PM?? ERROR Code:******** (QP132) Used by: QP242,QP201,QP202,QP203,QP132 Cause: Program data was transmitted to the PMC after an error was reported in response to a DWNPRG command. (value replacing "?" is module…

100%1 / 5282
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Parameter data was transmitted to the PMC without a PARSND (parameter transmission request)
command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?A1
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Parametr Trans'd w/o Req'st" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Parameter data was transmitted after an error was reported in response to a PARSND command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?A2
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"WrongDirection of ParaTrans" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Parameter data was transmitted to the PMC even though the PARSND command specified "UPLD"
as the transmission direction.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?A3
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Transd Para Larger Than Siz" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: The size of the parameter data transmitted to the PMC was larger than that specified by the
PARSND command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?A4
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Trans after ProgTransReqErr" (QP2)
第 744 页
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Program data was transmitted to the PMC after an error was reported in response to a DWNPRG
command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty production program or PMC control board may be the cause.
------------------------------
Code: 12070?A5
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Transmitted Needless Prog" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Program data was transmitted to the PMC after a "NO_NEED" message was sent in response to a
DWNPRG command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty production program or PMC control board may be the cause.
------------------------------
Code: 12070?A6
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Wrong Device Data Size" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: A DWNPRG command specified the wrong device data size.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMC. If the problem is recurring, issues such as a
faulty production program or PMC control board may be the cause.
The maximum number of sequences per production program is 5000, and the maximum number of
sequences for a PLM (PM), including mark sequences is 1000.
------------------------------
Code: 12070?A7
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Wrong Sequence Data Size" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: A DWNPRG command specified the wrong sequence data size.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMC. If the problem is recurring, issues such as a
faulty production program or PMC control board may be the cause.
The maximum number of sequences per production program is 5000, and the maximum number of
sequences for a PLM (PM), including mark sequences is 1000.
------------------------------
第 745 页
Code: 12070?A8
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Transd Prog Larger Than Siz" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: The size of the program transmitted to the PMC was larger than that specified by the DWNPRG
command.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMC. If the problem is recurring, issues such as a
faulty production program or PMC control board may be the cause.
The maximum number of sequences per production program is 5000, and the maximum number of
sequences for a PLM (PM), including mark sequences is 1000.
------------------------------
Code: 12070?AA
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Wrong Packet Number" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Incorrect packet number.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?AB
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Wrong HEXB Data" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Incorrect HEXB data.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------
Code: 12070?AC
Display: "ICM(PMC?,SCU?) Error Code:********" (QP2)
"Wrong HEXW Data" (QP2)
PM?? ERROR Code:******** (QP132)
Used by: QP242,QP201,QP202,QP203,QP132
Cause: Incorrect HEXW data.
(value replacing "?" is module number; error code appears in place of asterisks)
(value replacing "??" is module number)(QP132)
Remedy: Press the RESET button to clear the error, or restart the machine. If the problem occurs again,
use a reset-start to transmit the control software to the PMCs. If the problem is recurring, issues such as
a faulty PMC control board may be the cause.
------------------------------