semi合集-English.pdf - 第857页

SEMI E115-0302 E © SEMI 2002 3 8 Test Setup for Determining Load Impedance and Efficiency 8.1 Two test methods are des cribed for analyzing matching net works. The first method for det ermining the load impedance a n d e…

100%1 / 7923
SEMI E115-0302
E
© SEMI 2002 2
complex conjugate of a load impedance of 2.0 – j20
ohms would be 2.0 + j20 ohms.
5.2.2 device under test (DUT) — the matching network
to be tested.
5.2.3 harmonic frequency — the harmonic frequencies
are defined as integer multiples of the fundamental
frequency. For example, the second harmonic of 13.56
MHz is 27.12 MHz.
5.2.4 “L” type matching network — this type of
network consists of a tuning element that is connected
to ground, which is often a variable capacitor, and
another tuning element that is in series with the output
connection. The series section of the “L” matching
network typically consists of an inductor and a
capacitor, one of which is variable.
5.2.5 load and tune position — for some matching
networks, the tuning elements are referred to as the
Load Position and the Tune Position. This terminology
is common for “L” type matching networks, which
have a tuning element that is connected to ground and
another tuning element that is in series with the output
connection. The Load Position corresponds to the
tuning element that is grounded and is associated with
matching to the real part of the load impedance. The
Tune Position corresponds to the tuning element that is
in series with the output and is associated with
matching to the reactive part of the load impedance.
5.2.6 load impedance — the load impedance is the
impedance to which a matching network is matched.
5.2.7 load impedance simulator — the Load
Impedance Simulator is a device that presents a load
impedance to which a matching network can match.
Details of a typical Load Simulator can be found in the
Related Information section of this test method.
5.2.8 matched input impedance — a matched load
impedance is defined as typically having a magnitude
of 50 ± 3.3 ohms at a phase angle of up to ± 3.8
degrees. In other words, the load is considered matched
if the reflection coefficient is no greater than 0.032 at
any phase angle.
5.2.9 matching network — the device used to
transform the impedance of the load (chamber/chuck)
to match the impedance of the generator/cable
assembly, which is typically 50 ohms.
5.2.10 power efficiency — the ratio of the power
exiting the matching network divided by the power
entering the matching network.
5.2.11 S-parameters — the scattering matrix used to
describe a network. The reflection coefficient is the
S11 parameter and the transmission coefficient is the
S21 parameter.
5.2.12 tuning element position — the position of the
tuning element is defined as the output voltage or
output encoder value that corresponds to the position of
a variable tuning element in a Matching Network. For
example, the voltage from a rotary potentiometer on the
rotating shaft of a variable capacitor (the “Tuning
Element”) would be referred to as the capacitor’s
“Position”. In this example, the position/voltage
corresponds to a certain shaft location or position.
6 Test Apparatus
6.1 RF Vector Network Analyzer — The Network
Analyzer is used to measure the load impedance and
efficiency of the matching network. The Network
Analyzer requires vector capability so that both the
magnitude of phase of the reflection coefficient and
transmission coefficient can be measured at the
operating frequency. The Network Analyzer shall have
an up-to-date calibration per the manufacturer.
6.2 Coaxial Output Adapter An adapter to convert
the output connection of the matching network to a
standard coaxial interface is required for some of the
tests.
6.3 RF Adapters and Terminations — Various adapters
may be necessary to convert between different types of
coaxial connectors (e.g., type N to type HN adapters,
etc.). All adapters used shall have the same nominal
characteristic impedance as the system, which is
typically 50 ohms. For some measurements, additional
coaxial cable assemblies are used. These cable
assemblies shall also be of the same nominal
characteristic impedance as the system. Standard
terminations are also used, such as shorts, opens, and
precision 50-ohm loads.
6.4 RF Load Impedance Simulator — A device that
can be attached to the output of the DUT to act as a
load for the DUT is required for some of the
measurements. The load simulator shall have an
impedance range to match a minimum of 80% of the
tuning space of the matching network to be tested.
7 Safety Precautions
7.1 Work should be conducted in accordance with local
safety requirements and test device manufacturer
recommended safety procedures. The tests described in
this document involve using low output power test
instrumentation (typically less than 10 milli-Watt).
7.2 The area immediately surrounding the Test Setup
shall be keep free and clear of unnecessary equipment
and materials.
SEMI E115-0302
E
© SEMI 2002 3
8 Test Setup for Determining Load Impedance
and Efficiency
8.1 Two test methods are described for analyzing
matching networks. The first method for determining
the load impedance and efficiency measures the
complex conjugate of the load impedance and then
corrects for the matching network losses to determine
the load impedance and efficiency. A schematic of the
Test Setup is shown in Figure 1. The method uses a
Network Analyzer to measure the reflection coefficient,
which is related to the load impedance, and the
transmission coefficient, which is related to the
efficiency. The Test Setup for this approach consists of
the Network Analyzer, the matching network to be
tested (DUT), coaxial test cables, and the appropriate
adapters (if any) to connect the DUT to the Network
Analyzer.
8.2 The second method for determining the load
impedance and efficiency uses a Load Impedance
Simulator attached to the output of the matching
network. A schematic of the Test Setup is shown in
Figure 2. The Test Setup for this approach consists of
the Network Analyzer, the matching network to be
tested (DUT), the load simulator, coaxial test cables,
the appropriate adapter (if any) to connect the DUT to
the Network Analyzer, and the appropriate adapter to
connect the load simulator to the DUT.
8.3 Prior to making any measurements, the Network
Analyzer shall be turned on and allowed to warm up
before the testing is to take place. This time will allow
for electronics to come to a stable operating condition
for the measurements.
9 Test Procedure for Determining Load
Impedance and Efficiency
9.1 Two test procedures can be used to determine the
load impedance and efficiency of the matching
network. The first method is designed for “L” type
matching networks, where the losses are dominated by
the loss resistance of the inductor that is in series with
the load impedance. For the case where there are finite
losses in the shunt capacitor, the capacitor losses can be
lumped in with the inductor losses without introducing
significant error (usually less than 0.5% for typical
values of < 0.1 ohms). Lumping the total losses into an
overall series loss will also cause a slight shift in the
reactive part of the impedance, but the magnitude of the
shift is on the same order as the impedance
measurement uncertainty and can be ignored.
9.2 The second method is designed for other matching
network types and uses a load simulator to determine
the load impedance and efficiency.
9.3 Test Method 1 for Determining Matching Network
Load Impedance and Efficiency
9.3.1 This test method shall be used for “L” type
matching networks of the type shown schematically in
Figure 1, where the losses in the network are dominated
by the loss resistance of the inductor, RLOSS. The
efficiency for this type of matching network is given as
Eff =
RLOAD
RLOAD + RLOSS
(1)
where RLOAD refers to the real part of the load
impedance and RLOSS refers to the losses of the
matching network.
9.3.2 For this type of network, the real part of the
complex conjugate impedance, Re(Zout*), contains the
real part of the load impedance plus twice the loss
resistance, RLOSS.
Re(
Z
ou
t
*)
=
RLOAD + 2RLOS
S
(2)
9.3.3 The load impedance, therefore, is equal to the
complex conjugate impedance less twice the loss
resistance (along with the sign change of the reactive
part of the conjugate impedance). For example, if the
conjugate impedance is measured as 3 + j20 and
RLOSS is determined to be 0.5 ohms, then the load
impedance is 2 – j20 ohms.
9.3.4 The efficiency of the matching network and the
loss resistance, RLOSS, can be determined by
measuring both the transmission coefficient, S21, and
the reflection coefficient, S11, in the Test Setup shown
in Figure 1. Note that the reflection coefficient
measurement, S11, is equivalent to measuring the
complex conjugate impedance. If the matching
network is considered as a test load with an impedance
equal to the complex conjugate impedance, then the
loss resistance is found by measuring the efficiency of
the test load. This efficiency, Effm, can be expressed as
Effm =
Re(
Z
out*) RLOSS
Re(Zout*)
(3)
where Re(Zout*) is the real part of the complex
conjugate load impedance, Zout*. The measured
efficiency, Effm, can be determined from the S21 and
S11 measurements (as shown later in this section).
Thus, the measurements of Re(Zout*) and Effm can be
used to determine RLOSS as
)1(*)Re( EffmZoutRLOSS ×
=
(4)
and the load impedance and power efficiency of the
matching network can then be determined from
Effc =
Re(
Z
out*) 2RLOSS
Re(Zout*) RLOSS
(5)
SEMI E115-0302
E
© SEMI 2002 4
RLOAD = Re(
Z
ou
t
*) 2RLOS
S
(6)
X
LOAD =−Im(
Z
ou
t
*) (7)
where Effc is the calculated power efficiency based on
the measurement of Re(Zout*) and Effm, RLOAD is the
real part of the load impedance, and XLOAD is the
imaginary part of the load impedance.
9.3.5 Calibrate the Network Analyzer at the desired
operating frequency (e.g., 13.56 MHz). The Network
Analyzer shall be calibrated for measuring the
reflection coefficient at test Port 1 and for measuring
the transmission coefficient at test Port 2 (see Figure 1)
using the calibration kit provided with the Network
Analyzer. This measurement requires measuring the
S11 and S21 S-parameters and requires a full 2-port
calibration. The calibration shall be performed at fixed
frequency (continuous-wave operation) using the
lowest bandwidth possible (typically 10 Hz). The
calibration for each port shall include the additional test
cables and any additional adapters.
9.3.6 After calibration of the Network Analyzer, the
cable connected to Port 1 of the Network Analyzer shall
be connected to the output of the DUT. The cable
connected to Port 2 of the Network Analyzer shall be
connected to the input of the DUT.
9.3.7 The tuning elements shall be moved to their
minimum positions before the measurement is initiated.
After all connections are visually inspected for proper
contact and the Network Analyzer has stabilized, the
value of the complex conjugate impedance (Zout*), the
magnitude of the reflection coefficient (S11), and the
magnitude of the transmission coefficient (S21) shall be
recorded.
9.3.8 The efficiency when the DUT is viewed as a test
load, Effm, is determined from both the reflection and
transmission coefficients. The efficiency can be
calculated by taking the ratio of the output power
divided by the input power. The output power is
simply (S21)
2
and the input power is (1-(S11)
2
).
()
()
2
2
111
21
S
S
Effm
=
Typically, the reflection and transmission coefficients
are expressed in terms of dB (decibels). The conversion
between dB and efficiency is expressed as
)10/dBin 11S(
)10/dBin 21S(
101
10
=Effm
For example, if the transmission coefficient is measured
to be –10.2 dB and the reflection coefficient is
measured to be –0.61 dB, then Effm would be 0.7288.
The efficiency based on this measurement can then be
used to calculate RLOSS, Effc, RLOAD, and XLOAD by
using the equations previously shown. All of these
calculated numbers using equations 3–6 shall be
recorded, as well as the positions of the tuning elements
of the matching network.
9.3.9 For the next measurement, Tune Position shall
remain fixed, and the Load Position shall be increased
by an increment equal to no more than 10% of the full-
scale range of the tuning element position. For
example, if the range of the tuning element is 10 volts,
then the tuning element should be moved in increments
of no greater than 1 volt. A smaller increment shall be
used for the case where the incremental change in Load
Position results in an incremental impedance change of
more than 20% of the total impedance variation
measured by the full-scale variation of the Load
Position. For example, if the real part of the load
impedance varies 15 ohms over the 10 volt variation of
the Load Position, then a smaller Load Position
increment shall be used if the real load impedance
varies by more than 3 ohms between increments (0.2 ×
15 = 0.3). After the tuning elements have been moved
to their new values, the previous measurement steps
shall be repeated.
9.3.10 After the Load Position has been varied over its
entire range, the Tune Position shall be increased by an
increment equal to no more than 10% of the full-scale
range of the tuning element position. The Load
Position shall be moved back to its minimum position
and the above steps shall be repeated until the entire
tuning range of the matching network is measured.
9.3.11 The data shall be recorded and then presented in
both graphical and tabular forms. An example of a
typical impedance range graph is shown in Figure 3 for
the real load impedance and in Figure 4 for the reactive
load impedance. An example of a typical efficiency
plot is shown in Figure 5. An example of data
presented in tabular form is shown in Table I.
9.4 Test Method 2 for Determining Matching Network
Load Impedance and Efficiency
9.4.1 This test method shall be used for matching
networks that are not necessarily dominated by a series
loss resistance as in an ideal “L” type network. This
method uses a Load Simulator(s) attached to the DUT
and assumes that the DUT has two tuning elements.
The Load Simulator(s) shall have a tuning range that
will cover no less than 80% of the tuning range of the
matching network. Details of a typical Load Simulator
can be found in the Related Information section of this
Test Method. The test method outlined here assumes
that the Load Simulator(s) contains variable tuning
elements with position indicators to allow the load