11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 117
(d)
Mounting dimensional diagram
[Unit: mm]
Approx. 58
510
580
12
236
280
Approx. 260
84
194
20
145
Approx. 400
35
3.2
105155
Approx. 260
Approx. 11.5
Servo
amplifier
Servo amplifier
Mounting
hole
Panel
Panel
Attachment

11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 118
11.19 Mul
tifunction regeneration converter FR-XC-(H)
POINT
For details on the multifunction regeneration converter (FR-XC-(H)), refer to "FR-
XC INSTRUCTION MANUAL (IB(NA)-0600668ENG)".
11.19.1 Mul
tifunction regeneration converters and dedicated stand-alone reactors
Install a dedicated stand-alone reactor on the multifunction regeneration converter FR-XC-(H) according to
the following table.
Multifunction regeneration
converter
Dedicated stand-alone
reactor
FR-XC-7.5K FR-XCL-7.5K
FR-XC-11K FR-XCL-11K
FR-XC-15K FR-XCL-15K
FR-XC-22K FR-XCL-22K
FR-XC-30K FR-XCL-30K
FR-XC-37K FR-XCL-37K
FR-XC-55K FR-XCL-55K
FR-XC-H7.5K FR-XCL-H7.5K
FR-XC-H11K FR-XCL-H11K
FR-XC-H15K FR-XCL-H15K
FR-XC-H22K FR-XCL-H22K
FR-XC-H30K FR-XCL-H30K
FR-XC-H37K FR-XCL-H37K
FR-XC-H55K FR-XCL-H55K
11.19.2 P
recautions
Set the FR-XC-(H) to the common bus regeneration mode by turning on switch 1 of the function
selecting switch (SW2).
Do not supply power to the main circuit power supply terminals (L1/L2/L3) of the servo amplifier. Doing
so may fail the servo amplifier and the FR-XC-(H).
Connect the polarities of the DC power supply between the FR-XC-(H) and the servo amplifier correctly.
Failing to do so may fail the FR-XC-(H) and the servo amplifier.
For 400 V, use the rated voltage and permissible fluctuation of the input power supply within the
following range.
Rated voltage: 3-phase 380 V to 480 V, 50 Hz/60 Hz
Permissible fluctuation: 3-phase 323 V to 528 V, 50 Hz/60 Hz
11.19.3 Servo amplifier settings
When using the FR-XC-(H), set the parameters as follows.
[Pr. PA02]: "_ _ 0 1"
[Pr. PA04]: "0 0 _ _"
[Pr. PC20]: "_ _ _ 1"

11. OPTIONS AND PERIPHERAL EQUIPMENT
11 - 119
11.19.4 Capac
ity selection
(1) Selection conditions
The multifunction regeneration converter FR-XC-(H) can be used with 200 V class servo amplifiers with
capacities of 100 W to 22 kW and 400 V class servo amplifiers with capacities of 600 W to 22 kW. Select
a multifunction regeneration converter based on the following selection conditions.
Number of servo amplifiers to be connected to one FR-XC-(H) is 10 or less
Total capacity of servo amplifiers [kW] ≤ Total capacity of servo amplifiers that can be connected to the
FR-XC-(H) [kW]
Effective value of the total servo motor output power [kW] ≤ Continuous output of the FR-XC-(H) [kW]
Maximum value of the total servo motor output power [kW] ≤ Instantaneous maximum output of the
FR-XC-(H) [kW]
Item
FR-XC-(H)_
7.5K 11K 15K 22K 30K 37K 55K
Rated capacity [kW] 7.5 11 15 22 30 37 55
Maximum number of connectable servo amplifiers 10
Total capacity of connectable servo amplifiers
[kW] (Note)
3.5 (5.5) 5.5 (7.5) 7.5 (11) 22 30 37 55
Continuous output [kW] (Note) 3.5 (5.5) 5.5 (7.5) 7.5 (11) 18.5 22 30 45
Instantaneous maximum output [kW] 11.25 16.5 22.5 33 45 55.5 82.5
Note. Values in parentheses are when six servo amplifiers or less are connected.
(2)
Selection example
The following information explains how to select a multifunction regeneration converter to connect to the
servo amplifiers listed below.
Servo amplifier Servo motor
MR-J4-500B HG-SR502
MR-J4-500B HG-SR502
MR-J4-11KB HG-JR11K1M
MR-J4-22KB HG-JR22K1M
(a) Calc
ulate the running power and regenerative power from the servo motor speed and torque with the
following formulas.
For rotary servo motors
Running power and regenerative power [W] = Servo motor speed [r/min] × Torque [N•m]/9.55
For linear servo motors
Running power and regenerative power [W] = Servo motor speed [m/s] × Thrust [N]
(Running power is indicated by positive values, and regenerative power is indicted by negative
values.)