4. Spindle Adjustment 4 - 20 bit1. Speed detection (SD) This signal turns ON when the motor speed drops below the value set with param eter SP020 (SDTS). The ON to OFF hysteresis width is set with parameter SP047 (SDTR).…

4. Spindle Adjustment
4 - 19
(4) Spindle control output 4
Name Details
F E D C B A 9 8 7 6 5 4 3 2 1 0
AL4 AL3 AL2 AL1
EMG
A
TLU
MTC WRCF MKC
ORCF
ZS US SD CD
bit Details
0
CD
Current detection
1
SD
Speed detection
2
US
Up-to-speed
3
ZS
Zero speed
4
ORCF
Orientation complete
5
6
MKC
Changing coil
7
WRCF
Index positioning completed
8
MTC
In changeover (for 1-drive unit 2-motor changeover)
9
A
TLU
Torque reach
B
EMGA
In emergency stop
C
AL1
Alarm code 1
D
AL2
Alarm code 2
E
AL3
Alarm code 3
F
AL4
Alarm code 4
Spindle control output 4
bit0. Current detection (CD)
This signal turns ON when the start signal (forward run, reverse run, orientation) is ON, and the
current flowing to the motor is approx. 110% or more of the rating. (The motor output (current)
guarantee value is 120% of the rating.)
No. Abbr. Parameter name Details
Setting
range
Standard
SP141
to
SP154
HO1e
to
HO6c
General-purpose
output selection
Open emitter 1 to
General-purpose
output selection
Open collector 6
Set the following value in any one of these parameters when
using the current detection output.
“12”: Current detection (CD)
0 to 23 0

4. Spindle Adjustment
4 - 20
bit1. Speed detection (SD)
This signal turns ON when the motor speed drops below the value set with parameter SP020
(SDTS). The ON to OFF hysteresis width is set with parameter SP047 (SDTR). This signal turns
ON when the motor's speed is less than the set speed regardless of the input signal state.
Speed detection (SD) sequence
Related spindle parameters
No. Abbr. Parameter name Details
Setting
range
Standard
SP020 SDTS* Speed detection set
value
Set the motor speed for which speed detection output is
performed.
Usually, the setting value is 10% of SP017 (TSP).
0 to 32767
(r/min)
600
SP047 SDTR* Speed detection
reset value
Set the reset hysteresis width for a speed detection set value
defined in SP020 (SDTS).
0 to 1000
(r/min)
30
SP141
to
SP154
HO1e
to
HO6c
General-purpose
output selection
Open emitter 1 to
General-purpose
output selection
Open collector 6
Set the following value in any one of these parameters when
using the speed detection output.
“13”: Speed detection (SD)
0 to 23 0
SP047
Motor speed
Speed detection (SD)
ON
OFF
SP020
0

4. Spindle Adjustment
4 - 21
bit2. Up-to-speed (US)
This signal turns ON when the start command signal (forward run, reverse run) is ON, and the
motor speed has reached a range of ±15% (standard value) of the speed command value. This
signal turns OFF when the start command signal turns OFF. The up-to-speed output range can be
set with the parameter SP048 (SUT). Even though the setting value is small, the output will be
±45r/min. Pay attention when speed command value is small.
Up-to-speed (US) sequence
Related spindle parameter
No. Abbr. Parameter name Details
Setting
range
Standard
SP048 SUT* Speed reach range Set the speed deviation rate with respect to the commanded
speed for output of the speed reach signal.
0 to 100
(%)
15
SP141
to
SP154
HO1e
to
HO6c
General-purpose
output selection
Open emitter 1
to
General-purpose
output selection
Open collector 6
Set the following value in any one of these parameters when
using the up-to-speed output.
“14”: Up-to-speed (US)
0 to 23 0
Motor speed
Forward run start command
(SRN)
ON
OFF
0
SP048
Reverse run start command
(SRI)
ON
OFF
Up-to-speed (US)
ON
OFF
Out
p
ut ran
g
e
(
minimum ±45r/min
)
Out
p
ut ran
g
e