semi合集-English.pdf - 第6806页
SEMI S2-0703a E © SEMI 1991, 2004 35 Hood Type Recommended Test Methods Typical Design and Test Exhaust Parameters (See NOTE 1.) References Parts-Cleaning Hoods Primary: face velocit y , vapor visualization Supplemental:…

SEMI S2-0703a
E
© SEMI 1991, 2004 34
APPENDIX 2
DESIGN PRINCIPLES AND TEST METHODS FOR EVALUATING
EQUIPMENT EXHAUST VENTILATION — Design and Test Method
Supplement Intended for Internal and Third Party Evaluation Use
NOTICE: The material in this appendix is an official part of SEMI S2 and was approved by full letter ballot
procedures on December 15, 1999 by the North American Regional Standards Committee.
A2-1 Introduction
A2-1.1 This appendix provides specific technical
information relating to Section 22. In general, it
provides guidelines for:
ventilation design for semiconductor manufac-
turing equipment, and
test validation criteria.
A2-1.2 This appendix is intended to be used as a
starting point for reference during equipment design.
A2-1.3 This appendix is not intended to limit hazard or
test evaluation methods or control strategies (e.g.
design principles) employed by manufacturers or users.
Many different methods may be employed if they
provide a sufficient level of protection.
A2-1.4 This appendix is not intended to provide
exhaustive methods for determining final ventilation
specifications. Other methods may be used where they
provide at least equivalent sensitivity and accuracy.
A2-1.5 The exhaust velocities, volume flow rates and
pressures listed are derived from a mixture of
successful empirical testing and regulatory
requirements.
A2-1.6 Test validation criteria are generally referenced
from the applicable internationally recognized standard.
It is the user’s responsibility to ensure that the most
current revision of the standard is used.
Table A2-1 Ventilation
Hood Type Recommended Test Methods Typical Design and Test Exhaust
Parameters (See NOTE 1.)
References
Wet Station Primary: vapor visualization, air
sampling
Supplemental: Capture velocity, slot
velocity, tracer gas, air sampling
0.28–0.50 m/s (55–100 fpm) capture
velocity for non-heated
0.36–0.76 m/s (70–150 fpm) capture
velocity for heated
110–125% of the laminar flow
volume flow rate across the top of
the deck
ACGIH Industrial
Ventilation Manual
SEMI F15
Gas Cylinder
Cabinets
Primary: face velocity, tracer gas
Supplemental: vapor visualization
1.0–1.3 m/s (200–250 fpm) face
velocity
ACGIH Industrial
Ventilation Manual
SEMI F15
Equipment Gas
Panel Enclosure
Primary: tracer gas, static pressure
Supplemental: vapor visualization
4–5 air changes per minute
–1.3 to –2.5 mm (–0.05 to –0.1 in.)
H
2
O static pressure
ACGIH Industrial
Ventilation Manual
SEMI F15
Diffusion
Furnace
Scavenger
Primary: face velocity, vapor
visualization
Supplemental: tracer gas, air sampling
0.50–0.76 m/s (100–150) fpm face
velocity
NOTE: Do not use hot wire
anemometer.
ACGIH Industrial
Ventilation Manual
SEMI F15
Chemical
Dispensing
Cabinets
Primary: static pressure
Supplemental: vapor visualization, air
sampling where safe, tracer gas where
emission rates can be accurately
calculated
–1.3 to –2.5 mm (–0.05 to –0.1 in.)
H
2
O static pressure
2–3 air changes per minute
ACGIH Industrial
Ventilation Manual
SEMI F15

SEMI S2-0703a
E
© SEMI 1991, 2004 35
Hood Type Recommended Test Methods Typical Design and Test Exhaust
Parameters (See NOTE 1.)
References
Parts-Cleaning
Hoods
Primary: face velocity, vapor
visualization
Supplemental: tracer gas, air sampling
0.40–0.64 m/s (80–125 fpm) face
velocity
ASHRAE Standard 110
SEMI F15
ACGIH Industrial
Ventilation Manual
Pump and
Equipment
Exhaust Lines
Primary: static pressure
Supplemental: tracer gas
–6 to –25 mm (–0.25 to –1.0 in.)
H
2
O static pressure
125% maximum volume flow rate
from pump
ACGIH Industrial
Ventilation Manual
SEMI F15
Glove Boxes Primary: static pressure, tracer gas
Supplemental: vapor visualization, air
monitoring
No consensus for a reference at the
time of publication of this guideline.
ACGIH Industrial
Ventilation Manual
SEMI F15
Drying/ Bake/
Test Chamber
Ovens
Primary: static pressure, tracer gas
Supplemental: vapor visualization, air
monitoring
–1.3 to –2.5 mm (–0.05 to –0.1 in.)
H
2
O static pressure
SEMI F15
ACGIH Industrial
Ventilation Manual
Spin-Coater
(cup only)
Primary: vapor visualization,
velometry
Supplemental: air sampling
(see SEMI S2 Sections 23.5.1–3) ACGIH Industrial
Ventilation Manual
Supplemental
Exhaust
Primary: capture velocity, vapor
visualization, air sampling
0.50–0.76 m/s (100–150 fpm)
capture velocity
ACGIH Industrial
Ventilation Manual
NOTE 1: All measurements should be within ± 20% of average for face velocity, ± 10% of average along the length of each slot for slot velocity,
and ± 10% of average between slots for slot velocity.
A2-2 Exhaust Optimization
A2-2.1 Exhaust optimization is the use of good
ventilation design to create efficient equipment exhaust.
The design and measurement methods discussed below
confirm that equipment exhaust is acting as the
manufacturer intended. This information is not meant to
prohibit alternate methods of achieving or verifying
good ventilation design. References for ventilation
design are included at the end of this Appendix.
A2-2.2 Design Recommendations
A2-2.2.1 Equipment exhaust design can attempt to
reduce inefficient static pressure losses caused by:
friction losses from materials; openings, and duct
geometries (elbows, duct expansions or contractions);
turbulent air flow; fans; internal fittings such as blast
gates and dampers; directional changes in airflow.
A2-2.2.2 Other good design principles can include
minimizing distance between the source and hood, and
reducing enclosure volumes.
A2-2.2.3 For non-chemical issues such as heat from
electrical equipment, heat recapture rather than exhaust
may be appropriate.
A2-2.2.4 The possible impact of highly directional
laminar airflow found in most fabs should be
considered when designing equipment exhaust.
A2-2.3 Recommended Equipment Controls — The
location of internal blast gates or dampers inside
equipment, and their appropriate settings, should be
clearly identified. The number of equipment dampers
and blast gates should be minimized. Gates/dampers
should be lockable or otherwise securable. Static
pressure or flow sensors installed on equipment by the
manufacturer should have sufficient sensitivity and
accuracy to measure exhaust flowrate fluctuations that
place the equipment out of prescribed ranges.
A2-2.4 Recommended Measurement/Validation
Method — Measurements should be made to identify
optimal exhaust levels and confirm that safety and
process requirements are being addressed. The
manufacturer should be able to identify any critical
equipment locations for chemical capture, and quantify
appropriate exhaust values. Multiple validation/
measurement methods may be needed.
A2-2.4.1 Measurements should be done after
equipment components are assembled.
A2-2.4.2 Computer modeling can be done to predict
exhaust flow and hazardous material transport in
equipment by solving fluid mechanics conservation of
energy and mass equations. Modeling can be used in
the equipment design stage or to improve existing
equipment. Computer models should be verified
experimentally, using one or more of the methods
discussed below.
A2-2.4.3 Tracer gas testing provides a method to test
the integrity of hoods by simulating gas emission and
measuring the effectiveness of controls. Testing until

SEMI S2-0703a
E
© SEMI 1991, 2004 36
there is a failure, and then slightly increasing the flow
rate until the test is successful, can be used to help
minimize air flow specifications.
A2-2.4.4 Chemical air or wipe monitoring can be used
to confirm that chemical transport is not occurring into
unintended areas of the equipment.
A2-2.4.5 Velocity profiling will confirm expected
airflows, the direction of flow, and the effect of
distance.
A2-2.4.6 Vapor visualization will confirm expected
airflows, the direction of flow, and the effect of
distance. Vapor visualization is the observation of
aerosols (e.g., aerosols generated by using water, liquid
nitrogen, or dry ice) so that exhaust flow patterns can
be observed. Smoke tubes or aerosols may also be used,
however they can produce contamination.
A2-3 Chemical Laboratory Fume Hoods, Parts
Cleaning Hoods
Lab fume hoods and part cleaning hoods are designed
to control emission by enclosing a process on five sides
and containing the emission within the hood.
A2-3.1 Design Recommendations
A2-3.1.1 Fully enclosed on five sides, open on one side
for employee access and process/parts placement and
removals.
A2-3.1.2 Front (employee access side) should be
provided with sliding door and/or sash.
A2-3.1.3 Minimize size of the hood based on process
size.
A2-3.1.4 Minimize front opening size based on size of
process and employee access needs.
A2-3.1.5 Ensure hood construction materials are
compatible with chemicals used.
A2-3.2 Control Specifications — Face velocity is the
specification generally used with hoods open on only
one side.
A2-3.2.1 Generally acceptable laboratory fume hood
face velocities range from 0.40 to 0.60 m/s (80–120
fpm) with no single measurement 20 % of average.
0.64 to 0.76 m/s (125–150 fpm) is recommended for
hoods in which carcinogens or reproductive toxicants
may be used.
A2-3.2.2 Velocities as low as 0.30 to 0.40 m/s (60–80
fpm) can be effective but require no cross drafts or
competing air movement in the work area.
A2-3.2.3 An average face velocity of 0.50 m/s (100
fpm) is generally found to be acceptable in most
applications.
A2-3.2.4 Face velocities of 0.64 to 0.76 m/s (125 to
150 fpm) may be required when a lab hood is installed
in an area with laminar air flow.
A2-3.2.5 Face velocity above 0.76 m/s (150 fpm)
should be avoided to prevent eddying caused by a lower
pressure area in front of an employee standing at the
hood.
A2-3.3 Recommended Measurement/Validation
Method
A2-3.3.1 The preferred method is measurement of
average face velocity and hood static pressure.
Measurements are taken with a velometer or
anemometer. Multiple measurements are taken in a
grid, at least 10 to 40 per square meter (1–4 per square
foot) of open area, in the plane opening of the hood.
This allows representative, evenly spaced
measurements to be taken (see also open-surface tanks).
A2-3.3.2 Additional confirmation by visualization
check of containment using smoke or vapor testing.
A2-3.3.3 ASHRAE Method 110, or equivalent (use
appropriate sections), for tracer gas testing of lab hoods
may be used as a supplemental verification provided
that an accurate emission rate can be defined.
(ASHRAE 110 lists 3 tests: “as manufactured,” “as
used,” and “as installed.” The “as manufactured” test is
the test that is used most frequently.)
A2-4 Wet Stations
Wet stations are slotted hoods designed to capture
laminar air flow while also capturing wet process
emissions from the work area. Wet stations can be open
on the front, top and both sides (it is usually preferable
to enclose as much as possible).
A2-4.1
Design Recommendations
A2-4.1.1 Slots should be provided uniformly along the
length of the hood for even distribution of airflow.
A2-4.1.2 Additional lip exhaust slots should be
provided around tanks or sinks to control emissions.
A2-4.1.3 The plenum behind the slots should be sized
to ensure even distribution of static pressure. These
slots should be designed to ensure adequate airflow is
provided by the side slots, and to minimize turbulence
that could reduce exhaust performance.
A2-4.1.4 Velocity along length of slot should not vary
by more than 10% of the average slot velocity.
A2-4.1.5 Additional use of end or side panels/baffles
can reduce negative impact of side drafts.