semi合集-English.pdf - 第2178页

SEMI E54.16-0705 © SEMI 2005 23 Table 22 Actuator- AO Object Instance Network Services Actuator-AO Object (Aao) Profile ID = 180.31, Instance ID = 01 through n Service Request Code Service Name CDM Tag Request Parameters…

100%1 / 7923
SEMI E54.16-0705 © SEMI 2005 22
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
2 Abort SeiS2 Sensor-BI-TH Object
RQ_ABORT (*)
#1
3 Recover SeiS3 Sensor-BI-TH Object
RQ_RECOVER (*)
#1
6 Operate SeiS4 Sensor-BI-TH Object
RQ_NORMAL
4 GetAttribute SeiS5 Read NV or CP NV or CP Value
5 SetAttribute SeiS6 Sensor-BI-TH Object
RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault SeiS7 Sensor-BI-TH Object
RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.10.1 Sensor-BI-TH Object Network Variables A new functional profile is defined with the following
mandatory network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles
for SEMI SAN-compliant devices based on LONWORKS.
7.10.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.10.2 Sensor-BI-TH Object Configuration Parameters — The Sensor-BI-TH object has configuration properties to
control exception reporting as shown in Table 19. These parameters are Standard Configuration Property Types
(SCPTs). Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.11 Actuator-AO Object (Aao) — The presentation of the Actuator Analog Output (Actuator-AO) object instance
attributes are as indicated in Table 21. The presentation of Actuator-AO object services is indicated in Table 22.
Table 21 Actuator-AO Object Instance Network Variables
Actuator-AO Object (Aao)
Profile ID = 180.31, Instance ID = 01 through n
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP AaoA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO AaoA2 nvoStatus output of the Actuator-AO Object
3 Alarm Enable NVI AaoA3 nviRequest input of the Actuator-AO Object
4 Warning Enable NVI AaoA4 nviRequest input of the Actuator-AO Object
16 Setting NVI AaoA16 Typedef (*)
#3
SNVT_xxx
#2
17 SafeState CP AaoA17 Typedef BOOL SCPTsafeState (*)
#3
18 WatchRate CP AaoA18 SCPTmaxRcvTime
19 Watchdog CP AaoA19 SCPTmaxRcvTime
#1
64 Offset CP AaoA64 SCPToffset
65 Gain CP AaoA65 SCPTgain
66 DataType CP AaoA66 SCPTnvType
67 DataUnits CP AaoA67 SCPTnvType
#1
A value of 0 is used to disable the watchdog timeout.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
SEMI E54.16-0705 © SEMI 2005 23
Table 22 Actuator-AO Object Instance Network Services
Actuator-AO Object (Aao)
Profile ID = 180.31, Instance ID = 01 through n
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset AaoS1 Actuator-AO Object
RQ_RESET
2 Abort AaoS2 Actuator-AO Object
RQ_ABORT (*)
#1
3 Recover AaoS3 Actuator-AO Object
RQ_RECOVER (*)
#1
6 Operate AaoS4 Actuator-AO Object
RQ_NORMAL
4 GetAttribute AaoS5 Read NV or CP NV or CP Value
5 SetAttribute AaoS6 Actuator-AO Object
RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault AaoS7 Actuator-AO Object
RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.11.1 Actuator-AO Object Network Variables A new functional profile is defined with the following mandatory
network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles for SEMI
SAN-compliant devices based on LONWORKS.
7.11.1.1 SNVT_xxx — The setting of the actuator (associated with the object instance) that is to be made available
on the network. The form and content of this SNVT is context-specific.
7.11.2 Actuator-AO Object Configuration Parameters — The Actuator-AO object has configuration properties to
control exception reporting as shown in Table 21. These parameters are Standard Configuration Property Types
(SCPTs). Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.12 Actuator-EO Object (Aeo) — The presentation of the Actuator Enumerated Output (Actuator-EO) object
instance attributes are as indicated in Table 23. The presentation of Actuator-EO object services is indicated in Table
24.
Table 23 Actuator-EO Object Instance Network Variables
Actuator-EO Object (Aeo)
Profile ID = 180.34, Instance ID = 01 through o
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP AeoA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO AeoA2 nvoStatus output of the Actuator-EO Object
3 Alarm Enable NVI AeoA3 nviRequest input of the Actuator-EO Object
4 Warning Enable NVI AeoA4 nviRequest input of the Actuator-EO Object
16 Setting NVI AeoA16 Typedef (*)
#3
SNVT_xxx
#2
17 SafeState CP AeoA17 Typedef BOOL SCPTsafeState (*)
#3
18 WatchRate CP AeoA18 SCPTmaxRcvTime
19 Watchdog CP AeoA19 SCPTmaxRcvTime
#1
#1
A value of 0 is used to disable the watchdog timeout.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
SEMI E54.16-0705 © SEMI 2005 24
Table 24 Actuator-EO Object Instance Network Services
Actuator-EO Object (Aeo)
Profile ID = 180.34, Instance ID = 01 through o
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset AeoS1 Actuator-EO Object
RQ_RESET
2 Abort AeoS2 Actuator-EO Object
RQ_ABORT (*)
#1
3 Recover AeoS3 Actuator-EO Object
RQ_RECOVER (*)
#1
6 Operate AeoS4 Actuator-EO Object
RQ_NORMAL
4 GetAttribute AeoS5 Read NV or CP NV or CP Value
5 SetAttribute AeoS6 Actuator-EO Object
RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault AeoS7 Actuator-EO Object
RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.12.1 Actuator-EO Object Network Variables A new functional profile is defined with the following mandatory
network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles for SEMI
SAN-compliant devices based on LONWORKS.
7.12.1.1 SNVT_xxx — The setting of the actuator (associated with the object instance) that is to be made available
on the network. The form and content of this SNVT is context-specific.
7.12.2 Actuator-EO Object Configuration Parameters — The Actuator-EO object has configuration properties to
control exception reporting as shown in Table 23. These parameters are Standard Configuration Property Types
(SCPTs). Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.13 Actuator-BO Object (Abo) — The presentation of the Actuator Binary Output (Actuator-BO) object instance
attributes are as indicated in Table 25. The presentation of Actuator-BO object services is indicated in Table 26.
Table 25 Actuator-BO Object Instance Network Variables
Actuator-BO Object (Abo)
Profile ID = 180.33, Instance ID = 01 through p
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP AboA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO AboA2 nvoStatus output of the Actuator-BO
Object
3 Alarm Enable NVI AboA3 nviRequest input of the Actuator-BO
Object
4 Warning Enable NVI AboA4 nviRequest input of the Actuator-BO
Object
16 Setting NVI AboA16 Typedef (*)
#3
SNVT_xxx
#2
17 SafeState CP AboA17 Typedef BOOL SCPTsafeState (*)
#3
18 WatchRate CP AboA18 SCPTmaxRcvTime
19 Watchdog CP AboA19 SCPTmaxRcvTime
#1
#1
A value of 0 is used to disable the watchdog timeout.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.