sh030051g.pdf - 第346页

13 - 45 13. SERVO AMPLIFIERS WI TH A LARGE CAPACITY ( 30k TO 55kW ) 2) When CNP1 is invalid When the forced stop (EM1 ) is input in the converte r unit, the drive unit in operatio n stops and Main circuit off warning (E9…

100%1 / 424
13 - 44
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY
(
30k TO 55kW
)
(3) Forced stop (EM1) ON/OFF timing chart
(a) When control function of magnetic controller is enabled
1) Converter unit
When the forced stop (EM1) is made valid in the converter unit, the magnetic contactor is turned off
and the main circuit power supply is shut off. The drive unit in operation stops, and Main circuit off
warning (E9) appears. When the forced stop (EM1) is deactivated in the converter unit, the magnetic
contactor is turned on, the main circuit power is supplied, and then the drive unit automatically
resumes the operation.
(3s)
Electromagnetic brake
interlock (MBR)
(10ms)
(3s)
(3s)
ON
OFF
Base circuit
ON
OFF
Servo motor speed
Converter main circuit
off warning
ON
OFF
Main circuit
power supply
ON
OFF
Forced stop (EM1)
Invalid (ON)
Valid (OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake
operation delay time
Electromagnetic brake release
(Note)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
13 - 45
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY
(
30k TO 55kW
)
2) When CNP1 is invalid
When the forced stop (EM1) is input in the converter unit, the drive unit in operation stops and Main
circuit off warning (E9) appears. When the forced stop (EM1) is deactivated in the converter unit, the
drive unit automatically resumes the operation.
(3s)
(3s)
(3s)
Electromagnetic brake
interlock (MBR)
(10ms)
ON
OFF
Base circuit
ON
OFF
Servo motor speed
Converter main circuit
off warning
ON
OFF
Main circuit
power supply
ON
OFF
Forced stop (EM1)
Invalid (ON)
Valid (OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake
operation delay time
Electromagnetic brake release
(Note)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated
13 - 46
13. SERVO AMPLIFIERS WITH A LARGE CAPACITY
(
30k TO 55kW
)
(b) Forced stop in the drive unit
When the forced stop (EM1) is made valid in the drive unit, the drive unit in operation stops, Main circuit
off warning (E9) appears, and then the drive unit is forcedly stopped. Configure to activate the forced
stop (EM1) of the drive unit as the forced stop (EM1) of the converter unit is activated, and to activate
the forced stop (EM1) of the converter unit as the forced stop (EM1) of the drive unit is activated. Shut
off the power supply by the external sequence as soon as the forced stop (EM1) is activated.
Electromagnetic brake
interlock (MBR)
(10ms)
(3s)
(3s)
Invalid (ON)
Valid (OFF)
Base circuit
ON
OFF
Servo motor speed
Forced stop command
(from controller) or
forced stop (EM1)
ON
OFF
Main circuit
power supply
ON
OFF
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake
operation delay time
Electromagnetic brake release
(Note)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated