semi合集-English.pdf - 第7113页

SEMI S21-1103 © SEMI 2003 13 APPENDIX 1 CHEMICAL CATEGORIES AND ANTICIPATED HAZARDS BY CATEGORY NOTICE : The material in this appendix is an official part of SEMI S21. Table A1-1 Chemic al Category and Ha zards Descripti…

100%1 / 7923
SEMI S21-1103 © SEMI 2003 12
13.4 Members of any on-site responding organization
(such as emergency response teams (ERTs)) should be
trained on the use of the emergency response plan, and
all other procedures for which they are designated
responders.
13.4.1 Responders should not perform actions for
which they have not been trained.
13.4.2 If on-site responders are not provided, facility
operators should make provisions according to the
regulations for the location and should notify all
supplier employers about the extents and limits of such
response provisions.
NOTE 40: Some jurisdictions require trained on-site
responders at each facility. Other jurisdictions specify that
only local authorities (e.g., fire departments, hazardous
materials units, police) can respond to emergency situations.
Certain jurisdictions allow employers to choose whether they
train their employees to respond to emergencies or if they will
depend upon local authorities for emergency response. Each
employer should understand the requirements of each specific
jurisdiction in which they will perform work.
13.4.2.1 An example of an organization that offers
emergency medical training and certification is the Red
Cross.
SEMI S21-1103 © SEMI 2003 13
APPENDIX 1
CHEMICAL CATEGORIES AND ANTICIPATED HAZARDS BY
CATEGORY
NOTICE: The material in this appendix is an official part of SEMI S21.
Table A1-1 Chemical Category and Hazards
Description Hazard Examples
Compressed Gas High pressure cylinder gas
Potential for rapid, dangerous
release of contents
Argon, hydrogen, chlorine
Cryogen
Liquefied gas stored around –
200° C
Frostbite/freezing tissue Liquid oxygen, liquid nitrogen
Corrosives
Acids, bases, and some
oxidizers
Burns, irritation, visible
destruction or change to living
tissue
Hydrochloric acid, hydrogen
bromide, ammonium hydroxide
Solvents
A liquid used to dissolve or
clean other materials that can
produce flammable vapors
Fire, explosion Isopropyl alcohol, acetone
Flammable gases Can burn easily if ignited Fire, explosion Arsine, hydrogen
Pyrophoric gases
Gases which may ignite
spontaneously upon contact
with air
Fire, explosion Silane, phosphine
Poisons
Any substance that produces a
harmful effect when
introduced to the body
Serious illness or death Phosphine, diborane, arsine
Inert Gas
Non-corrosive, non-toxic and
non-flammable
Simple asphyxiant Nitrogen, argon
Oxidizers
React energetically with
reducing agents
Violent reactions when mixed
with other chemicals; can
enhance fire
Nitric acid, hydrogen peroxide,
nitrous oxide
Irritants
Corrosives, solvents, oxidizers
(effects depend on
concentration)
Local inflammatory response to
skin, eyes or respiratory tract
Hydrochloric acid, sodium hydroxide,
hydrogen peroxide, acetone
Sensitizers
Any substance that can illicit
an allergic reaction
Effects range from mild skin or
respiratory reactions to
anaphylactic shock and death
Uncured epoxies, ethylenediamine,
isocyanates
SEMI S21-1103 © SEMI 2003 14
APPENDIX 2
SELECTION OF PERSONAL PROTECTIVE EQUIPMENT
NOTICE: The material in this appendix is an official part of SEMI S21.
A2-1 Introduction
A2-1.1 This appendix provides specific technical information relating to Section 12. In general, it provides Personal
Protective Equipment (PPE) recommendations for specific hazards.
A2-1.2 This appendix is intended to be used as a guide to select PPE along with Section 12.
Table A2-1 PPE Selection Matrix
Personal Protective Equipment (PPE)
Potential
Hazard
Safety
Glasses,
Goggles
Face
Shield
Aprons,
Sleeves, or
Full Body
Suits
Gloves Skin
Protection
Safety
Shoes
Respirator Hardhat Hearing
Protection
(earplugs
or muffs)
Chemical R R
(if splash
hazard)
R
(if splash
hazard)
R R
(based on
hazard
assess-
ment)
Energized
Electrical
R R
(When
proper for
the
available
fault
current)
R
(When
proper for
the
available
fault
current)
R
(for high
voltage –
proper for
the
voltage)
R
(Insulation
-rated
proper for
the
voltage)
Ionizing
Radiation
R
*1
R
*2
R
*1
UV R
*4
R
*5
Visible R
*4
IR R
*3, 4
R
*5
Non-ionizing
Radiation
RF
Noise R
(at levels
>80 dBA)
Extreme
Temperatures
R R
Falling
Objects,
Bumping
Hazards
R R R
Mechanical R R R
Manual
Handling
R R
Oxygen
Deficiency
R
“R” indicates “Recommended”.
Note 1: Goggles and respirator should be worn if the sources are not isolated or exhausted, and are of a nature that they could enter the eye or be
inhaled.
Note 2: Gloves should be used if radioactive sources that are not sealed are being handled.
Note 3: Protective filters should be considered for long-term viewing (> 10 seconds). Where visible light doesn’t elicit the aversion response.