4. Spindle Adjustment
4 - 3
4-1-3 Setting the output magnification
(1) Meter output (Data No. 0)
With meter output, the output channel is fixed, and the output voltage range is 0 to 10V in the
positive range. Set the magnification with the following parameters. Also, low path filter can be set
on the load meter output.
No. Abbr. Parameter name Details
Setting
range
Standard
SP017 TSP* Maximum motor
speed
Set the maximum spindle motor speed.
When SP249=0, the motor speed will be the motor rotation
speed at the speedometer 10V output.
1 to 32767
(r/min)
6000
SP094 LMAV* Load meter output
filter
Set the filter time constant of load meter output.
When "0" is set, a filter time constant is set to 226ms.
0 to 32767
(3.5ms)
0
SP177
MADJ*
Meter full scale
compulsory output
When carrying out a full-scale adjustment to the speed meter
and load meter, set to "1" here so that the full scale voltage is
output and the adjustment mode is entered. Adjustment is
carried out with SP178(SMG) and SP179(LMG) at this time.
Always return the setting value to "0" when the adjustment is
completed.
0 to 1 0
SP178 SMG*
Speed meter output
full scale adjustment
Adjust the speed meter full scale.
Adjust so that the fluctuations of the speed meter is at the
intended position when "1" is set in SP177(MADJ).
0 to 1000
(1/1000-fold)
938
SP179 LMG*
Load meter output
full scale adjustment
Adjust the load meter full scale.
Adjust so that the fluctuations of the load meter is at the
intended position when "1" is set in SP177(MADJ).
0 to 1000
(1/1000-fold)
938
SP249 SMO Speedometer speed Set the motor rotation speed when the speedometer 10V is
output.
When set to "0", this parameter becomes the same as SP017
(TSP).
0 to 32767
(r/min)
0
SP250 LMO Load meter voltage Set the voltage when the load meter 120% is output. When set
to "0", this becomes 10V.
0 to 10
(V)
0
(2) Internal data output (Data No. 1 to 13)
Normally, the standard setting value is set for the output magnification (SP255, SP256). When
"0" is set, the magnification will be the same as "256".
DATA ×
SP255
256
×
10 [V]
256
(
8 bit
)
+ 5 [V] (offset) = Output voltage [V]
(Example) To output current FB at a 30-minute stall rating 20%/V unit (SP253=3, SP255=8)
819.2 ×
8
256
×
10
256
+ 5 = 6 [V]
No. Abbr. Parameter name Details
Setting
range
Standard
SP255 DA1MPY DA output channel 1
magnification
0
SP256 DA2MPY DA output channel 2
magnification
Set the output magnification with a 1/256 unit.
When "0" is set, the magnification will be the same as "256".
-32768 to
32767
(1/256-fold)
0

4. Spindle Adjustment
4 - 4
(3) Control signal output (Data No. 80 to 87)
A hexadecimal display is converted into a decimal and output. The method of calculating the
magnification is the same as (2). The status cannot be output for each bit, so output the status for
all 16 bits.
(Example) Orientation indexing control
With orientation indexing control, the following operations of the "Control output 4" can be
observed as shown on the right:
bit4: Orientation completed
bit7: Indexing positioning completed
Note that the weight of the D/A output differs for each bit.
Orientation indexing control sequence output
Orientation start
Orientation speed
Motor speed
Time
Control output 4
5[V]
Orientation time
Orientation
complete
0
10[V]
5
Indexing time
Indexing
complete

4. Spindle Adjustment
4 - 5
4-2 Spindle control signal
The sequence input/output signals of the spindle drive unit are explained in this section. The status of
each signal is displayed on the spindle monitor of the personal computer when the personal computer
is connected.
4-2-1 Spindle control input (NC to SP)
(1) Spindle control input 1
Name Details
F E D C B A 9 8 7 6 5 4 3 2 1 0
TL3 TL2 TL1
ALMR
PRM RDY
bit Details
0
RDY
READY ON command
1
2
3
4
5
6
PRM
Parameter conversion command
7
ALMR
Drive unit alarm reset command
8
TL1
Torque limit 1
9
TL2
Torque limit 2
A
TL3
Torque limit 3
B
C
D
E
F
Spindle control input 1
bit0. READY ON command (RDY)
1) This signal is input when the motor is ready to rotate. This is valid when the circuit between 1 pin
(REDY) and 19 pin (CES1) of CN10 is closed (ON). When this signal is turned ON, the main
circuit of the converter unit will be turned ON.
2) Before this signal is turned ON or within approx. one second from when this signal is turne d ON
till the "in READY ON" signal is turned ON, signals are not accepted even if turning the
forward/reverse run command, orie ntation command ON.
3) If this signal is turned OFF during motor rotation, the current to the motor is shut OFF and the
motor will coast to stop.
4) Turn this signal OFF for safety before the operator touches the spindle directly and
attaches/removes the workpiece or tools. However, be careful not to turn this signal ON/OFF
too frequently (100 times or more/day).
bit6. Parameter conversion command (PRM)
This is started when the spindle parameters are converted on the personal computer screen.
bit7. Drive unit alarm reset command (ALMR)
This turns ON while the alarm reset is input. Spindle alarms are reset.
However, if this signal is turned ON during the motor rotation, the power supplied to the motor is
shut off and the motor will coast to stop.