semi合集-English.pdf - 第489页
SEMI E69-0298 © SEMI 1998, 2003 10 NOTICE: SEMI makes no warranties or representations as to the suitability o f the standards set forth herein for any particular application. The determination of the suitability of the …

SEMI E69-0298 © SEMI 1998, 2003 9
13.3 Repeat Sections 13.2.1–13.2.6, for a total of three
times, until at least six sets of data have been collected
at each setpoint (with the exception of 100%).
13.4 Repeat Sections 13.1.1–13.3 weekly for a period
of at least 12 weeks. During the idle time, the MFC
should be continuously powered, with any exceptions
so noted. Gas flow is not required during the idle time,
but any gas flow shall be recorded. Finally, record all
details about the conditions of the MFC during the idle
time.
14 Data Analysis
14.1 Calculations
14.1.1 Determine the precision at a setpoint by
calculating the standard deviation of all the measured
values (both upscale and downscale) for that setpoint.
Perform this calculation at each setpoint:
P=
(V
i
−
A
a
)
2
∑
()
j
∑
n
j
P = Precision
V
i
=
The i
th
reading at a setpoint for a given cycle
A
a
=
Average measured value
n
j
=
N
umber of readings at a setpoint for a given cycle
14.1.2 Determine the short-term reproducibilty at a
setpoint by dividing the precision of the setpoint by the
average setpoint. This is expressed as a percentage of
setpoint. Perform this calculation at each point:
SRS% =
P
S
a
× 100
14.1.3 The long term reproducibility at a setpoint is the
greatest absolute weekly reproducibility at a setpoint.
14.1.4 Determine the precision over the test period at a
setpoint by calculating the standard deviation of all the
measured values (both upscale and downscale) for that
setpoint. Perform this calculation at each setpoint:
P
L
=
( V
i
−
A
a
)
2
∑
(
)
j
∑
( )
w
∑
n
j
∑
(
)
w
∑
P
L
= Precision over the test period
V
i
=
The i
th
reading at a setpoint for a given cycle
A
a
=
Average measured
l
n
j
=
N
umber of readings at a setpoint for a given cycle
w =
N
umber of weeks
14.1.5 Determine the reproducibility at a setpoint by
dividing the precision over the test period at this
setpoint by the average setpoint. This is expressed as a
percentage of setpoint. Perform this calculation at each
setpoint:
RS% =
P
L
S
a
× 100
14.1.6 The overall reproducibility of the DUT is the
maximum value calculated in Section 14.1.4:
±
RD% = RS
max
RD = Reproducibility of the device
14.1.7 Calculate zero drift by subtracting the minimum
zero value from the maximum zero value and dividing
by two. This number is reported as ± sccm or slm over
the specified time period.
15 Data Presentation
15.1 Plot the average measured value of each setpoint
(10%, 50%, 100%) for each measurement period on a
graph, with the x-axis representing time, and the y-axis
showing the actual flow output in sccm or slm.
15.2 Plot the measured value at zero for each
measurement period on a graph, with the x-axis
representing time and the y-axis showing flow output
signal in sccm or slm.
15.3 Reproducibility — Report a single number, as
calculated above, as a percentage of reading stated, with
the time period of the test.
15.4 Zero Drift — Report a single number, as
calculated above, stated with the time period of the test.
16 Related Documents
16.1 SEMI
Standard
SEMI E67 — Test Method for Determining Reliability
of Mass Flow Controller (Refer to this standard if
reliability data is needed for some of the parameters
tested in this method.)
NOTICE: Unless otherwise indicated, all documents
cited shall be the latest published versions.

SEMI E69-0298 © SEMI 1998, 2003 10
NOTICE: SEMI makes no warranties or
representations as to the suitability of the standards set
forth herein for any particular application. The
determination of the suitability of the standard is solely
the responsibility of the user. Users are cautioned to
refer to manufacturer’s instructions, product labels,
product data sheets, and other relevant literature
respecting any materials mentioned herein. These
standards are subject to change without notice.
The user’s attention is called to the possibility that
compliance with this standard may require use of
copyrighted material or of an invention covered by
patent rights. By publication of this standard, SEMI
takes no position respecting the validity of any patent
rights or copyrights asserted in connection with any
item mentioned in this standard. Users of this standard
are expressly advised that determination of any such
patent rights or copyrights, and the risk of infringement
of such rights, are entirely their own responsibility.
Copyright by SEMI® (Semiconductor Equipment and Materials
International), 3081 Zanker Road, San Jose, CA 95134. Reproduction o
f
the contents in whole or in part is forbidden without express written
consent of SEMI.

SEMI E70-1103 © SEMI 1998, 2003 1
SEMI E70-1103
GUIDE FOR TOOL ACCOMMODATION PROCESS
This guide was technically approved by the Global Facilities Committee and is the direct responsibility of the
North American Facilities Committee. Current edition approved by the North American Regional Standards
Committee on September 3, 2003. Initially available at www.semi.org September 2003; to be published
November 2003. Originally published June 1998.
1 Purpose
1.1 This document will provide an overview of the
various elements of Tool Accommodation, a
methodology by which semiconductor processing
equipment is installed in a cost-effective and timely
manner. This addition to the SEMI Tool
Accommodation Standards set describes the process by
which the referenced SEMI documents can be
effectively used to achieve tool installation cost and
schedule goals.
2 Scope
2.1 This overview document will provide process
development, facilities, manufacturing, and sales
engineers (as well as purchasing agents and managers)
with a basic understanding of the various elements in a
Tool Accommodation methodology. This process
emphasizes quality, completeness, timeliness, and cost-
effectiveness as key elements of successfully installing
semiconductor processing equipment into wafer
fabrication facilities. By describing a generic process
flow, this document identifies a road map for using
published standards that comprehend all the procedures
involved in tool accommodation from procurement
through acceptance. As a common ground for
communication and comparison, terms and definitions
are also included.
NOTICE: This standard does not purport to address
safety issues, if any, associated with its use. It is the
responsibility of the users of this standard to establish
appropriate safety and health practices and determine
the applicability of regulatory or other limitations prior
to use.
3 Referenced Standards
3.1 SEMI Standards
SEMI E6 — Guide for Semiconductor Equipment
Installation Documentation
SEMI E10 — Specification for Definition and
Measurement of Equipment Reliability, Availability,
and Maintainability (RAM)
SEMI E45 — Test Method for the Determination of
Inorganic Contamination from Minienvironments Using
Vapor Phase Decomposition-Total Reflection X-Ray
Spectroscopy (VPD-TXRF), VPD-Atomic Absorption
Spectroscopy (VPD-AAS), or VPD/Inductively
Coupled Plasma-Mass Spectrometry (VPD/ICP-MS
SEMI E49 — Guide for Standard Performance,
Practices, and Sub-Assembly for High Purity Piping
Systems and Final Assembly for Semiconductor
Manufacturing Equipment
SEMI E49.1 — Guide for Tool Final Assembly,
Packaging and Delivery
SEMI E49.2 — Guide for High Purity Deionized Water
and Chemical Distribution Systems in Semiconductor
Manufacturing Equipment
SEMI E49.3 — Guide for Ultrahigh Purity Deionized
Water and Chemical Distribution Systems in
Semiconductor Manufacturing Equipment
SEMI E49.4 — Guide for High Purity Solvent
Distribution Systems in Semiconductor Manufacturing
Equipment
SEMI E49.5 — Guide for Ultrahigh Purity Solvent
Distribution Systems in Semiconductor Manufacturing
Equipment
SEMI E49.6 — Guide for Subsystem Assembly and
Testing Procedures - Stainless Steel Systems
SEMI E49.7 — Purity Guide for the Design and
Manufacture of Ultrapure Water and Liquid Chemical
Systems in Semiconductor Process Equipment
SEMI E49.8 — Guide for High Purity and Ultrahigh
Purity Gas Distribution Systems in Semiconductor
Manufacturing Equipment
SEMI E51 — Guide for Typical Facilities Services and
Termination Matrix
SEMI S4 — Safety Guideline for the
Segregation/Separation of Gas Cylinders Contained in
Cabinets
3.2 ISO Standards
1
ISO 14644-1 — Cleanrooms and associated controlled
environments Part 1: Classification of air cleanliness.
1 International Organization for Standardization, ISO Central
Secretariat, 1, rue de Varembé, Case postale 56, CH-1211 Geneva 20,
Switzerland. Telephone: 41.22.749.01.11; Fax: 41.22.733.34.30,
Website: www.iso.ch