11 - 67 11. OPTIONS AND AUXILI ARY EQUIPMENT 11.11 Selection example of wires POINT Refer to section 11.1.5 for SSCNET cable. Wires indicated in this section are separated wi res. When using a cable for power line (U, V,…

11 - 66
11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Fitting method
Fit using the
assembling
screws.
Attachment
Servo
amplifier
Attachment
Servo
amplifier
Punched
hole
Control box
a. Assembling the heat sink outside mounting attachment b. Installation to the control box
(4) Outline dimension drawing
[Unit: mm]
236
280
Approx. 260
20
3.2
105155
Approx. 260
Approx. 11.5
Servo
amplifier
Servo amplifier
Mounting
hole
Panel
Panel
Attachment

11 - 67
11. OPTIONS AND AUXILIARY EQUIPMENT
11.11 Selection example of wires
POINT
Refer to section 11.1.5 for SSCNET cable.
Wires indicated in this section are separated wires. When using a cable for
power line (U, V, and W) between the servo amplifier and servo motor, use a
600V grade EP rubber insulated chloroprene sheath cab-tire cable (2PNCT).
For selection of cables, refer to appendix 6.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper
wires rated at 60
(140 ) or more for wiring. To comply with other
standards, use a wire that is complied with each standard
Selection condition of wire size is as follows.
Construction condition: One wire is constructed in the air
Wire length: 30m or less
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or equivalent.
C
P
U
V
W
L
11
L21
U
V
W
L
1
L
2
L3
B1
B2
1) Main circuit power supply lead
Servo amplifier
3) Motor power supply lead
Servo motor
Power supply
Motor
Electro-
magnetic
brake
Encoder
4) Electromagnetic
brake lead
Encoder cable
2) Control power supply lead
(Note)
C
P
N
Regenerative option
4) Regenerative option lead
Cooling fan
BU
BV
BW
6) Cooling fan lead
Power supply
7) Thermal
OHS1
OHS2
Thermal
8) Power regeneration
converter lead
Power regeneration
converter
Note. There is no L
3
for 1-phase 100 to 120VAC power supply.

11 - 68
11. OPTIONS AND AUXILIARY EQUIPMENT
(a) When using the 600V Polyvinyl chloride insulated wire (IV wire)
Selection example of wire size when using IV wires is indicated below.
Table 11.1 Wire size selection example 1 (IV wire)
Servo amplifier
Wires [mm
2
] (Note 1, 4)
1)
L
1 L2 L3
2) L11 L21
3)
U
V W
4) P C 5) B1 B2
6)
BU
BV BW
7)
OHS1 OHS2
MR-J3-10B(1)
MR-J3-20B(1)
MR-J3-40B(1) 1.25(AWG16)
MR-J3-60B 2(AWG14)
1.25(AWG16)
2(AWG14)
MR-J3-70B
MR-J3-100B
2(AWG14)
MR-J3-200B
MR-J3-350B 3.5(AWG12) 3.5(AWG12)
MR-J3-500B
(Note 2)
5.5(AWG10): a
1.25(AWG16):
h
5.5(AWG10): a 2(AWG14): g
MR-J3-700B
(Note 2)
8(AWG8): b 8(AWG8): b 3.5(AWG12): a
2(AWG14)
(Note 3)
1.25(AWG16)
(Note 3)
MR-J3-11KB
(Note 2)
14(AWG6): c 22(AWG4): d
5.5(AWG10): j 1.25(AWG16)
MR-J3-15KB
(Note 2)
22(AWG4): d
1.25(AWG16):
g
30(AWG2): e 2(AWG14) 1.25(AWG16)
MR-J3-22KB
(Note 2)
50(AWG1/0):
f
60(AWG2/0): f 5.5(AWG10): k
MR-J3-60B4
1.25(AWG16)
MR-J3-100B4 2(AWG14) 1.25(AWG16) 2(AWG14)
MR-J3-200B4 2(AWG14)
MR-J3-350B4 2(AWG14): g
1.25(AWG16):
h
2(AWG14): g
2(AWG14): g
MR-J3-500B4
(Note 2)
5.5(AWG10): a 5.5(AWG10): a
MR-J3-700B4
(Note 2)
2(AWG14)
(Note 3)
1.25(AWG16)
(Note 3)
MR-J3-11KB4
(Note 2)
8(AWG8): l 8(AWG8): l 3.5(AWG12): j
MR-J3-15KB4
(Note 2)
14(AWG6): c
1.25(AWG16):
g
22(AWG4): d 5.5(AWG10): j 2(AWG14) 1.25(AWG16)
MR-J3-22KB4
(Note 2)
14(AWG6): m 22(AWG4): n 5.5(AWG10): k
Note 1. Alphabets in the table indicate crimping tools. For crimping terminals and applicable tools, refer to (1) (c) in this section.
2. When connecting to the terminal block, be sure to use the screws which are provided with the terminal block.
3. For the servo motor with a cooling fan.
4. Wires are selected based on the highest rated current among combining servo motors.
Use wires 8) of the following sizes with the power regeneration converter (FR-RC-(H)).
Model Wires[mm
2
]
FR-RC-15K 14(AWG6)
FR-RC-30K 14(AWG6)
FR-RC-55K 22(AWG4)
FR-RC-H15K 14(AWG6)
FR-RC-H30K 14(AWG6)
FR-RC-H55K 14(AWG6)