MDS-C1-SPA Series INSTRUCTION MANUALib1500152(eng)a.pdf - 第72页

3. Setup 3 - 12 No. Abbr. Parameter name Details Setting rang e (Unit) Standard setting F E D C B A 9 8 7 6 5 4 3 2 1 0 amp rtyp ptyp bit Explanation 0 1 2 When the CN4 connector of the drive unit and the CN4 or CN9 conn…

100%1 / 234
3. Setup
3 - 11
No. Abbr. Parameter name Details
Setting range
(Unit)
Standard
setting
Set the spindle drive unit's capacity type.
(HEX setting)
Setting Unit capacity
S
etting Unit capacity
0000 --- 0010 MDS-B-SPA-550
0001 MDS-B-SPA-075 0011 ---
0002 MDS-B-SPA -15 0012 ---
0003 MDS-B-SPA -22 0013 ---
0004 MDS-B-SPA -37 0014 ---
0005 MDS-C1-SPA-55 0015 ---
SP039 ATYP Drive unit type 0006 MDS-C1-SPA-75 0016 --- 0000 to FFFF 0000
0007 MDS-C1-SPA-110 0017 ---
0008 MDS-C1-SPA-150 0018 ---
0009 MDS-C1-SPA-185 0019 ---
000A MDS-C1-SPA-220 001A ---
000B MDS-C1-SPA-260 001B ---
000C MDS-C1-SPA-300 001C ---
000D MDS-B-SPA -370 001D ---
000E MDS-B-SPA -450 001E ---
000F MDS-B-SPA -04 001F ---
This parameter is valid when SP034 (SFNC2)/bit0 is set
to "0". (Old type of motor)
Set the appropriate motor number from the standard
motors listed below.
(HEX setting)
Setting Motor name
Maximum
speed
Corresponding
drive unit
0000 --- --- ---
0001 SJ-2.2A 10000 r/min MDS-B-SPA -22
0002 SJ-3.7A 10000 r/min MDS-B-SPA -37
0003 SJ-5.5A 8000 r/min MDS-C1-SPA-55
0004 SJ-7.5A 8000 r/min MDS-C1-SPA-75
0005 SJ-11A 6000 r/min MDS-C1-SPA-110
0006 SJ-15A 6000 r/min MDS-C1-SPA-150
0007 SJ-18.5A 6000 r/min MDS-C1-SPA-185
0008 SJ-22A 4500 r/min MDS-C1-SPA-220
0009 SJ-26A 4500 r/min MDS-C1-SPA-260
SP040 MTYP Motor type 000A SJ-30A 4500 r/min MDS-C1-SPA-300 0000 to FFFF 0000
000B --- --- ---
000C --- --- ---
000D --- --- ---
000E --- --- ---
000F --- --- ---
0010 --- --- ---
0011 SJ-N0.75A 10000 r/min MDS-B-SPA-075
0012 SJ-N1.5A 10000 r/min MDS-B-SPA-15
0013 SJ-N2.2A 10000 r/min MDS-B-SPA-22
0014 SJ-N3.7A 10000 r/min MDS-B-SPA-37
0015 SJ-N5.5A 8000 r/min MDS-C1-SPA-55
0016 SJ-N7.5A 8000 r/min MDS-C1-SPA-75
0017 --- --- ---
0018 --- --- ---
0019 --- --- ---
001A --- --- ---
001B SJ-J2.2A 10000 r/min MDS-B-SPA-22
001C SJ-J3.7A 10000 r/min MDS-B-SPA-37
001D SJ-J5.5A 8000 r/min MDS-C1-SPA-55
001E SJ-J7.5A 8000 r/min MDS-C1-SPA-75
001F --- --- ---
3. Setup
3 - 12
No. Abbr. Parameter name Details
Setting range
(Unit)
Standard
setting
F E D C B A 9 8 7 6 5 4 3 2 1 0
amp rtyp ptyp
bit Explanation
0
1
2
When the CN4 connector of the drive unit and the CN4 or CN9 connector
of the power supply are connected, setting below is necessary.
To validate the external emergency stop function, add 40h.
3
Setting 0x 1x 2x 3x 4x 5x 6x 7x 8x
4
x0 Not used CV-300
5
x1 CV-110 CR-10
6
x2 CV-220 CR-15
7
ptyp
x3 CR-22
x4 CV-37 CR-37
x5 CV-150
MDS-B-
CVE-450
MDS-B-
CVE-550
x6 CV-55 CV-260 CR-55
x7 CV-370
x8 CV-75 CR-75
x9 CV-185 CR-90
SP041 PTYP Power supply type
8
Set the regenerative resistor type when MDS-A-CR is used.
9 Setting Regenerative resistor model name
Resistance
value
Capacity
A0
MDS-C1-CV (Setting when using power supply regeneration)
B
rtyp
1
GZG200W260HMJ (Note)
26
80W
2
GZG300W130HMJ×2
26
150W
3
MR-RB30
13
300W
4
MR-RB50
13
500W
5
GZG200W200HMJ×3
6.7
350W
6
GZG300W200HMJ×3
6.7
500W
7
R-UNIT-1
30
700W
8
R-UNIT-2
15
700W
9
R-UNIT-3
15
2100W
A~F
No setting
(Note) When MDS-B-SPA-370, 450 or 550 is used, set "0" even if power
regeneration type is applied.
C
D
E
F
amp
Always set to "0".
SP042 Not used. Set "0". 0 0
SP043 Not used. Set "0". 0 0
SP044 Not used. Set "0". 0 0
SP045 CSNT* Dual cushion timer
Set the cycle to add the increment values in the dual
cushion process.
When this setting value is increased, the dual cushion will
increase, and the changes in the speed during
acceleration/deceleration will become gradual.
0 to 1000 (ms) 0
Parameters having an abbreviation with "*" (CSNT*, etc.) are validated right after the settings are changed by the personal
computer, without turning the spindle drive unit's power ON and OFF.
3. Setup
3 - 13
No. Abbr. Parameter name Details
Setting range
(Unit)
Standard
setting
SP046 CSN2
Speed command dual
cushion
For an acceleration/deceleration time constant defined in
SP019 (CSN1) , this parameter is used to provide smooth
movement only at the start of acceleration/deceleration.
As the value of this parameter is smaller, it moves
smoother but the acceleration/deceleration time becomes
longer.
To make this parameter invalid, set "0".
0 to 1000 0
SP047 SDTR
Speed detection reset
value
Set the reset hysteresis width for a speed detection set
value defined in SP020 (SDTS).
0 to 1000
(r/min)
30
SP048 SUT Speed reach range
Set the speed deviation rate with respect to the
commanded speed for output of the speed reach signal.
0 to 100 (%) 15
SP049 TLM2* Torque limit 2
Set the torque limit rate when the torque limit signal 1, 2 or
1, 2, 3 are assigned to the general-purpose input and only
the torque limit 2 is turned ON.
0 to 120 (%) 20
SP050 TLM3* Torque limit 3
Set the torque limit rate when the torque limit signal 1, 2 or
1, 2, 3 are assigned to the general-purpose input and the
torque limit 1, 2 are turned ON.
0 to 120 (%) 30
SP051 TLM4* Torque limit 4
Set the torque limit rate when the torque limit signal 1, 2, 3
are assigned to the general-purpose input and the torque
limit 3 is turned ON.
0 to 120 (%) 40
SP052 TLM5* Torque limit 5
Set the torque limit rate when the torque limit signal 1, 2, 3
are assigned to the general-purpose input and the torque
limit 1, 3 are turned ON.
0 to 120 (%) 50
SP053 TLM6* Torque limit 6
Set the torque limit rate when the torque limit signal 1, 2, 3
are assigned to the general-purpose input and the torque
limit 2, 3 are turned ON.
0 to 120 (%) 60
SP054 TLM7* Torque limit 7
Set the torque limit rate when the torque limit signal 1, 2, 3
are assigned to the general-purpose input and the torque
limit 1, 2, 3 are all turned ON.
0 to 120 (%) 70
SP055 SETM
Excessive speed
deviation timer
Set the timer value until the excessive speed deviation
alarm is output.
The value of this parameter should be longer than the
acceleration/deceleration time.
0 to 160 (s) 12
SP056 PYVR*
Variable excitation
(min value)
Set the minimum value of the variable excitation rate.
Select a smaller value when gear noise is too high.
0 to 100 (%) 50
SP057 STOD*
Constant transition
judgment value
Set the value for judging when changing the speed
command from a constant to acceleration/deceleration.
When "0" is set, judge the speed with 12 r/min.
Motor maximum speed under 10000r/min: Set “7”.
Motor maximum speed 10000r/min or more: Set “40”.
Note that “20” is set when using some of the ultra
high-speed motors.
0 to 50 (r/min) 7
SP058 Not used. Set "0". 0 0
SP059 MKT*
Winding changeover
base shut-off timer
Set the base shut-off time for contactor switching at coil
changeover.
Note that the contactor may be damaged with burning if
the value of this parameter is too small.
50 to 10000
(ms)
150
SP060 MKT2*
Current limit timer after
coil changeover
Set the current limit time to be taken after completion of
contactor switching at coil changeover.
0 to 10000
(ms)
500
SP061 MKIL*
Current limit value after
coil changeover
Set the current limit value during a period defined in
SP060 (MKT2) after completion of contactor switching at
coil changeover.
0 to 120 (%) 75
SP062 Not used. Set to "0". 0 0
SP063 OLT*
Overload alarm detection
time
Set the time constant for detection of the motor overload
alarm.
(For machine tool builder adjustment)
0 to 1000 (s) 60
SP064 OLL*
Overload alarm detection
level
Set the detection level of the motor overload alarm.
(For machine tool builder adjustment)
0 to 120 (%) 110
SP065 VCGN1*
Target value of variable
speed loop proportional
gain
Set the magnification of speed loop proportional gain with
respect to SP022 (VGNP1) at the maximum motor speed
defined in SP017 (TSP).
0 to 100 (%) 100
Parameters having an abbreviation with "*" (TML2*, etc.) are validated right after the settings are changed by the personal
computer, without turning the spindle drive unit's power ON and OFF.