-series specifications.
CJ2 Series Catalog (P059) for details on CJ2-series specifications.
Dimensions
31 x 90 x 65 mm (W x H x D)
Unit
classification
Product name Specifications Communications
No. of unit
numbers
allocated
Current consumption (A)
Model
5 V 24V
CJ1 CPU
Bus Unit
DeviceNet
Unit
Equipped with Master and
Slave functionality. Controls for
up to 32,000 points per Master.
• Remote I/O Communications Master (fixed
allocations or user-set allocations)
• Remote I/O Communications Slave (fixed
allocations or user-set allocations)
• Message communications
10.29 -CJ1W-DRM21
Communications power supply voltage 11 to 25 VDC *1
Current consumption
Communications: 18 mA max.
Internal circuit: 290 mA max.
Max. number of connectable slaves Remote I/O, explicit message service 63 *2
Max. number of I/O points
Fixed allocations
When used as a master 2,048 points
When used as a slave 32 points
User-set
allocations
Using allocated
DM Area words
When used as a master 16,000 points
When used as a slave 3,200 points
Using
Configurator
When used as a master 32,000 points
When used as a slave 4,800 points
Number of allocated words
Fixed allocations
When used as a master
64 input and 64 output words
Software switch/status area: 25 words
When used as a slave 1 input word, 1 output word *3
User-set
allocations
Using allocated
DM Area words
When used as a master
500 input and 500 output words
Software switch/status area: 25 words
When used as a slave
100 input and 100 output words *3
Software switch/status area: 25 words
Using
Configurator
When used as a master
500 input words x 2 blocks, 500 output words x 2 blocks
Software switch/Status area: 25 words
When used as a slave
100 input words x 1 blocks, 100 output words x 2 blocks *3
Software switch/Status area: 25 words
Message communications Max. message length 542 bytes *4
Max. number of Units mountable to
PLC
Fixed allocations 3
User-set allocations 16
Weight 118 g

CS-series DeviceNet Unit CS1W-DRM21-V1 3
CS-series DeviceNet Unit
CS1W-DRM21-V1
A DeviceNet Unit for the CS Series
• Allows control of up to 32,000 points (2,000 words) per master, and ensures a high degree of
simultaneity between data.
• Can be used as both a master and a slave at the same time.
• Equipped with settings and monitor functions aimed at improving both design and startup efficiency.
Achieve maximum performance by using in combination with a Configurator.
• Files of master and slave settings can be uploaded and downloaded using memory cards, allowing
effective debugging and easier setup.
Ordering Information
Master/Slave Specifications
*1. Refer to the DeviceNet Operation Manual (W267) for the communications power supply specifications.
*2. The Device Unit uses a node, and so connection is possible to 63 slaves only.
*3. When the DeviceNet is used as a slave, “input” and “output” respectively refer to input from the slave to the master and output from the master to the slave.
*4. The maximum message length includes the command code when using the CMND instruction.
General Specifications
The specifications conform to the CS Series. Refer to the CS Series
Catalog (P047) for details on CS-series specifications.
Dimensions
34.5 X 130 X 111.2 mm (W X H X D)
Unit
classification
Product
name
Specifications
No. of unit
numbers
allocated
Current
consumption
(A)
Model
Communications
Cable
Communications
Redundant
communications
Max. No. of
Units
mounted to 1
CPU Unit
5V 26V
CS1 CPU Bus
Unit
DeviceNet
Unit
DeviceNet Cable
• Remote I/O Communications
Master (fixed allocations or
user-set allocation)
• Remote I/O Communications
Slave (fixed allocation or user-
set allocation)
• Message communications
Not supported. 16 1 0.29 - CS1W-DRM21-V1
Communications power supply voltage 11 to 25 VDC *1
Current consumption
Communications: 30 mA max.
Internal circuit: 290 mA max.
Max. number of connectable slaves Remote I/O, explicit message service 63 *2
Maximum I/O points
Fixed allocations
When used as a master 2,048 points
When used as a slave 32 points
User-set
allocations
Using allocated
DM Area words
When used as a master 16,000 points
When used as a slave 3,200 points
Using
Configurator
When used as a master 32,000 points
When used as a slave 4,800 points
Number of allocated words
Fixed allocations
When used as a master
64 input and 64 output words
Software switch/status area: 25 words
When used as a slave input word, 1 output word *3
User-set
allocations
Using allocated
DM Area words
When used as a master
500 input and 500 output words
Software switch/status area: 25 words
When used as a slave
100 input and 100 output words *3
Software switch/status area: 25 words
Using
Configurator
When used as a master
500 input words x 2 blocks, 500 output words x 2 blocks
Software switch/Status area: 25 words
When used as a slave
100 input words x 1 blocks, 100 output words x 2 blocks
Software switch/Status area: 25 words
Max. message length 542 bytes *4
Max. number of Units mountable to
PLC
Fixed allocations 3
User-set allocations 16
Weight 169 g

4 Programmable Controllers NSJ Series NSJ@-@@@@(B)-G5D/M3D
Programmable Controllers NSJ Series
NSJ
@
-T@@1(B)-G5D
The NSJ-series Controller Completely Integrates
a PT and Controller into One Package
• A PT, Controller CPU Unit, and DeviceNet Master Unit are completely
integrated.
• Super space-saving design.
• Easily transfer screens and ladder programming using a commercially
available USB cable.
• No cable connections or complicated communications settings required.
Start operation simply by turning ON the power supply.
• Equipped with troubleshooter for the Controller and DeviceNet Master as a
standard feature.
Ordering Information
■ Controllers
* (B) in the model number indicates that the color of the Controller frame is black.
■ Accessories and Expansion Units
Name Controller Section
Display Section
Ethernet port Model *
Display device Resolution
NSJ Series
No. of I/O points: 1,280
Program capacity: 60K steps
Data memory capacity:
128K words (DM: 32K words,
EM: 32K words x 3 banks)
5.7-inch color High-luminance
TFT LCD
320 X 240 (QVGA)
10/100Base-T
NSJ5-TQ11(B)-G5D
8.4-inch color TFT LCD
640 X 480 (VGA)
NSJ8-TV01(B)-G5D
10.4-inch color TFT LCD NSJ10-TV01(B)-G5D
12.1-inch color TFT LCD 800 X 600 (SVGA) NSJ12-TS01(B)-G5D
Name Specifications Model
Expansion
Units
NSJ Controller Link Unit
For increasing the number of Controller Link ports
Same as the CJ1W-CLK21-V1 Controller Link Unit for the CJ Series.
NSJW-CLK21-V1
NSJ Ethernet Unit
For increasing the number of Ethernet ports
Same as the CJ1W-ETN21 Ethernet Unit for the CJ Series.
NSJW-ETN21
NSJ I/O Control Unit
For adding CJ-series Expansion Racks.
Same as the CJ1W-IC101 I/O Control Unit for the CJ Series.
NSJW-IC101
Options
Memory Cards
(for both Controller Section
and Display Section)
Flash memory: 128 MB HMC-EF183
Flash memory: 256 MB HMC-EF283
Flash memory: 512 MB HMC-EF583
Memory Card Adapter HMC-AP001