11 - 54 11. OPTIONS AND AUXILI ARY EQUIPMENT (5) Other precautions (a) Always use the FR-CVL-(H) as the power factor imp roving reac tor. Do not use the FR-BAL or FR-BEL. (b) The inputs/outputs (ma in circuits) of the FR…

100%1 / 424
11 - 53
11. OPTIONS AND AUXILIARY EQUIPMENT
(b) Example of selecting the wire sizes
When connecting multiple servo amplifiers, always use junction terminals for wiring the servo amplifier
terminals P, N. Also, connect the servo amplifiers in the order of larger to smaller capacities.
1) 200V class
R2/L
1
S2/L
2
T2/L3
R/L
11
S/L21
T/MC1
P/L
N/L
P
N
50mm
2
Overall wiring length 5m or less
First unit:
50mm
2
assuming that the total of servo amplifier
capacities is 27.5kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
P
N
P
N
P
N
22mm
2
8mm
2
2mm
2
22mm
2
8mm
2
3.5mm
2
2mm
2
Junction terminals
Wire as short as possible.
Second unit:
22mm
2
assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
Third unit:
8mm
2
assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
Fourth unit:
2mm
2
assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
FR-CV-55K Servo amplifier (15kW)
Servo amplifier (7kW)
Servo amplifier (3.5kW)
Servo amplifier (2kW)
(Note)
(Note)
(Note)
(Note)
Note. When using the servo amplifier of 7kW or less, make sure to disconnect the wiring of built-in regenerative resistor (3.5kW or
less: P-D, 5k/7kW: P-C).
2) 400V class
R2/L
1
S2/L2
T2/L
3
R/L
11
S/L
21
T/MC1
P/L+
N/L-
P
N
22mm
2
P
N
P
N
P
N
14mm
2
5.5mm
2
2mm
2
14mm
2
5.5mm
2
2mm
2
2mm
2
FR-CV-55K
Servo amplifier (7kW)
Servo amplifier (3.5kW)
Servo amplifier (2kW)
(Note)
Overall wiring length 5m or less
First unit:
22mm
2
assuming that the total of servo amplifier
capacities is 27.5kW since 15kW + 7kW + 3.5kW
+ 2.0kW = 27.5kW.
Junction terminals
Wire as short as possible.
Second unit:
14mm
2
assuming that the total of servo amplifier
capacities is 15kW since 7kW + 3.5kW + 2.0kW =
12.5kW.
Third unit:
5.5mm
2
assuming that the total of servo amplifier
capacities is 7kW since 3.5kW + 2.0kW = 5.5kW.
Fourth unit:
2mm
2
assuming that the total of servo amplifier
capacities is 2kW since 2.0kW = 2.0kW.
Servo amplifier (15kW)
(Note)
(Note)
Note. These servo amplifiers are development forecasted.
11 - 54
11. OPTIONS AND AUXILIARY EQUIPMENT
(5) Other precautions
(a) Always use the FR-CVL-(H) as the power factor improving reactor. Do not use the FR-BAL or FR-BEL.
(b) The inputs/outputs (main circuits) of the FR-CV-(H) and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment (such as
AM radios) used near them. In this case, interference can be reduced by installing the radio noise filter
(FR-BIF-(H)) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV-(H) and servo
amplifiers should be 5m or less, and the wiring must be twisted.
11 - 55
11. OPTIONS AND AUXILIARY EQUIPMENT
(6) Specifications
Power regeneration common converter
FR-CV-
Item
7.5K 11K 15K 22K 30K 37K 55K
Total of connectable servo amplifier capacities [kW] 3.75 5.5 7.5 11 15 18.5 27.5
Maximum servo amplifier capacity [kW] 3.5 5 7 11 15 15 22
Output
Total of connectable servo motor
rated currents [A]
33 46 61 90 115 145 215
Regenerative
braking torque
Short-time
rating
Total capacity of applicable servo motors, 300% torque, 60s (Note 1)
Continuous
rating
100% torque
Power supply
Rated input AC voltage/frequency Three-phase 200 to 220V 50Hz, 200 to 230V 60Hz
Permissible AC voltage fluctuation Three-phase 170 to 242V 50Hz, 170 to 253V 60Hz
Permissible frequency fluctuation 5%
Power supply capacity (Note 2) [kVA] 17 20 28 41 52 66 100
Protective structure (JEM 1030), cooling system Open type (IP00), forced cooling
Environment
Ambient temperature -10
to +50 (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Ambience Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude, vibration 1000m or less above sea level, 5.9m/s
2
2 or less
No-fuse breaker or leakage current breaker
30AF
30A
50AF
50A
100AF
75A
100AF
100A
225AF
125A
225AF
125A
225AF
175A
Magnetic contactor S-N20 S-N35 S-N50 S-N65 S-N95 S-N95 S-N125
Power regeneration common converter
FR-CV-H
Item
22K 30K 37K 55K
Total of connectable servo amplifier capacities [kW] 11 15 18.5 27.5
Maximum servo amplifier capacity [kW] 11 15 15 22
Output
Total of connectable servo motor
rated currents [A]
43 57 71 110
Regenerative
braking torque
Short-time
rating
Total capacity of applicable servo motors, 300%
torque, 60s (Note 1)
Continuous
rating
100% torque
Power supply
Rated input AC voltage/frequency Three-phase 380 to 480V, 50Hz/60Hz
Permissible AC voltage fluctuation Three-phase 323 to 528V, 50Hz/60Hz
Permissible frequency fluctuation 5%
Power supply capacity [kVA] 41 52 66 100
Protective structure (JEM 1030), cooling system Open type (IP00), forced cooling
Environment
Ambient temperature -10
to +50 (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Ambience
Indoors (without corrosive gas, flammable gas, oil
mist, dust and dirt)
Altitude, vibration 1000m or less above sea level, 5.9m/s
2
2 or less
No-fuse breaker or leakage current breaker
60AF
60A
100AF
175A
100AF
175A
225AF
125A
Magnetic contactor S-N25 S-N35 S-N35 S-N65
Note 1. This is the time when the protective function of the FR-CV-(H) is activated. The protective function of the servo amplifier is
activated in the time indicated in section 10.1.
2. When connecting the capacity of connectable servo amplifier, specify the value of servo amplifier.