Display: In-carrier sensor error. Used by: CP-732E, CP-742ME, CP-742E Cause: The clamper open limit and close limit sensors at the in-carrier's advance limit side are both off. Remedy: Move the clamper to either the…
------------------------------
Code: 15040215
Display: In-conveyor panel conveyance error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-conveyor's second panel arrival confirmation sensor (X0AE) failed to detect the panel
within the prescribed period of time even though the panel has passed the in-conveyor's second panel
deceleration sensor (X0AD) position.
Remedy: Check the panel conveyance condition, and verify that the in-conveyor's second panel
deceleration sensor is operating correctly.
------------------------------
Code: 15040216
Display: In-conveyor panel conveyance error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The interval between the first and second panel s is incorrect. Alternatively, the interval
confirmation sensor (X0AF) is mounted in the wrong position.
Remedy: Check the first and second panel interval setting in the production program. Adjust the
mounting position of the interval confirmation sensor (X0AF) if necessary. If this error occurs when both
the interval setting data and the sensor mounting position are correct, check to see if the interval
confirmation sensor is operating correctly. This sensor should be on when no panel is detected.
------------------------------
Code: 15040217
Display: In-lifter sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-lifter's up limit and down limit sensors are both off.
Remedy: Move the in-lifter to either the up limit or the down limit position. If this error occurs even when
the in-lifter is at the up or down limit position, adjust the sensor mounting positions. If the sensors still
fail to switch on, there may be a sensor wiring problem or a sensor failure.
------------------------------
Code: 15040218
Display: In-lifter sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-lifter's up limit and down limit sensors are both on.
Remedy: Adjust the sensor mounting positions. If the sensors still fail to switch off, there may be a
sensor wiring problem or a sensor failure.
------------------------------
Code: 15040219
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carriers advance limit and retract limit sensors are both off.
Remedy: Move the in-carrier to either the advance limit or the retract limit position. If this error still
occurs, adjust the sensor mounting positions. If the sensors still fail to switch on after adjusting their
mounting positions, there may be a sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021A
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carriers advance limit and retract limit sensors are both on.
Remedy: Adjust the sensor mounting positions. If the sensors still fail to switch off, there may be a
sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021B
第 1115 页
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The clamper open limit and close limit sensors at the in-carrier's advance limit side are both off.
Remedy: Move the clamper to either the open limit or the close limit position. If this error still occurs,
adjust the sensor mounting positions. If the sensors still fail to switch on after adjusting their mounting
positions, there may be a sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021C
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The clamper open limit and close limit sensors at the in-carrier's advance limit side are both on.
Remedy: Adjust the sensor mounting positions. If the sensors still fail to switch off, there may be a
sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021D
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The clamper open limit and close limit sensors at the in-carrier's retract limit side are both off.
Remedy: Move the clamper to either the open limit or the close limit position. If this error still occurs,
adjust the sensor mounting positions. If the sensors still fail to switch on after adjusting their mounting
positions, there may be a sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021E
Display: In-carrier sensor error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The clamper open limit and close limit sensors at the in-carrier's retract limit side are both on.
Remedy: Adjust the sensor mounting positions. If the sensors still fail to switch off, there may be a
sensor wiring problem or a sensor failure.
------------------------------
Code: 1504021F
Display: In-carrier operation disabled.
Used by: CP-732E, CP-742ME, CP-742E
Cause: In-carrier cannot be advanced, as there is a risk of interference with the panel on the in-lifter
(because it is not known if there is a panel on the in-carrier).
Remedy: Remove the panel from the in-lifter.
------------------------------
Code: 15040220
Display: In-carrier operation disabled.
Used by: CP-732E, CP-742ME, CP-742E
Cause: In-carrier cannot be retracted because there is a risk of interference between the panel on the in-
carrier and the panel on the in-lifter.
Remedy: Remove the panel from the in-lifter.
------------------------------
Code: 15040221
Display: In-carrier operation disabled.
Used by: CP-732E, CP-742ME, CP-742E
Cause: There is a risk of interference with the panel on the in-lifter when the in-carrier is retracted
because it is not known if there is a panel on the in-carrier.
Remedy: Remove the panel from the in-lifter.
------------------------------
Code: 15040222
第 1116 页
Display: In-carrier clamp error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: In-carrier close was executed but in-carrier close limit sensor failed to switch on. An in-carrier
close was executed in order to retract the in-carrier from the advance limit position, but the open
confirmation sensor at the retract side failed to switch off within the prescribed period of time. An in-
carrier close was executed in order to advance the in-carrier from the retract limit position, but the open
confirmation sensor at the advance side failed to switch off within the prescribed period of time.
Remedy: Check to see if the in-carrier close operation has occurred correctly. Also verify that the in-
carrier open limit sensor is mounted at the correct position.
------------------------------
Code: 15040223
Display: In-carrier clamp error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: An in-carrier open was executed but the in-carrier open limit sensor failed to switch on.
Remedy: Check to see if the in-carrier open operation has occurred correctly. Also verify that the in-
carrier open limit sensor is mounted at the correct position.
------------------------------
Code: 15040224
Display: In-carrier clamp error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carrier clamper's open limit (clamp limit) sensor failed to switch on.
Remedy: The clamper must be closed in order to move the XY-table to the middle loading position. Check
to see if the in-carrier clamper is closed. If closed, and if this error occurs anyway, adjust the sensor
mounting position.
------------------------------
Code: 15040225
Display: In-carrier panel conveyance error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carrier panel sensors 1 and 2 (X0B1, X0B2) failed to switch on even though 2 panel s were
loaded from the in-lifter.
Remedy: Check the panel conveyance condition. If this error occurs even though panel s are being
conveyed properly, check to see if the sensor is operating correctly.
------------------------------
Code: 15040226
Display: In-carrier panel conveyance error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carrier panel sensor 1 (X0B1) failed to switch on even though 1 panel was loaded from the
in-lifter.
Remedy: Check the panel conveyance condition. If this error occurs even though panel s are being
conveyed properly, check to see if the sensor is operating correctly.
------------------------------
Code: 15040227
Display: In-carrier panel conveyance error.
Used by: CP-732E, CP-742ME, CP-742E
Cause: The in-carrier panel sensor failed to switch on even though a panel was conveyed from the in-
lifter to the XY-table.
Remedy: Check to see if the panel was conveyed properly to the XY-table. If this error occurs even though
panel was conveyed properly, adjust the sensor mounting position.
------------------------------
Code: 15040228
Display: In-conveyor mid-stopper error.