semi合集-English.pdf - 第860页
SEMI E115-0302 E © SEMI 2002 6 10.2 Report the m atching network load impedance an d e fficiency as a function of tu ning element positions . The data shall be presented in both graphical and tabular form s. 11 Related D…

SEMI E115-0302
E
© SEMI 2002 5
impedance to vary. An example of a load simulator
would be a matching network used in reverse, where
the output of the DUT would attach to the output of
another matching network.
9.4.2 Calibrate the Network Analyzer at the desired
operating frequency (e.g., 13.56 MHz). The Network
Analyzer shall be calibrated for measuring the
reflection coefficient at test Port 1 and for measuring
the transmission coefficient at test Port 2 (see Figure 1)
using the calibration kit provided with the Network
Analyzer. This measurement requires measuring the
S11 and S21 S-parameters and requires a full 2-port
calibration. The calibration shall be performed at fixed
frequency (continuous-wave operation) using the
lowest bandwidth possible (typically 10 Hz). The
calibration for each port shall include the additional test
cables and any additional adapters.
9.4.3 After calibration of the Network Analyzer, the
test cable connected to Port 1 of the Network Analyzer
shall be connected to the input of the matching network
to be tested (DUT). The Load Simulator shall be
connected to the output of the DUT. The cable
connected to Port 2 of the Network Analyzer shall be
connected to the output of the Load Simulator.
9.4.4 The tuning elements shall be moved to their
minimum positions (or the positions that can match to
lowest tuning point of the Load Simulator(s)) before the
measurement is initiated. The variable elements in the
Load Simulator shall be adjusted until the input
impedance of the matching network is matched (i.e.,
input impedance = 50 ohms). After all connections are
visually inspected for proper contact and the Network
Analyzer has stabilized, the value of the input
impedance and the magnitude of the transmission
coefficient (S21) shall be recorded. In addition, the
positions of the tuning elements of the DUT and the
Load Simulator shall be recorded.
9.4.5 The load impedance of the DUT corresponds to
the input impedance of the Load Simulator. At this
point in the process, the Load Simulator can be
disconnected and its input impedance can be measured.
Alternatively, the input impedance can be measured
later by moving the Load Simulator tuning element
values to the positions recorded in Section 9.4.4.
9.4.6 The efficiency of the Test Setup, which includes
the DUT and the Load Simulator, is determined from
the transmission coefficient. Typically, the
transmission coefficient is expressed in terms of dB
(decibels). The conversion between dB and percentage
is expressed as:
Efficiency(%) = 100 × 10
(loss in dB
/
10)
For example, if the transmission coefficient is measured
to be –3 dB, then the power transfer efficiency would
be 50.1%. In other words, 49.9% of the power is lost in
the Test Setup.
9.4.7 The efficiency of the DUT is determined by
dividing the efficiency of the Test Setup by the
efficiency of the Load Simulator. For example, if the
efficiency of the Test Setup is 70% and the efficiency
of the Load Simulator is 90%, then the efficiency of the
DUT is 77.8% (0.7/0.9). The efficiency of the Load
Simulator is typically determined separately (see
Related Information Section at the end of this Test
Method).
9.4.8 For the next measurement, one tuning element
(element 1) shall remain fixed, and the other tuning
element (element 2) shall be increased by an increment
equal to no more than 10% of the full scale range of the
tuning element position. For example, if the range of
the tuning element is 10 volts, then the tuning element
shall be moved in increments of no greater than 1 volt.
A smaller increment shall be used for the case where
the incremental change in tuning element position
results in an incremental impedance change of more
than 20% of the total impedance variation measured by
the full-scale variation of the tuning element. For
example, if the real part of the load impedance varies
15 ohms over the 10 volt variation of the tuning
element, then a smaller tuning element increment shall
be used if the real load impedance varies by more than
3 ohms between increments (0.2 × 15 = 0.3). After the
tuning elements have been moved to their new values,
the previous measurement steps shall be repeated.
9.4.9 After the tuning element (element 2) has been
varied over its entire range, the other tuning element
(element 1) shall be increased by an increment equal to
no more than 10% of its full-scale range. Tuning
element 2 shall be moved back to its minimum position
and the above steps shall be repeated until the entire
tuning range of the matching network is measured.
9.4.10 The data shall be recorded and then presented in
both graphical and tabular forms. An example of a
typical impedance range graph is shown in Figure 3 for
the real load impedance and in Figure 4 for the reactive
load impedance. An example of a typical efficiency
plot is shown in Figure 5. An example of data
presented in tabular form is shown in Table 1.
10 Reporting Test Results
10.1 Report the type of Network Analyzer and the
details of the Network Analyzer parameters used for the
tests, including the bandwidth, the number of data
points, and the test frequency. Also report which Test
Method was used.

SEMI E115-0302
E
© SEMI 2002 6
10.2 Report the matching network load impedance and efficiency as a function of tuning element positions. The
data shall be presented in both graphical and tabular forms.
11 Related Documents
11.1 IEEE Standards
1
IEEE-STD-572 — IEEE Standard for Qualification of Class 1E Connection Assemblies for Nuclear Power
Generating Stations
11.2 Military Standards
2
MIL-PRF-31031A — General Specification for Connectors, Electrical, Plugs and Receptacles, Coaxial, Radio
Frequency, High Reliability, for Flexible and Semirigid Cables.
MIL-STD-348 — General Specification for Radio Frequency Connector Interfaces.
MIL-STD-220B — Test Method Standard: Method of Insertion Loss Measurement.
RF out R
AB
Port 2Port 1
Port 1
RLOSS
LC2
C1
Input Connection
Output Connection
Matching Network
Port 2
Perform Calibrations
at End of Additional
Test Cables
Network
Analyzer
NOTE 1: Both the Port 1 and Port 2 outputs need to be used for the measurement. Additional test cables are needed for the
transmission calibration between the two ports. The output connection of the matching network to be tested (DUT) attaches to
Port 1 and the input connection of the matching network attaches to Port 2 of the Network Analyzer.
Figure 1
Schematic of the Test Method 1 Network Analyzer Test Setup for the Load Impedance and Efficiency
Measurement for “L” Type Matching Networks

SEMI E115-0302
E
© SEMI 2002 7
RF out R
AB
Port 2Port 1
Port 1
Port 2
Perform Calibrations
at End of Additional
Test Cables
RLOSS
LC2
C1
Load Simulator
Input Connection
Output Connection
Matching Network
Network
Analyzer
NOTE 1: Both the Port 1 and Port 2 outputs need to be used for the measurement and additional test cables are needed for the
transmission calibration between the two ports. The input connection of the matching network to be tested (DUT) attaches to
Port 1, the output connection of the matching network attaches to the input of the Load Simulator, and the output of the Load
Simulator attaches to Port 2 of the Network Analyzer.
Figure 2
Schematic of the Test Method 2 Network Analyzer Test Setup for the Load Impedance and Efficiency
Measurement