IPC-TM-650 EN 2022 试验方法.pdf - 第576页

5.4.3 Test to Breakdown, Step-by-Step Test An initial voltage shall be applied equal to 50 of the breakdown voltage in the short-time test, adjusted as shown in Table 1. The voltage shall then be increased in equal incre…

100%1 / 824
opposing
cylindrical rods 6.4 mm in diameter, with edges
rounded to a radius of 0.75 mm. The upper movable elec-
trodes shall weigh 45.35g ± 2g. When 6.4 mm electrodes are
used, it is advisable that they be surrounded by guard elec-
trodes or shrouds.
4.5.1
The
dielectric strength of an insulating material varies
with the thickness of the material and the area and geometry
of the test electrodes, and these should be specified in the
specification. Tests made with different electrodes are not
comparable. Where materials are made up into forms of uni-
form thickness, such as sheets and plates, tests shall be
made upon that thickness of material. In other cases, a thick-
ness of the test specimen and diameter and shape of the
electrode have been selected, which are compatible with con-
venience of testing.
4.6
Equipment Testing Apparatus
4.6.1 For Tests Made in Air
Use
may be made of any well
designed oven of sufficient size to hold the test equipment. It
should be provided with some means of circulating air so that
approximately constant temperature is maintained around the
test specimen and with a thermometer or thermocouple for
measuring the temperature as near the point of test as prac-
ticable to the nearest 1°C.
4.6.2
For Test Under Oil
Use
may be made of an oil bath,
provided with some means for circulating the oil so that the
temperature is substantially uniform around the test speci-
mens and with a thermometer or thermocouple for measuring
the temperature as near the point of test as practicable to the
nearest 1°C.
5
Procedure
5.1 Test Medium
The
medium to be used in the tests
should be specified in the specification. In general, it is prefer-
able to test materials in the medium, whether air or oil, in
which they are to be used. Where conditions of use are not
well defined, materials should be tested in air up to the point
where the breakdown is so high that an excessive amount of
material is required to prevent flashover to excessive burning
of the surface. For specimens having a high breakdown, such
as the thicker and highgrade materials, it is usually necessary
to make dielectric strength tests under oil: however; it should
be understood that breakdown values obtained under oil are
not comparable with those obtained in air.
5.2
Preparing Specimens
5.2.1
In
the preparation of test specimens, care shall be
taken to have the surfaces adjacent to the electrodes parallel
and as plane and smooth as the material permits. The dielec-
tric strength of an insulating material varies with the thickness
of the test specimen. Therefore, tests on specimens of differ-
ent thicknesses are not comparable. The thickness used shall
be the average thickness of the sample measured as specified
in the specification involved.
5.2.2
The
dielectric strength of most insulating materials var-
ies with temperature and humidity. The test coiditions to be
used should be specified in the specification. Usually it is
desirable to determine the dielectric behavior of a material
over the range of temperature and humidity to which it is likely
to be subjected in use. When required, materials may be con-
ditioned in a suitably controlled chamber. The test specimen
shall be kept in the chamber long enough to reach a uniform
temperature and humidity prior to testing. When required, the
dielectric strength tests shall be made on the specimen while
still in the conditioning chamber. For purpose of tests, a high-
voltage conductor may be conveniently carried into the cham-
ber through an insulating bushing.
5.3
Positioning and Care of Electrodes
Electrodes
shall
be held truly coaxial. Where electrodes have flat test faces, the
latter shall be parallel to each other. The test faces shall be
kept smooth and polished and free from pitting.
5.4
Application of Voltage
5.4.1 Test for Specified Minimum Requirement
The
voltage
shall be applied and increased at a uniform rate from
zero to the value specified in the material specification and
shall be held at the value for the specified time. Unless other-
wise specified, the rate of rise per second shall be 5% of the
specified voltage. Note that this test is to check for ability to
withstand a specified voltage and not to determine the break-
down value.
5.4.2
Test to Breakdown, Short-time Test
The
voltage
shall be increased from zero to breakdown at a uniform rate.
The rate of rise shall be 0.5 or 1.0 kilovolts per second.
depending on the total test time required and the voltage-time
characteristic of the material. The rate of rise of voltage should
be specified in the material specification.
IPC-TM-650
Number
2.5.6.3
Subject
Dielectric
Breakdown Voltage and Dielectric Strength
Date
10/86
Revision
P
age2of3
电子技术应用       www.ChinaAET.com
5.4.3
Test to Breakdown, Step-by-Step Test
An
initial
voltage shall be applied equal to 50 of the breakdown voltage
in the short-time test, adjusted as shown in Table 1.
The voltage shall then be increased in equal increments as
stated in the various material specifications, the voltage being
held at each step for a definite time as stated in the specifica-
tions. The change from each step to the next higher shall be
made as rapidly as possible and the time of change included
in the succeeding test interval.
5.4.4
Test to Breakdown, Slow-Rate-of-Test
An
initial
voltage shall be applied equal to approximately 50% of the
breakdown voltage in the short time test, unless otherwise
specified. The voltage shall then be increased at a uniform
rate up to the point of breakdown. Unless otherwise specified,
the rate should be chosen to give approximately the same
voltage-time exposure of the test specimen, as provided in
the step-by-step test.
5.4.5
Determining Rate of Rise of Voltage
The
rate of
voltage rise may be calculated from measurements of time
required to raise the voltage between two prescribed values.
When motordriven regulating equipment is used, the speed-
control rheostat may be calibrated in terms of voltage rise for
any particular test transformer.
5.5
Number of Tests
Unless
otherwise specified, five tests
shall be made. If the average deviation from the mean
exceeds 10% or if any individual test deviates more than 15%
from the mean, five additional tests shall be made.
5.6
Report
The
report shall include the following data:
1. The average thickness of the sample
2. Breakdown voltage at each puncture
3. Volts per mil for each puncture
4. The average, maximum, and minimum volts per 0.0075
mm for each sample
5. The temperature of the surrounding medium should be
recorded
6. The RH% of the surrounding air
7. The conditioning treatment
8. The duration of the test
9. In the step-by-step test, the value of the initially applied
voltage and the voltage increment
10. In the slow rate of rise test, the value of the initially applied
voltage and the rate of rise of the voltage
11. The size and type of electrodes
12. The test medium (air or type of oil)
6 Notes
Due
to the high voltage used in this test method,
extreme caution should be exercised.
T
able 1 Application of Initial Voltage
Breakdown
voltage by
short-time method
Adjust 50% of breakdown
voltage to nearest
25
kilovolts or less 1.0 kilovolt (unless
otherwise specified)
Over 25 to 50 kilovolts.
inclusive
2.0 kilovolts
Over 50 to 100 kilovolts,
inclusive
5.0 kilovolts
Over 100 kilovolts 10.0 kilovolts
IPC-TM-650
Number
2.5.6.3
Subject
Dielectric
Breakdown Voltage and Dielectric Strength
Date
10/86
Revision
P
age3of3
电子技术应用       www.ChinaAET.com
1
Scope
The
dielectric withstanding voltage test (also
called high-potential, over potential, voltage breakdown, or
dielectric strength test) consists of the application of a voltage
higher than rated voltage for a specific time between mutually
isolated portions of a PCB or between isolated portions and
ground. This is used to prove that the PCB can operate safely
at its rated voltage and withstand momentary over potentials
due to switching, surges, and other similar phenomena.
Although this test is often called a voltage breakdown or
dielectric strength test, it is not intended that this test cause
insulation breakdown or that it be used for detecting corona,
rather it serves to determine whether insulating materials
and/or conductor spacings are adequate.
2
Applicable Documents
None
3
Test Specimen
The
test specimen shall be comprised of
a minimum of two conductor lines per conductive layer, suffi-
cient to allow a voltage to be applied between adjacent con-
ductor patterns both between conductive layers and on the
same conductive layer (see 6.1).
4
Apparatus or Material
4.1
A high voltage source capable of supplying the specified
voltage with a tolerance of ± 5% (see 6.2).
4.2
A
voltage measuring device with an accuracy of 5%. If
leakage current measuring capability is required, the device
shall be capable of detecting the leakage current to within 5%
of the requirement.
4.3
Soft
bristle brush
4.4 Deionized
or distilled water (2 megohm-cm minimum
resistivity recommended)
4.5
Isopropyl
alcohol
4.6
Drying
oven
5
Procedure
5.1 Specimen Preparation
(see
6.3)
5.1.1
Positive,
permanent, and noncontaminating identifica-
tion of test specimen is of paramount importance.
5.1.2 Visually
inspect the test specimens for any obvious
defects, as described in the applicable performance specifica-
tion. If there is any doubt about the overall quality of any test
specimen, the test specimen should be replaced and this
replacement noted.
5.1.3
Solder
single stranded (to simulate discrete compo-
nent axial leads) polytetrafluroethylene (PTFE) insulated wires
in each of the connection points of the test specimens. These
wires will be used to connect the test patterns of the test
specimens to the high voltage source.
5.1.4
Wet
test lead terminals with deionized or distilled
water and scrub with a soft bristle brush for a minimum of 30
seconds. During the remainder of the test specimen prepara-
tion, handle test specimens by the edges only (see 6.4).
5.1.5
Spray
rinse thoroughly with deionized or distilled
water. Hold test specimen at an approximate 30° angle and
spray from top to bottom.
5.1.6
Wet
test lead terminals with clean isopropyl alcohol
and agitate for a minimum of 30 seconds. Scrub with a soft
bristle brush to remove flux residue.
5.1.7
Rinse
cleaned area thoroughly with fresh isopropyl
alcohol.
5.1.8
Dry
test specimens in a drying oven for a minimum of
three hours at an oven temperature of between 49 °C to
60 °C (120 °F to 140 °F).
5.1.9
Allow
the test specimens to cool to room temperature.
(see 6.5)
2215
Sanders Road
Northbrook, IL 60062-6135
IPC-TM-650
TEST
METHODS MANUAL
Number
2.5.7
Subject
Dielectric
Withstanding Voltage, PCB
Date
05/04
Revision
D
Originating Task Group
Rigid Printed Board Performance Task Group
(D-33a)
Material
in this Test Methods Manual was voluntarily established by Technical Committees of IPC. This material is advisory only
and its use or adaptation is entirely voluntary. IPC disclaims all liability of any kind as to the use, application, or adaptation of this
material. Users are also wholly responsible for protecting themselves against all claims or liabilities for patent infringement.
Equipment referenced is for the convenience of the user and does not imply endorsement by IPC.
P
age1of2
ASSOCIA
TION CONNECTING
ELECTRONICS INDUSTRIES
®
电子技术应用       www.ChinaAET.com