11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 49
(4) Selection example of wires used for wiring
POINT
Selection conditions of wire size are as follows.
600 V grade heat-resistant polyvinyl chloride insulated wire (HIV wire)
Construction condition: Single wire set in midair
(a) Wire sizes
1) Across P to P4, N to N
The following table indicates the connection wire sizes of the DC power supply (P4, N- terminals)
between the FR-CV and servo amplifier.
Total of servo amplifier capacities [kW] Wire [mm
2
]
1 or less 2 (AWG 14)
2 3.5 (AWG 12)
5 5.5 (AWG 10)
7 8 (AWG 8)
11 14 (AWG 6)
15 22 (AWG 4)
22 50 (AWG 1/0)
27.5 50 (AWG 1/0)
The following table indicates the connection wire sizes of the DC power supply (P4, N- terminals)
between the FR-CV-H and servo amplifier.
Total of servo amplifier capacities [kW] Wire [mm
2
]
2 or less 2 (AWG 14)
3.5 3.5 (AWG 12)
5 5.5 (AWG 10)
7 5.5 (AWG 10)
11 8 (AWG 8)
15 8 (AWG 8)
22 14 (AWG 6)
27.5 22 (AWG 4)
2) Grounding
For grounding, use the wire of the size equal to or greater than that indicated in the following
table, and make it as short as possible.
Power regeneration common
converter
Grounding wire size
[mm
2
]
FR-CV-7.5K to FR-CV-15K 8 (AWG 8)
FR-CV-22K/FR-CV-30K 22 (AWG 4)
FR-CV-37K/FR-CV-55K 38 (AWG 2)
FR-CV-H7.5K to FR-CV-H15K 3.5 (AWG 12)
FR-CV-H22K/FR-CV-H30K 8 (AWG 8)
FR-CV-H37K/FR-CV-H55K 14 (AWG 6)
11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 50
(b) Example of selecting the wire sizes
When connecting multiple servo amplifiers, always use junction terminals for wiring the servo
amplifier terminals P4, N-. Also, connect the servo amplifiers in the order of larger to smaller
capacities.
1) 200 V class
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
N/L-
P4
N-
50 mm
2
Overall wiring length 5 m or less
First unit:
50 mm
2
assuming that the total of servo amplifier
capacities is 27.5 kW since 15 kW + 7 kW + 3.5 kW
+ 2.0 kW = 27.5 kW.
P4
N-
P4
N-
P4
N-
22 mm
2
8 mm
2
22 mm
2
8 mm
2
3.5 mm
2
5.5 mm
2
Junction terminals
Wire as short as possible.
Second unit:
22 mm
2
assuming that the total of servo amplifier
capacities is 15 kW since 7 kW + 3.5 kW + 2.0 kW =
12.5 kW.
Third unit:
8 mm
2
assuming that the total of servo amplifier
capacities is 7 kW since 3.5 kW + 2.0 kW = 5.5 kW.
Fourth unit:
2 mm
2
assuming that the total of servo amplifier
capacities is 2 kW since 2.0 kW = 2.0 kW.
FR-CV-55K Servo amplifier (15 kW)
Servo amplifier (7 kW)
Servo amplifier (3.5 kW)
Servo amplifier (2 kW)
(Note)
(Note)
(Note)
(Note)
Note. When using the servo amplifier of 7 kW or less, make sure to disconnect the wiring of built-in regenerative resistor (5 kW
or less: P+ and D, 7 kW: P+ and C
)
.
2) 400 V class
R2/L1
S2/L2
T2/L3
R/L11
S/L21
T/MC1
P/L+
N/L-
P4
N-
22 mm
2
Overall wiring length 5 m or less
First unit:
22 mm
2
assuming that the total of servo amplifier
capacities is 27.5 kW since 15 kW + 7 kW + 3.5 kW
+ 2.0 kW = 27.5 kW.
P4
N-
P4
N-
P4
N-
8 mm
2
5.5 mm
2
8 mm
2
5.5 mm
2
2 mm
2
3.5 mm
2
Junction terminals
Wire as short as possible.
Second unit:
8 mm
2
assuming that the total of servo amplifier
capacities is 15 kW since 7 kW + 3.5 kW + 2.0 kW =
12.5 kW.
Third unit:
5.5 mm
2
assuming that the total of servo amplifier
capacities is 7 kW since 3.5 kW + 2.0 kW = 5.5 kW.
Fourth unit:
2 mm
2
assuming that the total of servo amplifier
capacities is 2 kW since 2.0 kW = 2.0 kW.
FR-CV-H55K Servo amplifier (15 kW)
Servo amplifier (7 kW)
Servo amplifier (3.5 kW)
Servo amplifier (2 kW)
(Note)
(Note)
(Note)
(Note)
Note. When using the servo amplifier of 7 kW or less, make sure to disconnect the wiring of built-in regenerative resistor (5 kW
o
r
less: P+ and D, 7 kW: P+ and C
)
.
11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 51
(5) Other precautions
(a) When using the FR-CV-(H), always install the dedicated stand-alone reactor (FR-CVL-(H)). Do not
use the power factor improving AC reactor (FR-HAL-(H)) or power factor improving DC reactor (FR-
HEL-(H)).
(b) The inputs/outputs (main circuits) of the FR-CV-(H) and servo amplifiers include high-frequency
components and may provide electromagnetic wave interference to communication equipment (such
as AM radios) used near them. In this case, interference can be reduced by installing the radio noise
filter (FR-BIF(-H)) or line noise filter (FR-BSF01, FR-BLF).
(c) The overall wiring length for connection of the DC power supply between the FR-CV-(H) and servo
amplifiers should be 5 m or less, and the wiring must be twisted.
(6) Specifications
Power regeneration common
converter FR-CV-_
Item
7.5K 11K 15K 22K 30K 37K 55K
Total of connectable servo amplifier
capacities
[kW] 3.75 5.5 7.5 11 15 18.5 27.5
Maximum servo amplifier capacity [kW] 3.5 5 7 11 15 15 22
Output
Total of connectable servo
motor rated currents
[A] 33 46 61 90 115 145 215
Regenerative
braking torque
Short-time rating Total capacity of applicable servo motors, 300% torque, 60 s (Note 1)
Continuous rating 100% torque
Power
Rated input AC voltage/frequency 3-phase 200 V AC to 220 V AC, 50 Hz, 200 V AC to 230 V AC, 60 Hz
Permissible AC voltage fluctuation 3-phase 170 V AC to 242 V AC, 50 Hz, 170 V AC to 253 V AC, 60 Hz
Permissible frequency fluctuation ±5%
Power supply capacity
(Note 2)
[kVA] 17 20 28 41 52 66 100
IP rating (JEM 1030), cooling method Open type (IP00), forced cooling
Environment
Ambient temperature -10 ˚C to 50 ˚C (non-freezing)
Ambient humidity 5 %RH to 90 %RH (non-condensing)
Ambience
Indoors (no direct sunlight), free from corrosive gas, flammable gas,
oil mist, dust, and dirt
Altitude, vibration resistance 1000 m or less above sea level, 5.9 m/s
2
Molded-case circuit breaker or earth-
leakage current breaker
30AF
30A
50AF
50A
100AF
75A
100AF
100A
125AF
125A
125AF
125A
225AF
175A
Magnetic contactor
S-N20
S-T21
S-N35
S-T35
S-N50
S-T50
S-N65
S-T65
S-N80
S-T80
S-N95
S-T100
S-N125