drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第120页
100 DeviceNet-compliant Digital Controllers E5AR-DRT/E5ER-DRT DeviceNet-compli ant Digital Controllers Final order entry date: Th e end of March, 2021 E5AR-DRT/E5ER-DRT General-purpose Digital Controllers with High Speed…

DeviceNet-compliant Digital Indicators K3HB-@-DRT 99
Dimensions (Unit: mm)
Terminal Arrangement
8
8
Panel Cutout Dimensions
120 min.
45
+0.6
0
92
+0.8
0
75 min.
Character Size for Main Display
PV display SV display
4.9
3.5
101.2
91
96
48
12
1.3
100
(112)
44.8
97
2
7.6
14.2
K3HB
ATerminals B C D E
1
2
3
4
5
6
Operating Power Supply
A
Sensor Power Supply/Outputs
B
Relay, Transistor, BCD, and DeviceNet
C
Event Inputs
D
Analog Inputs
E
Analog Inputs
E
Analog Inputs
E
100 to 240 VAC
24 VAC/DC
A1
A2
* Check the required power supply type.
Note: Refer to the measurement ranges
on the front.
Inputs
B
Inputs
A
COM
Inputs
A
Inputs
B
N/C
A
B
C
D
COM
Current
input
Voltage
input
AC voltage only
A
Pt
B
B'
N/C
N/C
COM
COM
AB
D
C
N/C
N/C
(K3HB-X, V)(K3HB-S)(K3HB-H)
TC
E1
E2
E3
E4
E5
E6
E1
E2
E3
E4
E5
E6
E1
E2
E3
E4
E5
E6
TIMING
S-TMR
HOLD
RESET
ZERO
COM
Models with Terminal Blocks
<1><3>
D1
D2
D3
D4
D5
D6
Applicable connector (order separately):
XG4M-1030 (OMRON)
Special cable (order separately):
K32-DICN (OMRON)
(XG4M-1030 with 3-m Cable)
2:S-TMR
4:RESET
6:COM
8:BANK2
10:COM
1:TIMING
3:HOLD
5:ZERO
7:BANK4
9:BANK1
Models with Connectors
<2><4>
10
2
9
1
1: V – (power supply wire: black)
2: CAN L (communications wire: blue)
3: Shield
4: CAN H (communications wire: white)
5: V+ (power supply wire: red)
Applicable connector:
HR31-5.08P-5SC (01) (Hirose Electric)
Note: Attach the enclosed crimp terminals.
Sensor Power Supply
and PASS Output
Sensor Power Supply
and Linear Output
Sensor Power Supply
Sensor Power Supply
and Communications
Sensor Power
Supply
Sensor Power
Supply
Sensor Power
Supply
Sensor Power
Supply

100 DeviceNet-compliant Digital Controllers E5AR-DRT/E5ER-DRT
DeviceNet-compliant Digital Controllers Final order entry date: The end of March, 2021
E5AR-DRT/E5ER-DRT
General-purpose Digital
Controllers with High Speed and
High Accuracy. Three, 5-digit
Easy-to-read Tall LCD Displays.
• High-speed sampling cycle (50 ms) for applications requiring
high-speed response.
• Three backlit, negative LCD displays for simultaneous display of PV,
SV, and MV.
• Multipoint control, cascade control, and proportional control all
possible with a single Controller.
• Data processing functions provided as standard features: Square
root extraction, linear approximation, and more.
• DeviceNet communications for data setting and monitoring without
special programming.
Ordering Information
■ Digital Controllers
● E5AR DeviceNet-compliant Models
Note: When ordering, specify the power supply. Different models are used for 100 to 240 VAC and 24 VDC/AC.
* Control can be switched between closed control and floating control.
Size Type Control modes
No. of outputs
(control/transfer)
Optional features
Model
No. of
auxiliary
outputs
(SUB)
No. of event
inputs
Communications
96 x 96 mm
Basic Type
(1 input)
Standard control
Heating/cooling control
2
(pulse voltage + pulse voltage/
current outputs)
4 2 DeviceNet
E5AR-Q4B-DRT
2 (2 current outputs) E5AR-C4B-DRT
4
(1 pulse voltage + 1 pulse
voltage/current + 2 current
outputs)
E5AR-QC4B-DRT
2-input Type
2-channel standard control
2-channel heating/cooling control
1-channel cascade control
1-channel control with remote SP
1-channel ratio control
4
(2 pulse voltage + 2 pulse
voltage/current)
4 None DeviceNet E5AR-QQ4W-DRT
4-input Type
4-channel standard control
2-channel heating/cooling control
4 (4 current outputs) 4 None DeviceNet E5AR-CC4WW-DRT
Control Valve
Control Type
(1 input)
1-channel position proportional
control *
Relay outputs
(1 open and 1 closed)
4 None DeviceNet
E5AR-PR4F-DRT
Relay outputs (1 open and 1
closed) + 1 current (transfer)
E5AR-PRQ4F-DRT

DeviceNet-compliant Digital Controllers E5AR-DRT/E5ER-DRT 101
● E5ER DeviceNet-compliant Models
Note: When ordering, specify the power supply. Different models are used for 100 to 240 VAC and 24 VDC/AC.
*1. Transistor outputs.
*2. Control can be switched between closed control and floating control.
Order using the following model number together with the model
number of the Digital Controller to obtain inspection results.
Inspection Results (Sold Separately)
■ Optional Accessories (Sold separately)
● Terminal Cover
Specifications
● E5AR
Note: Do not use the output from an Inverter for the power supply.
*1. When ordering, specify the power supply. Different models are used for 100 to 240 VAC and 24 VDC/AC.
*2. Multi-input. Switch between temperature and analog input using the input type switch.
Basic insulation is provided between the power supply and input terminals and between the power supply and output terminals.
Size Type Control modes No. of outputs (control/transfer)
Optional features
Model
No. of
auxiliary
outputs
(SUB)
No. of event
inputs
Communications
48 x 96 mm
Basic Type
(1 input)
Standard control
Heating/cooling control
2
(pulse voltage + pulse voltage/
current outputs)
2 *1 2 DeviceNet
E5ER-QTB-DRT
2 (2 current outputs) E5ER-CTB-DRT
2-input Type
2-channel standard control
1-channel heating/cooling control
1-channel cascade control
1-channel control with remote SP
1-channel ratio control
2
(pulse voltage + pulse voltage/
current outputs) 2 *1 None DeviceNet
E5ER-QTW-DRT
2 (2 current outputs) E5ER-CTW-DRT
Control Valve
Control Type
(1 input)
1-channel position proportional
control *2
Relay outputs
(1 open and 1 closed)
2 *1 None DeviceNet E5ER-PRTF-DRT
Inspection Results
Model
E5AR-K
E5ER-K
Digital Controller Model
E5AR E53-COV14
E5ER E53-COV15
Item *1 Power supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz or 24 VDC
Allowed voltage variance range 85% to 110% of power supply voltage
Power consumption 22 VA max. (under maximum load) 15 VA/10 W max. (under maximum load)
Sensor input *2
Thermocouples: K, J, T, E, L, U, N, R, S, B, W
Platinum resistance temperature input sensors: Pt100
Current inputs: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input)
Voltage inputs: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input)
(Input impedance: 150 using current input, approx. 1 M using voltage input)
Control
output
Voltage (pulse) output 12 V DC, 40 mA max., with short-circuit protection circuit
Current output
0 to 20 mA DC/4 to 20 mA DC, 500 load max. (including transfer output)
(Resolution: Approx. 54,000 at 0 to 20 mA DC, approx. 43,000 at 4 to 20 mA DC)
Relay output
Position proportional control type (open, closed)
NO-SPST 250 VAC 1 A (including inrush current)
Auxiliary output NO-SPST 250 V AC 1 A (resistive load)
Potentiometer input 100 to 2.5 k
Event
input
Contact Input ON: 1 k max., OFF: 100 k max.
Non-contact Input ON: Residual voltage 1.5 V max., OFF: Leakage current 0.1 mA max.
Short-circuit current: Approx. 4 mA
Remote SP input See Sensor inputs.
Transfer output See Control outputs.
Control method Advanced PID or ON/OFF
Setting method Digital setting by front panel keys, setting by serial communications
Indication method
7-segment digital display and LED indicators
Character heights: PV 12.8 mm, SV 7.7 mm, MV 7.7 mm
Other functions Varies by model
Ambient operating temperature -10°C to 55°C (no condensation or icing), 3 year warranty: -10°C to 55°C (no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25°C to 65°C (no condensation or icing)