Appendix 3. EMC Installation Guidelines
A3 - 17
(2) Example of surge protector installation
An example of installing the surge protector in the machine control panel is shown below.
A short-circuit fault will occur in the surge protector if a surge exceeding the tolerance is applied.
Thus, install a circuit protection breaker in the stage before the surge protector. Note that almost no
current flows to the surge protector during normal use, so a breaker installed as the circuit
protection for another device can be used for the surge protector.
Installing the surge absorber
CAUTION
1. The wires from the surge protector should be connected without extensions.
2. If the surge protector cannot be installed just with the enclosed wires, keep
the wiring length of A and B to 2m or less. If the wires are long, the surge
protector's performance may drop and inhibit protection of the devices in the
panel.
3. Surge protector to be selected varies depending on input power voltage.
NC unit
Control panel
(relay panel,
etc.)
(1) Surge protector
(Protection across phases)
Other device
(panel power
su
pp
l
y,
etc.
)
Panel earth
leakage
breaker
Input
power
Breaker
AC reactor
Transformer
Grounding
Grounding plate
Factory
power
B
A
MC
Contactor
Breaker
Breaker
Power supply
unit
and
drive unit
Other device
(panel power
supply, etc.)
(2) Surge protector
(Protection across each phase's grounding)
A4 - 1
Appendix 4. Servo/spindle drive unit categories based
on higher harmonic suppression
countermeasure guidelines
Appendix 4-1 Servo/spindle drive unit circuit categories based on higher harmonic suppression
countermeasure guidelines..........................................................................................A4-2
Appendix 4. Servo/spindle drive unit categories based on higher harmonic suppression countermeasure guidelines
A4 - 2
Appendix 4-1 Servo/spindle drive unit circuit categories based on higher harmonic
suppression countermeasure guidelines
Refer to the following table and calculate the circuit category (conversion coefficient) and the power
capacity based on higher harmonic suppression countermeasure guidelines.
Circuit category
Name Model
Circuit
category
Circuit type
Conversion
coefficient
TRS Series
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
MR-S1/S2/S3
MR-S11/12 Series
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
MDS-A-SVJ
MDS-B-SJV2
MR-J2-CT Series
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
AC servo
drive unit
MDS-A-V1/V2
MDS-B-V1/V14/V2/V24
MDS-C1-V1/V2 Series
3
3-phase bridge (smoothing
capacitor) with AC reactor
K32 = 1.8
SFJ/SGJ Series
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
MDS-A-SPJ
MDS-B-SPJ2 Series
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
MDS-A-CSP-370/450
3
3-phase bridge (smoothing
capacitor) with no reactor
K31 = 3.4
AC spindle
drive unit
MDS-A-SP/SPA
MDS-B-SP/SPA/SPH/SPM/SPX
MDS-C1-SP/SPA/SPM/SPX Series
3
3-phase bridge (smoothing
capacitor) with no AC
reactor
K32 = 1.8
Usage conditions: The power supply unit (MDS-A/B/C1-CV Series) applies when using the AC reactor (B-AL Series). When
using the MDS-A-CR Series, calculate using the conversion coefficient K31 = 3.4 (no reactor).
Power facility capacity
Type
Rated
capacity
[kVA]
Type
Rated
capacity
[kVA]
Type
Rated
capacity
[kVA]
MDS-A/B/C1-SP-37 4.61 MDS-A/B/C1-V1-03 0.6 MDS-A/B/C1-V2-0503 1.6
MDS-A/B/C1-SP-55 6.77 MDS-A/B/C1-V1-05 1.0 MDS-A/B/C1-V2-0505 2.0
MDS-A/B/C1-SP-75 9.07 MDS-A/B/C1-V1-10 1.6 MDS-B/C1-V2-1003 2.2
MDS-A/B/C1-SP-110 13.1 MDS-A/B/C1-V1-20 2.7 MDS-A/B/C1-V2-1005 2.6
MDS-A/B/C1-SP-150 17.6 MDS-A/B/C1-V1-35 4.7 MDS-A/B/C1-V2-1010 3.2
MDS-A/B/C1-SP-185 21.8 MDS-A/B/C1-V1-45 5.9 MDS-A/B/C1-V2-2010 4.3
MDS-A/B/C1-SP-220 25.9 MDS-A/B/C1-V1-70 9.0 MDS-A/B/C1-V2-2020 5.4
MDS-A/B/C1-SP-260 30.0 MDS-A/B/C1-V1-90 11.5 MDS-A/B/C1-V2-3510 6.3
MDS-A/B/C1-SP-300 34.7 MDS-A/B/C1-V2-3520 7.4
MDS-B-SP-370 42.8 MDS-A/B/C1-V2-3535 9.4
MDS-B-SP-450 52.1 MDS-A/B/C1-V2-4520 8.6
MDS-B-SP-550 63.7 MDS-A/B/C1-V2-4535 10.6
MDS-C1-V2-4545 11.8
MDS-C1-V2-7070 18.0
SP: Including SPA/SPH/SPM/SPX V1: Including V14 V2: Including V24