SEMI E54.16-0705 © SEMI 2005 20 7.8.1.1 SNVT_xxx — The value of the sensor (associated with the object in stance) that is to be made available on the network. T he form and content of this SNVT is context-specific. 7.8.2…

100%1 / 7923
SEMI E54.16-0705 © SEMI 2005 19
7.7.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.7.2 Sensor-AI Object Configuration Parameters — The Sensor-AI object has configuration properties to control
exception reporting as shown in Table 15. These parameters are Standard Configuration Property Types (SCPTs).
Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.8 Sensor-EI Object (Sei) — The presentation of the Sensor Enumerated Input (Sensor-EI) object instance
attributes are as indicated in Table 15. The presentation of object services shall be indicated in Table 16.
Table 15 Sensor-EI Object Instance Network Variables
Sensor-EI Object (Sei)
Profile ID = 180.22, Instance ID = 01 through l
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP SeiA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO SeiA2 nvoStatus output of the Sensor-EI Object
3 Alarm Enable NVI SeiA3 nviRequest input of the Sensor-EI
Object
4 Warning Enable NVI SeiA4 nviRequest input of the Sensor-EI
Object
16 Value NVO SeiA16 Typedef (*)
#3
SNVT_xxx
#2
17 ReportInhibitTimer CP SeiA17 SCPTminSendTime
18 EnableReportRate CP SeiA18 SCPTmaxSendTime
#1
19 ReportRate CP SeiA19 SCPTmaxSendTime
64 DebounceControl CP SeiA64 SCPTdebounce
65 AlarmState CP SeiA65 Typedef BOOL SCPTalarmState (*)
#3
66 WarningState CP SeiA66 Typedef BOOL SCPTwarningState (*)
#3
#1
A SCPTmaxSendTime value of 0 is used to inhibit report rate reporting.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
Table 16 Sensor-EI Object Instance Network Services
Sensor-EI Object (Sei)
Profile ID = 180.22, Instance ID = 01 through l
Service
Request Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset SeiS1 Sensor-AI Object RQ_RESET
2 Abort SeiS2 Sensor-AI Object RQ_ABORT (*)
#1
3 Recover SeiS3 Sensor-AI Object RQ_RECOVER (*)
#1
6 Operate SeiS4 Sensor-AI Object RQ_NORMAL
4 GetAttribute SeiS5 Read NV or CP NV or CP Value
5 SetAttribute SeiS6 Sensor-AI Object RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault SeiS7 Sensor-AI Object RQ_PROPAGATE
(*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.8.1 Sensor-EI Object Network Variables A new functional profile is defined with the following mandatory
network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles for SEMI
SAN-compliant devices based on LONWORKS.
SEMI E54.16-0705 © SEMI 2005 20
7.8.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.8.2 Sensor-EI Object Configuration Parameters — The Sensor-EI object has configuration properties to control
exception reporting as shown in Table 17. These parameters are Standard Configuration Property Types (SCPTs).
Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.9 Sensor-BI Object (Sbi) — The presentation of the Sensor Binary Input (Sensor-BI) object instance attributes are
as indicated in Table 17. The presentation of Sensor-BI object services is indicated in Table 18.
Table 17 Sensor-BI Object Instance Network Variables
Sensor-BI Object (Sbi)
Profile ID = 180.18, Instance ID = 01 through m
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP SbiA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO SbiA2 nvoStatus output of the Sensor-BI
Object
3 Alarm Enable NVI SbiA3 nviRequest input of the Sensor-BI
Object
4 Warning Enable NVI SbiA4 nviRequest input of the Sensor-BI
Object
16 Value NVO SbiA16 Typedef (*)
#3
SNVT_xxx
#2
17 ReportInhibitTimer CP SbiA17 SCPTminSendTime
18 EnableReportRate CP SbiA18 SCPTmaxSendTime
#1
19 ReportRate CP SbiA19 SCPTmaxSendTime
64 DebounceControl CP SbiA64 SCPTdebounce
65 AlarmState CP SbiA65 Typedef BOOL SCPTalarmState (*)
#3
66 WarningState CP SeiA66 Typedef BOOL SCPTwarningState (*)
#3
#1
A SCPTmaxSendTime value of 0 is used to inhibit report rate reporting.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
Table 18 Sensor-BI Object Instance Network Services
Sensor-BI Object (Sbi)
Profile ID = 180.18, Instance ID = 01 through m
Service
Request Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset SbiS1 Sensor-BI Object RQ_RESET
2 Abort SbiS2 Sensor-BI Object RQ_ABORT (*)
#1
3 Recover SbiS3 Sensor-BI Object RQ_RECOVER (*)
#1
6 Operate SbiS4 Sensor-BI Object RQ_NORMAL
4 GetAttribute SbiS5 Read NV or CP NV or CP Value
5 SetAttribute SbiS6 Sensor-BI Object RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault SbiS7 Sensor-BI Object RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.9.1 Sensor-BI Object Network Variables A new functional profile is defined with the following mandatory
network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles for SEMI
SAN-compliant devices based on LONWORKS.
SEMI E54.16-0705 © SEMI 2005 21
7.9.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.9.2 Sensor-BI Object Configuration Parameters — The Sensor-BI object has configuration properties to control
exception reporting as shown in Table 19. These parameters are Standard Configuration Property Types (SCPTs).
Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.10 Sensor-BI-TH Object (Sbith) — The presentation of the Sensor Binary Input Threshold (Sensor-BI-TH) object
instance attributes are as indicated in Table 19. The presentation of Sensor-BI-TH object services is indicated in
Table 20.
Table 19 Sensor-BI-TH Object Instance Network Variables
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP SbiA1 Typedef unsigned char SCPTname
(*)
#4
2 Status NVO SbiA2 nvoStatus output of the Sensor-BI-TH
Object
3 Alarm Enable NVI SbiA3 nviRequest input of the Sensor-BI-TH
Object
4 Warning Enable NVI SbiA4 nviRequest input of the Sensor-BI-TH
Object
16 Value NVO SbiA16 Typedef (*)
#4
SNVT_xxx
#2
17 ReportInhibitTimer CP SbiA17 SCPTminSendTime
18 EnableReportRate CP SbiA18 SCPTmaxSendTime
#1
19 ReportRate CP SbiA19 SCPTmaxSendTime
64 DebounceControl CP SbiA64 Typedef unsigned char SCPTname
(*)
#4
65 AlarmState CP SbiA65 nvoStatus output of the Sensor-BI-TH
Object
66 WarningState CP SbiA66 nviRequest input of the Sensor-BI-TH
Object
67 ReadingValid NVO sbithA64 SNVT_switch
#3
68 State NVO sbithA65 nvoStatus output of the Sensor-BI-TH
Object
69 Status NVO sbithA66 nvoStatus output of the Sensor-BI-TH
Object
#1
A SCPTmaxSendTime value of 0 is used to inhibit report rate reporting.
#2
The form and content of this SNVT is context-specific.
#3
An invalid value output is used to indicate an invalid reading.
#4
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
Table 20 Sensor-BI-TH Object Instance Network Services
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset SeiS1 Sensor-BI-TH Object
RQ_RESET