semi合集-English.pdf - 第7065页
SEMI S18-1102 © SEMI 2002 3 American Conference of Go ve rnmental Industrial Hygienists.) [SEMI F6]. 5.2.8 TWA — Time Weighted Average As defined by the American Confer ence of Governmental Industrial Hygienists (ACGIH…

SEMI S18-1102 © SEMI 2002
2
SEMI S2 — Environmental, Health, and Safety
Guideline for Semiconductor Manufacturing Equipment
SEMI S4 — Safety Guideline for the
Segregation/Separation of Gas Cylinders Contained in
Cabinets
SEMI S5 — Safety Guideline for Flow Limiting
Devices
SEMI S6 — Safety Guideline for Ventilation
SEMI S10 Safety Guideline for Risk Assessment
SEMI S13 Safety Guideline for Operation and
Maintenance Manuals Used with Semiconductor
Manufacturing Equipment
SEMI S14 Safety Guidelines for Fire Risk
Assessment and Mitigation for Semiconductor
Manufacturing Equipment
4.2 NFPA
1
Standards
NFPA 13 Installation of Sprinkler Systems
NFPA 70 National Electrical Code
NFPA 318 Standard for the Protection of
Cleanrooms
4.3 Compressed Gas Association
2
CGA P-20 Standard for the Classification of Toxic
Gas Mixtures
CGA P-23 Standard for Categorizing Gas Mixtures
Containing Flammable and Nonflammable Components
4.4 Other Documents
High Pressure Gas Safety Law
3
The High Pressure Gas Safety Institute of Japan
(KHK), Application Guide for the High Pressure Gas
Safety Law
4
Santa Clara County Toxic Gas Ordinance No. NS-
517.44
5
SSA Journal
6
, Volume 11 No. 4, Winter 1997
1 National Fire Protection Association, 1 Batterymarch Park, PO Box
9101, Quincy, MA 02269-9101
2 Compressed Gas Association, 1725 Jefferson Davis Highway, Suite
1004, Arlington, Virginia 22202-4102
3 KHK, Sumitomo-Tranomon Bldg., 4-3-9 Toranomon, Minatoku,
Tokyo 105-8447
4 KHK, Sumitomo-Tranomon Bldg., 4-3-9 Toranomon, Minatoku,
Tokyo 105-8447
5 Santa Clara County TGO
6 SSA Journal, SSA Journal Headquarters 1313 Dolly Madison Blvd.
Suite402, McLean, VA22101
4.5 US Code of Federal Regulations
Uniform Fire Code (UFC)
7
Sections 51, 79 and 80
Semiconductor Facility-Specific Sections
29CFR 1910.1200
8
, “Hazard Communication”
(OSHA)
NIOSH Pocket Guide available online at
http://www.cdc.gov/niosh/topreq.html
4.6 EU Directive
The Safety Sheets Directive 93/112 EEC
5 Terminology
5.1 Terminology defined in SEMI S2 should be
referred to except if otherwise specified below.
5.2 Abbreviations and Acronyms
5.2.1 ACGIH
®
— American Conference of
Governmental Industrial Hygienists. (ACGIH is a
registered trademark of the American Conference of
Governmental Industrial Hygienists.)
5.2.2 ESOV Emergency Shut Off Valve.
5.2.3 IDLH Immediately Dangerous to Life and
Health, concentration of airborne contaminants,
normally expressed in parts per million or milligrams
per cubic meter, which represents the maximum level
from which one could escape within thirty minutes
without any escape-impairing symptoms or irreversible
health effects. This level is established by the National
Institute of Occupational Safety and Health (NIOSH).
[SEMI F6]
5.2.4 MSDS Material Safety Data Sheet, a
document that provides information on the properties of
a chemical material in a format specified by a
regulation such as OSHA 29 CFR 1910.1200, “Hazard
Communication”.
5.2.5 PTFE Poly Tetra Fluoro Ethylene.
5.2.6 SSCS silane safety control system. SSCSs are
integrated systems of detection devices that, when
monitored as a group, provide for an overall status of
the safety of the hazardous gas handling system (e.g.,
pressure transducers linked to valve status monitors and
valve cycle counting programs or excess-flow
monitoring interlocked to shutdown the source).
5.2.7 TLVs
®
Threshold Limit Values for chemical
substances in the work environment adopted by
ACGIH
®
(TLV
®
is a registered trademark of the
7 Uniform Fire Code, 5360 South Workman Mill Road, Whitter, CA
90601
8 Occupational Safety and Health Administration U.S. Department
of Labor, http://www.osha.gov

SEMI S18-1102 © SEMI 2002
3
American Conference of Governmental Industrial
Hygienists.) [SEMI F6].
5.2.8 TWA — Time Weighted Average As defined
by the American Conference of Governmental
Industrial Hygienists (ACGIH
®
) [SEMI F6].
5.2.9 VMB — Valve Manifold Box.
5.3 Definitions
5.3.1 abatement system — a system used to modify the
effluent from a process in order to make it safe to emit
from the facility or to reduce emissions of hazardous
materials to safe levels.
5.3.2 authorized personnel those persons trained
and capable of performing activities involving the risks
associated with the defined tasks.
5.3.3 carriage a hand cart for carrying one or two
gas cylinders.
5.3.4 chlorosilane dichlorosilane or trichlorosilane.
5.3.5 controlled condition when related to silane
family gases, a condition in which the gas is controlled
within the confines of an approved piping system with
controls that can determine if the safe parameters of the
piping system have failed.
5.3.6 exhaust treatment system a system similar to
an abatement system, except it handles only the
airborne emissions from a process in order to make
them safe to emit or to reduce the levels of hazardous
materials to safe emission levels.
5.3.7 fail-safe designed so that a failure does not
result in an increased risk [SEMI S2].
5.3.8 flammable gas any gas that forms an ignitable
mixture in air at 20 degrees C (68°F) and 101.3 kPa
(14.7 psia) [SEMI S2].
5.3.9 Flow Limiting Device a device installed in a
valve that is designed to reduce the maximum flow
from the valve under full flow conditions [SEMI F5]
[One such device is a Restricted Flow Orifice (RFO)].
5.3.10 foolproof designed so that any single human
error or misuse does not result in unacceptable risk.
5.3.11 occupational exposure limits (OELs) Various
terms are used to refer to OELs, such as permissible
exposure levels, Threshold Limit Values
®
, maximum
acceptable concentrations, maximum exposure limits,
and occupational exposure standards. When OELs are
used to specify work-area criteria in this document ,
OELs are generally established on the basis of an eight
hour workday. When OELs are used to specify criteria
in this document for alarm or warning in non-
occupational area, OELs established on shorter
exposure basis may be used. However, the criteria
used in determining OELs can differ among the various
countries that have established values. Refer to the
national bodies responsible for the establishment of
OELs. (Threshold Limit Value is a registered trademark
of the American Conference of Governmental Industrial
Hygienists.)
5.3.12 oxidizer gas a gas which will support
combustion or increase the burning rate of a
combustible material with which it may come in contact
[SEMI S4].
5.3.13 pyrophoric gas “a gas which upon contact
with air will ignite spontaneously at or below a
temperature of 54°C (130°F) [SEMI S4]” at a pressure
of 101.3kPa (14.7psia).
5.3.14 safe shutdown condition a condition in which
all hazardous energy sources are removed or suitably
contained and hazardous production materials are
removed or contained, unless this results in additional
hazardous conditions.
5.3.15 safe state a condition in which the equipment
does not present any uncontrolled hazards to itself or to
personnel. It does not allow hazardous production
chemicals to flow.
An acceptable safe state is
determined by the designer of the equipment and is
based on the hazards in the design.
5.3.16 silane any of monosilane, disilane, or
trisilane.
5.3.17 unacceptable risks — risks of a degree or type
which are not acceptable to the person who approves a
design or procedure.
5.3.18 unsafe gas condition a condition in which the
gas is not safely contained within the designed
parameters of the equipment process, or which could
lead to a gas emission or gas hazard.
6 General Principles
6.1 Since silane family gases have several hazardous
properties, personnel should wear appropriate
protective equipment when working with silane family
gas sources.
6.1.1 Monosilane (SiH
4
), disilane (Si
2
H
6
) and trisilane
(Si
3
H
8
) are pyrophoric. If these gases are mixed with
stronger oxidizing gases than air, combustion and
explosion energies can radically increase.
6.1.2 Dichlorosilane (SiH
2
Cl
2
) is pyrophoric and
trichlorosilane (SiHCl
3
) is flammable. Dichlorosilane
(SiH
2
Cl
2
) and trichlorosilane (SiHCl
3
) are also
corrosive gases. If these gases are mixed with

SEMI S18-1102 © SEMI 2002
4
moisture, corrosivity can radically increase and
pyrophoric byproduct gases might also be produced.
NOTE 2: The most recent and best research on DCS puts the
AIT (Auto Ignition Temperature) at 44 degrees C plus/minus
3 degrees C, or about 111 degrees F. It should be noted
however, that unlike silane, DCS is not expected to autoignite
in almost all ambient conditions where we would find it in
use. For fire protection purposes it can be treated as a highly
flammable gas.
6.2 Risk Management Strategies Fundamental
concepts of safety and accident prevention are:
6.2.1 An understanding of facilities, piping and
equipment, from storage to gas abatement, is essential
for safe handling of silane family gases in
semiconductor or FPD manufacturing facilities.
6.2.2 The safety of facilities can be enhanced by
implementation of designs for sources, piping and
equipment that use devices with fail-safe, foolproof,
self-diagnostic and predictive functions.
6.2.3 Safety systems should detect current safety status
and generate notices that indicate conditions of elevated
risk, through computer self-diagnosis and dedicated
SSCS devices. If the SSCSs cannot confirm normal
operation of assigned silane family gas handling system
or unit, the silane family gas supply should
automatically be shut off.
6.2.3.1 SSCSs can determine if a safe status has been
achieved before proceeding to the next step in a silane
family gas handling process.
6.2.3.2 SSCSs should be provided in distribution
facilities, cylinder cabinets, process equipment, gas
treatment systems, and the like.
6.2.4 Safe design depends on equipment designers’ and
facilities designers’ understanding of silane family gas
properties and hazards. Design methods for controlling
these hazards require full integration of measures from
all portions of the delivery and use systems.
NOTE 3: Information on silane family gases’ hazards is
available from various sources, including: regulations,
MSDSs, Factory Mutual Loss Prevention Data Sheets, NFPA
Standards, consensus Building Codes, and various research
papers.
6.2.4.1 The supplier should complete, prior to use, a
hazard identification and risk assessment [such as
Process Hazard Analysis (PHA), Hazard and
Operability Analysis (Haz-Op), Failure Mode Effects
Analysis (FMEA)], for all silane family gas systems.
6.2.4.2 The results of the analysis should be reported
using the SEMI S10 risk matrix.
6.2.5 Minimization of Quantity The quantity of any
silane family gas online and in use should be limited to
the smallest amount necessary for effective production.
NOTE 4: Separation and setback considerations for silane
family gas storage and dispensing areas must be in
accordance with jurisdictional requirements.
6.2.6 Periodic accident prevention assessments should
be performed to assist in minimizing incident
frequency.
6.3 Isolation (Lockout/Tagout) Isolation (“lock
out/tag out”) capability should be provided for all silane
sources at all levels necessary to perform service or
maintenance safely on silane family gas systems.
6.3.1 Energy isolation of all other energy sources (e.g.,
electrical, mechanical) should be performed, as
appropriate, to provide safety for personnel working on
energy systems associated with silane family gases.
NOTE 5: Maintenance on energized non-hazardous electrical
systems may not be safe when a silane family gas is present in
the system.
6.4 Access Control
6.4.1 Multiple level access control, to each point where
any hazard may exist in a normal or failure state, should
be provided for all silane family gas systems.
6.5 All personnel concerned in silane family gas
handling should be trained for the jobs they are to
perform and hazards to which they will be exposed. All
such training should be formally documented and if
regulations apply then the documentation should be in
accordance with the regulations.
6.5.1 Audits of system status and equipment condition
should be performed and documented on a periodic
basis.
6.5.2 The operator or technician should be capable of
checking the current status and any abnormal condition
before beginning work on any system or sub-system.
6.5.3 Evacuation and Purging
6.5.3.1 When connecting silane family gas piping to
equipment, the air in the piping should be purged out
with inert gas such as nitrogen into a safe location to
prevent reaction with silane family gases.
6.5.3.2 To enable purging without venting into unsafe
locations, a purge port should be installed at locations
where sealed systems require purging. Purge ports
should have a stop valve and, if not connected to the
purge gas, should be sealed with a cap or plug.