drt2_devicenet_q102-e1_20_22_csm2147.pdf - 第131页
111 CIP Safety on DeviceNet System Safety Network Controller ............. ............ ........ .................... ...................... ... 112 NE0A- SCPU01 Safety Network Controller ............. ............ .....…

110
MEMO

111
CIP Safety on DeviceNet System
Safety Network Controller.............................................................................. 112
NE0A-SCPU01
Safety Network Controller.............................................................................. 117
NE1A-SCPU Series
Safety I/O Terminals...................................................................................... 122
DST1 Series
Network Configurator..................................................................................... 125
WS02-CFSC1-E

112 Safety Network Controller NE0A-SCPU01
Safety Network Controller
NE0A-SCPU01
New Lineup for Safety
Applications with Up to 12 Inputs
• Circuits for the required safety category are easy to build.
• The safety circuits you create can be registered as templates and
reused, for easy standardization.
• TÜV-certified templates is also available.
• The NE0A operating conditions can be monitored from a standard
DeviceNet Master.
• Network distribution is possible by combining with an NE1A Safety
Controller.
• ISO13849-1 (PLe) and IEC 61508 SIL3 certification.
Ordering Information
Note 1: The standard NE0A Safety Network Controller is equipped with spring-cage terminal blocks, but screw terminal blocks are available if desired, e.g., to replace previous
terminals.
Note 2: Network Configurator version 2.1@ or higher must be used when using a NE0A-SCPU01 Safety Network Controller.
* When using the NE0A-SCPU01 as a standalone Controller, one input each is required for the feedback input and manual restart.
Specifications
Certified Standards General Specifications
*1. V0-G0: Internal control circuit
V1-G1 (G): For external input device, test output
V2-G2 (G): For external output device
*2. Not including power consumption for external devices.
Name
I/O points
Model Unit version
Safety inputs Test outputs Safety outputs
Safety Network Controllers 12 * 26NE0A-SCPU01 Ver. 1.0
Certification body Standard
TÜV Rheinland
EN ISO 13849-1
EN ISO 13849-2
IEC 61508
EN 62061
EN 61131-2
IEC 61326-3-1
UL
UL508
ISA12.12.01
UL1998
IEC 61508-3
DeviceNet Communications power
supply voltage
11 to 25 VDC
(supplied from the communications
connector)
Internal circuit power supply
voltage (V0) *1
20.4 to 26.4 VDC
(24 VDC -15%/+10%)
I/O power supply voltage (V1, V2)
*1
Current
consumption
Communications
power supply
24 VDC, 15 mA
Internal circuit
power supply
24 VDC, 110 mA
I/O power supply *2
24VDC, 80mA(Input)
80mA(Output)
Overvoltage category II
Noise immunity Conforms to IEC61131-2.
Vibration resistance
10 to 57 Hz: 0.35 mm,
57 to 150 Hz: 50 m/s
2
Shock resistance 150 m/s
2
: 11 ms
Mounting method
DIN track mounting
(IEC 60715 TH35-7.5/TH35-15)
Ambient operating temperature -10°C to 55°C
Ambient operating humidity 10% to 95% (with no condensation)
Ambient storage temperature -40°C to 70°C
Degree of protection IP20
Serial interface USB version 1.1
Weight 440 g max.