semi合集-English.pdf - 第837页
output encoder v alue that corresponds to the position of a variable tuning element in a Matching Network. For example, the voltage from a rotary potentiometer on the rotating shaft of a variable capacitor (t he “Tuning …

4 Referenced Standards
4.1 SEMI Standards
SEMI E10 — Specification for Definition and
Measurement of Equipment Reliability, Availability,
and Maintainability (RAM)
SEMI E78 — Electrostatic Compatibility - Guide to
Assess and Control Electrostatic Discharge (ESD) and
Electrostatic Attraction (ESA) for Equipment
SEMI E114 — Test Method for RF Cable Assemblies
Used in Semiconductor Processing Equipment RF
Power Delivery Systems
SEMI E115 — Test Method for Determining the Load
Impedance and Efficiency of Matching Networks Used
in Semiconductor Processing Equipment RF Power
Delivery Systems
SEMI E135 — Test Method for RF Generators to
Determine Transient Response for RF Power Delivery
Systems used in Semiconductor Processing Equipment
4.2 IEEE Standard
1
IEEE-STD-383 — IEEE Standard for Type Test of
Class 1E Electrical Cables, Field Splices, and
Connections for Nuclear Power Generating Stations
4.3 MIL-Specification
2
MIL-C-17G — General Specification for Cables, Radio
Frequency, Flexible and Semirigid
MIL-PRF-39012D — General Specification for
Connectors, Coaxial, Radio Frequency
NOTICE: Unless otherwise indicated, all documents
cited shall be the latest published versions.
5 Terminology
5.1 Abbreviations and Acronyms
5.1.1 CVD — Chemical Vapor Deposition
5.1.2 PVD — Physical Vapor Deposition
5.1.3 VSWR — Voltage Standing Wave Ratio
5.2 Definitions
5.2.1 cable assembly — the section of cable
(transmission line), including the connectors, used to
connect various parts of the RF power delivery system.
1 Institute of Electrical and Electronics Engineers, IEEE Operations
Center, 445 Hoes Lane, P.O. Box 1331, Piscataway, New Jersey
08855-1331, USA. Telephone: 732.981.0060; Fax: 732.981.1721
website: www.ieee.org
2 Available from Naval Publication and Forms Center, 5801 Tabor
Avenue, Philadelphia PA 19120 U.S.A website:
www.dodssp.daps.mil/products.htm.
5.2.2 electrical length — the length of the cable
assembly at the operating frequency expressed in terms
of degrees, where one wavelength at the nominal
operating frequency is equal to 360°.
5.2.3 harmonic frequency — the harmonic frequencies
are defined as integer multiples of the fundamental
frequency. For example, the second harmonic of 13.56
MHz is 27.12 MHz.
5.2.4 load Q — the quality factor, Q, of the load is
defined here as the magnitude of the reactive part of the
load divided by the real part of the load. For example, a
load impedance of 2 – j20 ohms would have a load Q of
10.
5.2.5 matched load — a matched load impedance is
defined as typically having a magnitude of 50 3.3
ohms at a phase angle of up to 3.8°. In other words,
the load is considered matched if the reflection
coefficient is no greater than 0.032 at any phase angle.
5.2.6 matching network — the device used to
transform the impedance of the load (chamber/chuck)
to match the impedance of the generator/cable
assembly, which is typically 50 ohms.
5.2.7 matching network load impedance — the
impedance of the load to which the matching network is
matched.
5.2.8 MTBF
p
— mean (productive) time between
failures; the average time the equipment performed its
intended function between failures; productive time
divided by the number of failures during that time.
Only productive time is included in this calculation.
5.2.9 power efficiency — the power efficiency of a
matching network is defined as the power exiting the
network (output power) divided by the power entering
the network (input power).
5.2.10 RF applicator/interface — the part of the
chamber where the RF system is terminated. This
interface can either be a chuck (driven electrode) or the
coil/antenna part of a plasma source.
5.2.11 RF system — the RF system is defined as the
combination of the generator, matching network,
chamber interface, and the associated connecting cable
assemblies that are specific to a particular tool/chamber.
5.2.12 tap point — for some systems, partial tuning of
the matching network is achieved by switching in a
combination of fixed tuning elements, such as different
values of capacitors. The tap point is defined as the
position of the switch(es) that connect or disconnect
tuning elements in the matching network circuit.
5.2.13 tuning element position — the position of the
tuning element is defined as the output voltage or
SEMI E113-1104 © SEMI 2001, 2004 2

output encoder value that corresponds to the position of
a variable tuning element in a Matching Network. For
example, the voltage from a rotary potentiometer on the
rotating shaft of a variable capacitor (the “Tuning
Element”) would be referred to as the capacitor’s
“Position”. In this example, the position/voltage
corresponds to a certain shaft location or position.
6 Ordering Information
6.1 Semiconductor manufacturers may use this
standard when procuring processing equipment to
specify RF power delivery system performance and
documentation. The equipment suppliers may also use
this document to specify the RF system components
and subassemblies.
6.2 Orders for equipment in accordance with this
standard shall include:
6.2.1 This specification number and date of issue.
6.2.2 Any certification showing passage of
qualification tests required to be provided (optional).
6.2.3 Any test results required to be included in reports
to be provided (optional).
7 Requirements
7.1 Semiconductor processing equipment shall be
designed and built with a reliable RF power delivery
system. The requirements defined in this specification
address the integrated RF system as well as the
following RF power delivery system components: the
RF cable assemblies, the matching network, the
generator, and the RF applicator/interface, as well as
specific components of these assemblies or systems.
7.2 The mean (productive) time between failures
(MTBF
p
), as outlined in SEMI E10, of the generator,
matching network, and the RF power delivery system
as a whole shall be provided by the supplier, as well as
the test method used to determine MTBF
p
.
7.3 RF Cable Assemblies (Transmission Lines)
7.3.1 Many RF power delivery systems use RF cable
assemblies to transfer power from the generator to the
input of the matching network and, in some cases, from
the output of the matching network to the process
chamber (e.g., the chuck assembly). All cable
assemblies shall adhere to industry standards for cables
and connectors (e.g., MIL-C-17G, MIL-PRF-39012D,
IEEE-STD-383) in terms of rated power/voltage/
current, allowed bending radius, expected variation in
characteristic impedance, and attenuation at the
expected operating frequency(s) for the specific cable
type (e.g., RG-217, RG-218) per the cable
manufacturer’s specifications. SEMI E114 or an
equivalent test method(s) shall be used to determine the
electrical length, power dissipation (loss), and
characteristic impedance of the RF cable assemblies.
7.3.2 The length of the cable assemblies used to
connect portions of the RF power delivery system shall
be specified in terms of electrical length at the nominal
operating frequency, in addition to the nominal physical
length. The electrical length shall be given in terms of
degrees of phase shift. Variations in the dielectric
properties (e.g., phase velocity, characteristic
impedance) of the cable assemblies can cause the
electrical length to differ between assemblies.
7.3.3 The electrical length of cables used between the
matching network and the chamber (if any) shall be
specified to within 0.25° of the standard electrical
length value at the operating frequency for fixed
frequency systems or at the midpoint frequency for
variable frequency systems, for frequencies less than or
equal to 13.56 MHz. For frequencies above 13.56
MHz, the length should be specified to a value (in
degrees) equal to the frequency in MHz multiplied by
0.018 (e.g., the specification for 60 MHz would be
60 0.018 = 1.1°). For example, at 13.56 MHz, the
physical length of typical cable (RG-217)
corresponding to 0.25° of phase shift (0.5° of reflection
coefficient phase shift) would be approximately 1 cm.
This specification would result in impedance variations
seen by the matching network of less than
approximately 1 percent between processing chambers.
7.3.4 The length of cables used between the matching
network and the generator shall be specified to within
1.0° of the standard electrical length value at the
operating frequency for fixed frequency systems or at
the midpoint frequency for variable frequency systems,
for frequencies less than or equal to 13.56 MHz. For
frequencies above 13.56 MHz, the length shall be
specified to a value (in degrees) equal to the frequency
in MHz multiplied by 0.074 (e.g., the specification for
60 MHz would be 60 0.074 = 4.44°). For example, at
13.56 MHz, the physical length of typical cable (RG-
217) corresponding to 1.0° of phase shift (2.0° of
reflection coefficient phase shift) would be
approximately 4 cm. This specification would
minimize the impedance transformation at the harmonic
frequencies (10° of phase shift at the 10
th
harmonic
frequency).
7.3.5 The expected power dissipation in the cable
assembly(s) supplied with the system shall be provided
as a function of the operating frequency(s) of the
system. The amount of power transmitted through the
cable assembly shall be given in terms of dB (decibels)
and percentage. The relationship between dB and
percentage is given as:
SEMI E113-1104 © SEMI 2001, 2004 3

Percentage = 100 10
(dB/10)
.
For example, approximately 94.8% (–0.232 dB of loss)
of the power at 13.56 MHz will be transmitted through
a cable assembly made from RG-217 cable with a
physical length of 15.24 meters (electrical length of
375.74°). In other words, 5.2% of the power is
dissipated in the cable assembly at 13.56 MHz.
7.4 Matching Networks
7.4.1 Matching networks transform the impedance of
the plasma load to match the impedance of the
generator, which is nominally 50 ohms. The
transformation is achieved by the use of various
reactive components, such as capacitors and inductors,
that “tune” the matching network by transforming the
impedance at the output of the network to the input of
the matching network. For a given frequency, there is a
fixed relationship between the impedance at the input of
the matching network and the impedance at the output
of the matching network (the load impedance). In other
words, the impedance to which the matching network is
matched (the load impedance) can be determined if the
transform properties of the network are known for a
given frequency. Typically, there are two methods of
impedance transformation. The first method uses a
fixed frequency (e.g., 13.56 MHz) and variable tuning
elements, while the second method uses a variable
frequency and fixed tuning elements. Specifications for
both methods are given below. SEMI E115 or an
equivalent test method(s) shall be used to determine the
load impedance and efficiency of matching networks
that are designed to operate at fixed frequency with a
50-ohm input impedance.
7.4.2 For those systems that use fixed frequency
operation, matching networks typically have two
variable tuning elements, which are usually variable
capacitors and/or inductors. These variable tuning
elements typically have an output voltage or encoder
value that corresponds to a certain value of the element
(i.e., an output voltage will correspond to a specific
value of capacitance or inductance in the matching
network). The value of the output voltage or encoder
value is referred to as the tuning element position. To
obtain information on the operation and performance of
the matching network, the tuning element positions
must be provided as outputs.
7.4.3 For those systems that use variable frequency
operation, matching networks typically have fixed
tuning elements (no variation) or tap points between
fixed tuning elements, and the frequency is varied to
obtain the best matched condition. In some cases, the
tap points are also varied for matching. To obtain
information on the operation and performance of these
types of networks, the operating frequency and the
input impedance (or reflection coefficient magnitude
and phase angle) shall be provided. For those systems
that have variable tap points, the tap point position shall
also be provided as an output.
7.4.4 For matching networks run at a fixed frequency
with variable tuning elements, the load impedance shall
be provided as a function of the tuning element
positions. In addition, the efficiency of the matching
network shall be provided as a function of the tuning
element positions. The information shall be provided in
tabular form. The increment of the tuning element
positions shall be in steps equal to or less than 10% of
the full range. For example, a voltage increment of 1
volt or less shall be used in the case where the full
range of the tuning element position is 10 volts. A plot
providing an example of the real part of the load
transformed to 50 ohms by the matching network as a
function of tuning element position indicator is shown
in Figure 1 and a plot of the reactive part of the load
impedance is shown in Figure 2. A plot of the power
efficiency is shown in Figure 3. An example of data to
be provided in tabular form is shown in Table 1. The
required uncertainty of the magnitude of the impedance
is 1.5%, the required uncertainty in the phase angle of
the impedance is 0.35°, and the required uncertainty
of the power efficiency is 2.0%. For example, a load
impedance of 2.0 – j20 ohms would have an uncertainty
in the real part of 0.15 ohms and an uncertainty in the
reactive part of 0.32 ohms.
7.4.5 For matching networks run at a variable
frequency with fixed tuning elements and/or tap points,
the efficiency and load impedance as a function of its
output parameters (frequency, input impedance, and tap
point value (if any)) shall be provided. The information
shall be provided in tabular form. The increment of the
output parameters shall be in steps equal to or less than
10% of the full range. For example, if the operating
frequency parameter is given as an output voltage, a
voltage increment of 1 volt or less shall be used in the
case where the full range of the output parameter is 10
volts. The required uncertainty of the magnitude of the
impedance is
1.5%, the required uncertainty in the
phase angle of the impedance is 0.35°, and the
required uncertainty of the power efficiency is 2.0%.
7.4.6 The tuning element positions/values for each
matching network (of the same type/model) shall be
adjusted to provide consistent efficiency and matching
network input impedance when the matching network is
connected to a fixed load impedance. The load
impedance used shall be one that is typically
encountered by the matching network during processing
and/or shall be an impedance that is near the mid-range
of the tuning space (e.g., 2 – j20 ohms). A simple way
to ensure network-to-network consistency is to adjust
SEMI E113-1104 © SEMI 2001, 2004 4