drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第53页

e-CON Connector Terminals DRT2- @ D16S(-1) 33 Wiring Diagrams DRT2-ID16S (NPN) DRT2-ID16S-1 (PNP) DRT2-MD16S (NPN) DRT2-MD16S-1 (PNP) V NC IN 0 V NC G1 IN 1 V NC G2 IN 2 V NC G2 IN 3 V NC G3 IN 4 V NC G3 IN 5 V NC G4 IN …

100%1 / 199
32 e-CON Connector Terminals DRT2-@D16S(-1)
Input Specifications
Terminals with 16 Inputs Terminal with 8 Inputs/8 Outputs
Applicable Connectors (sold separately)
OMRON Connectors
Tyco Electronics Connectors
Sumitomo 3M Connectors
Dimensions (Unit: mm)
Item Model DRT2-ID16S DRT2-ID16S-1
Internal I/O common
NPN PNP
I/O points 16 inputs
ON voltage
9 VDC min. (between each
input terminal and V)
9 VDC min. (between each
input terminal and G)
OFF voltage
5 VDC max. (between each
input terminal and V)
5 VDC max. (between each
input terminal and G)
OFF current 1 mA max.
Input current
11 mA max./point (at 24 VDC)
3.0 mA min./point (at 11 VDC)
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits
per common
16 per common
Sensor short-circuit
detection current
The total current for all of the following input points is
monitored to detect sensor short-circuits.
IN0/IN1, IN2/IN3, IN4/IN5, IN6/IN7, IN8/IN9, IN10/IN11,
IN12/IN13, IN14/IN15
Item Model DRT2-MD16S DRT2-MD16S-1
Internal I/O common
NPN PNP
I/O points 8 inputs
ON voltage
9 VDC min. (between each
input terminal and V)
9 VDC min. (between each
input terminal and G)
OFF voltage
5 VDC max. (between each
input terminal and V)
5 VDC max. (between each
input terminal and G)
OFF current 1 mA max.
Input current
11 mA max./point (at 24 VDC)
3.0 mA min./point (at 11 VDC)
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits
per common
8 per common
Sensor short-circuit
detection current
The total current for all of the following input points is
monitored to detect sensor short-circuits.
IN0/IN1, IN2/IN3, IN4/IN5, IN6/IN7
Model Specifications Compatible wire size
XN2A-1470 Spring-clamp style Stranded wire 28 to 20 AWG (0.08 to 0.5 mm
2
) wire, 1.5 mm max. outer diameter including insulation
Model Color of housing Compatible wire size
3-1473562-4 Orange 0.6 to 0.9 mm max. outer diameter including insulation
Wire size: 0.08 to 0.5 mm
2
1-1473562-4 Red 0.9 to 1.0 mm max. outer diameter including insulation
1473562-4 Yellow 1.0 to 1.15 mm max. outer diameter including insulation
2-1473562-4 Blue 1.15 to 1.35 mm max. outer diameter including insulation
4-1473562-4 Green 1.35 to 1.60 mm max. outer diameter including insulation
Model Specifications/color of housing Compatible wire size
37104-3101-000FL Red 26 to 24 AWG (0.14 to 0.2 mm
2
) wire, 0.8 to 1.0 mm max. outer diameter including insulation
37104-3122-000FL Yellow 26 to 24 AWG (0.14 to 0.2 mm
2
) wire, 1.0 to 1.2 mm max. outer diameter including insulation
37104-3163-000FL Orange 26 to 24 AWG (0.14 to 0.2 mm
2
) wire, 1.2 to 1.6 mm max. outer diameter including insulation
37104-2124-000FL Green 22 to 20 AWG (0.3 to 0.5 mm
2
) wire, 1.0 to 1.2 mm max. outer diameter including insulation
37104-2165-000FL Blue 22 to 20 AWG (0.3 to 0.5 mm
2
) wire, 1.2 to 1.6 mm max. outer diameter including insulation
37104-2206-000FL Gray 22 to 20 AWG (0.3 to 0.5 mm
2
) wire, 1.6 to 2.0 mm max. outer diameter including insulation
INPUT
0TO 7
MS
MODE ADDRESS
NS
U,ERR1
U,ERR2
IN
IN
0
8
1
9
2
10
3
11
4
12
5
13
6
14
7
15
INPUT
8TO15
95
88±0.2
Two, 4.2 dia. or M4
33.3
50
Mounting Hole Dimension
DRT2-ID16S(-1)
MS NS
SHT 0 0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
IN
SHT 1
OUT
NODE ADDRESS
IN
0-7
OUT 0-7
×10
×1
3
36.8
Two, 4.2 dia. or M4
88±0.2
50
95
33.3
DRT2-MD16S(-1)
Mounting Hole Dimension
e-CON Connector Terminals DRT2-@D16S(-1) 33
Wiring Diagrams
DRT2-ID16S (NPN) DRT2-ID16S-1 (PNP)
DRT2-MD16S (NPN)
DRT2-MD16S-1 (PNP)
V
NC
IN
0
V
NC
G1
IN
1
V
NC
G2
IN
2
V
NC
G2
IN
3
V
NC
G3
IN
4
V
NC
G3
IN
5
V
NC
G4
IN
6
V
NC
G4
IN
7
V
NC
G5
IN
8
1
2
V
NC
G5
IN
9
V
NC
G6
IN
10
V
NC
G6
IN
11
V
NC
G7
IN
12
V
NC
G7
IN
13
V
NC
G8
IN
14
V
NC
G8
IN
15
3
4
1
2
3
4
G1
2-wire sensor
(e.g., limit
switch)
3-wire sensor with
NPN output
(Photoelectric or
proximity sensor)
Brown
(white)
Blue
(black)
Blue
(black)
Black
(white)
Brown
(red)
V1
NC
G
IN
0
V1
NC
G
IN
1
V2
NC
G
IN
2
V2
NC
G
IN
3
V3
NC
G
IN
4
V3
NC
G
IN
5
V4
NC
G
IN
6
V4
NC
G
IN
7
V5
NC
G
IN
8
V5
NC
G
IN
9
V6
NC
G
IN
10
V6
NC
G
IN
11
V7
NC
G
IN
12
V7
NC
G
IN
13
V8
NC
G
IN
14
V8
NC
G
IN
15
1
2
3
4
1
2
3
4
2-wire sensor
(e.g., limit
switch)
3-wire sensor with
PNP output
(Photoelectric or
proximity sensor)
Brown
(white)
Blue
(black)
Blue
(black)
Black
(white)
Brown
(red)
V1
NC
G1
IN
0
V1
NC
IN
1
V1
NC
IN
2
V1
NC
IN
3
V1
NC
IN
4
V1
NC
IN
5
V1
NC
IN
6
V1
NC
IN
7
V2
NC
NC
OUT
0
1
2
NC
NC
OUT
1
NC
NC
OUT
2
NC
NC
OUT
3
NC
NC
OUT
4
NC
NC
OUT
5
NC
NC
OUT
6
NC
NC
OUT
7
3
4
1
2
3
4
G1
G2 G2
G3
G3 G4
G4
V2
V2
V2
V2
V2 V2 V2
G0
G0
V0
V0
2-wire sensor
(e.g., limit switch)
3-wire sensor with NPN output
(Photoelectric or proximity sensor)
Solenoid valve, etc. Solenoid valve, etc.
Connection can be
made to either V0
terminal.
Connection can be
made to either G0
terminal.
Brown
(white)
Blue
(black)
Blue
(black)
Black
(white)
Brown
(red)
V1
NC
G1
IN
0
V1
NC
IN
1
V2
NC
IN
2
V2
NC
IN
3
V3
NC
IN
4
V3
NC
IN
5
V4
NC
IN
6
V4
NC
IN
7
NC
NC
G2
OUT
0
1
2
NC
G2
OUT
1
NC
G2
OUT
2
NC
G2
OUT
3
NC
G2
OUT
4
NC
G2
OUT
5
NC
G2
OUT
6
NC
G2
OUT
7
3
4
1
2
3
4
G1
G1 G1
G1
G1 G1
G1
NC
NC
NC
NC
NC NC NC
G0
G0
V0
V0
2-wire sensor
(e.g., limit switch)
3-wire sensor with PNP output
(Photoelectric or proximity sensor)
Solenoid valve, etc. Solenoid valve, etc.
Connection can be
made to either V0
terminal.
Connection can be
made to either G0
terminal.
Brown
(white)
Blue
(black)
Blue
(black)
Black
(white)
Brown
(red)
34 MIL Connector Terminals with Transistors DRT2-@D32ML(-1)/@D16ML(-1)
MIL Connector Terminals with Transistors
DRT2-
@
D32ML(-1)/
@
D16ML(-1)
Very Compact 16-/32-point Remote
Terminals
Used in combination with Interface Conversion Boards (e.g., D-Sub) to connect to a
wide range of interfaces.
35 x 60 x 80 mm (W x D x H)
Smart Slave Functions
Ordering Information
Specifications I/O connections
Rated internal circuit
power supply voltage
Rated I/O power
supply voltage
Model
Inputs
NPN (+ common)
32 points
MIL connector
Supplied from the
communications
connector
24 VDC
DRT2-ID32ML
PNP (- common) DRT2-ID32ML-1
Outputs
NPN (- common) DRT2-OD32ML
PNP (+ common) DRT2-OD32ML-1
I/O
NPN (input: + common, output: - common)
16 inputs/
16 outputs
DRT2-MD32ML
PNP (input: - common, output: + common) DRT2-MD32ML-1
Inputs
NPN (+ common)
16 points
MIL connector
DRT2-ID16ML
PNP (- common) DRT2-ID16ML-1
Outputs
NPN (- common) DRT2-OD16ML
PNP (+ common) DRT2-OD16ML-1
Inputs
NPN (+ common)
MIL connector
(Connector with
10-cm cable)
DRT2-ID16MLX
PNP (- common) DRT2-ID16MLX-1
Outputs
NPN (- common) DRT2-OD16MLX
PNP (+ common) DRT2-OD16MLX-1
Mounting Bracket SRT2-ATT02
Power-ON inrush current protection (input or I/O only)
Operation time monitor Contact operation counter Unit conduction time monitor
Total ON time monitor Unit comments Connected device comments
Network power supply voltage monitor I/O power supply monitor function Communications error log function
Input filter (input or I/O only)
Communications speed auto-detection No need to wire Unit power supply Last maintenance date