Chapter 1 Errors Displayed by the GL-541E
0003
Cause: The mark-reading sequence that should be referred to comes
after the glue sequences in the sequence data.
Remedy: Using the F4G program editor, input the mark-reading
sequence before the glue sequence data and then retransmit
the program to the machine.
0004
Cause: The mark-reading sequence that should be referred to is
skipped.
Remedy: Using the F4G program editor, cancel the mark-reading
sequence skip flag or create a new mark-reading sequence.
Then retransmit the program to the machine.
0010
Cause: An attempt was made to execute glue sequences either
without executing the required mark-reading sequences or
after a mark-reading sequence error had occurred.
Remedy: If there is no mark-reading sequence, use the F4G program
editor to set such a sequence. If the mark-reading sequence
has stopped because of an error then execute the sequence
again.
0011
Cause: The fiducial marks specified in the “M Mark #” and “S Mark
#” columns of a glue sequence do not exist.
Remedy: Using the F4G program editor, check the relevant columns
for the sequences in question in mark data.
Either the mark-reading sequences must have the same block
number “Block #” as the glue sequences they refer to, or the
mark-reading sequences must have block number zero.
0020
Cause: G data has not been input in a glue sequence.
Remedy: Input G data into the glue sequence using the F4G program
editor, then retransmit the program to the machine.
GL-541E Operation

Chapter 1 Errors Displayed by the GL-541E
Part 6
PCB Transport Error: #
Cause: A board could not be properly transported on the conveyor
indicated by #.
Remedy: Transmit Proper and status data to the machine. The conveyor types which
may be indicated by # are identified below.
“Prev.” — Previous stage conveyor
“MCID” — MCID conveyor
“IN” — In-conveyor
“OUT” — Out-conveyor
“NEXT” — Next stage conveyor
PCB Stopper Error
Cause: The upper or lower limit sensor for the board stopper has not been tripped
within 5 seconds after the board stopper has been signaled to rise or drop.
Remedy: Check for foreign objects (for example, a board) that may hinder stopper
movement.
If such a foreign object is found, remove it. If no such object is found check
the stopper upper and lower limit sensors using the I/O board. For details
on performing checks with the I/O map, refer to Part 3, “Description of
Commands” and to Appendix A concerning the GL-541E I/O map. For
further information on sensor adjustment procedures see the
GL-541E Maintenance Manual.
PCB Setting Error
Cause: If a board is on the main conveyor an attempt to load a board has been
made. If a board is not presently on the main conveyor then an attempt to
unload a board has been made.
Remedy: Check the condition of the main conveyor for any unnatural movement. If
no such movement is found, check the MAIN ARRV CHK sensor on the
main conveyor using the I/O check function.
For details on performing checks with the I/O map, refer to Part 3,
“Description of Commands” and to Appendix A concerning the GL-541E
I/O map. For further information on sensor adjustment procedures see the
GL-541E Maintenance Manual.
Conv. PLC Alarm
Cause: The CPU module (board loader PLC) is not working properly.
Remedy: Contact Fuji.
6 - 6
Version 2.0
GL-541E Operation

Part 6
6 - 7
Version 2.0
Chapter 1 Errors Displayed by the GL-541E
PLC Link Alarm
Cause: Communication with the CPU module (board loader PLC) is not possible.
Remedy: Check the connection of the signal wires linking the VME interface board
and the CPU module (board loader PLC). For details on the VME interface
board and the CPU module (board loader PLC) refer to Part 1, “GL-541E
Machine Operation”, section 1.3, “Control System”.
Loader ROM Error
Cause: The machine ROM version is older than that of the board loader PLC.
Remedy: Contact Fuji.