11 - 47 11. OPTIONS AND AUXILI ARY EQUIPMENT (3) Outside dimensions of the power regeneration converters [Unit : mm] AA A C F K EE BA B E D 2- D hole Rati ng plat e Front cover Display panel window Mounting foot (removab…

100%1 / 424
11 - 46
11. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
NFB
MC
Servo amplifier
L
11
L21
L1
L
2
L3
SK
ON
MC
BC
NPC
RDY
SE
Alarm
output
RDY
output
A
B
C
5m or less
Operation ready
MC
OFF
EMG
ALM
RA2
FR-RC-(H)
Ready
Power factor improving reactor
(Note 7)
R/L
1
S/L2
T/L
3
B
C
RRX
R
SX
S
TX
T
Phase detection
terminals
(Note 1)
Power regeneration
converter FR-RC-(H)
N/
P/
EM1
RA
DOCOM
DICOM
ALM Trouble
(Note 3)
DOCOM
Forced stop
24VDC
P2P1
(Note 4)
(Note 2)
CN3 CN3
(Note 5)
(Note 6)
Power supply
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain
removed, the FR-RC-(H) will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected
to P terminal and C terminal.
3. When setting not to output Trouble (ALM) with parameter change, configure power supply circuit for turning
magnetic contactor off after detecting an occurrence of alarm on the controller side.
4. Between P
1
and P
2
(P
1
and P for 11kW to 22kW) is connected by default.
5. Stepdown transformer is required for coil voltage of magnetic contactor more than 200V class in 400V class servo
amplifiers.
6. Refer to section 1.3 for the power supply specification.
7. For selection of power factor improving AC reactors, refer to "Power Regeneration Converter FR-RC Instruction Manual
(IB(NA)66330)".
11 - 47
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outside dimensions of the power regeneration converters
[Unit : mm]
AA
A
C
F
K
EE
BA
B
E
D
2- D hole
Rating plate
Front cover
Display
panel
window
Mounting foot (removable)
Mounting foot
movable
Cooling fan
Heat generation area outside mounting dimension
Power
regeneration
converter
A AA B BA C D E EE K F
Approx. mass
[kg(Ib)]
FR-RC-15K 270 200 450 432 195 10 10 8 3.2 87
19
(41.888)
FR-RC-H15K
340 270 600 582 195 10 10 8 3.2 90
31
(68.343)
FR-RC-30K
FR-RC-H30K
FR-RC-55K
480 410 700 670 250 12 15 15 3.2 135
55
(121.3)
FR-RC-H55K
(4) Mounting hole machining dimensions
When the power regeneration converter is fitted to a totally enclosed type box, mount the heat generating
area of the converter outside the box to provide heat generation measures. At this time, the mounting hole
having the following dimensions is machined in the box.
[Unit : mm]
(AA)
(BA)
b
a
(2- D hole)
(Mounting hole)
Power
regeneration
converter
a b D AA BA
FR-RC-15K 260 412 10 200 432
FR-RC-H15K
FR-RC-30K 330 562 10 270 582
FR-RC-H30K
FR-RC-55K
470 642 12 410 670
FR-RC-H55K
11 - 48
11. OPTIONS AND AUXILIARY EQUIPMENT
11.5 Power regeneration common converter
POINT
Use the FR-CV for the servo amplifier of 200V class and the FR-CV-H for that
of 400V class.
For details of the power regeneration common converter FR-CV-(H), refer to
the FR-CV-(H) Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L
1
, L
2
, L
3
) of
the servo amplifier. Doing so will fail the servo amplifier and FR-CV-(H).
Connect the DC power supply between the FR-CV-(H) and servo amplifier
with correct polarity. Connection with incorrect polarity will fail the FR-CV-(H)
and servo amplifier.
Two or more FR-CV-(H)'s cannot be installed to improve regeneration
capability. Two or more FR-CV-(H)'s cannot be connected to the same DC
power supply line.
When using the power regeneration common converter, set parameter No.PA02 to "
01".
(1) Model
Symbol
Voltage class
None 200V class
H 400V class
Symbol
Capacity [kW]
7.5K 7.5
11K 11
15K 15
22K 22
30K 30
37K 37
55K 55
Capacity
(2) Selection
The power regenerative common converter FR-CV can be used for the servo amplifier of 200V class with
750 to 22kW and that of 400V class with 11k to 22kW. The following shows the restrictions on using the
FR-CV-(H).
(a) Up to six servo amplifiers can be connected to one FR-CV-(H).
(b) FR-CV-(H) capacity [W] Total of rated capacities [W] of servo amplifiers connected to FR-CV-(H) 2
(c) The total of used servo motor rated currents should be equal to or less than the applicable current [A] of
the FR-CV-(H).
(d) Among the servo amplifiers connected to the FR-CV-(H), the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].