SEMI E54.16-0705 © SEMI 2005 22 Sensor-BI-TH Object (Sbith) Profile ID = 180.19, Instance ID = 01 through s Service Request Code Service Name CDM Tag Request Parameters Result Parameters 2 Abort SeiS2 Sensor-BI-TH Object…

100%1 / 7923
SEMI E54.16-0705 © SEMI 2005 21
7.9.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.9.2 Sensor-BI Object Configuration Parameters — The Sensor-BI object has configuration properties to control
exception reporting as shown in Table 19. These parameters are Standard Configuration Property Types (SCPTs).
Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.10 Sensor-BI-TH Object (Sbith) — The presentation of the Sensor Binary Input Threshold (Sensor-BI-TH) object
instance attributes are as indicated in Table 19. The presentation of Sensor-BI-TH object services is indicated in
Table 20.
Table 19 Sensor-BI-TH Object Instance Network Variables
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP SbiA1 Typedef unsigned char SCPTname
(*)
#4
2 Status NVO SbiA2 nvoStatus output of the Sensor-BI-TH
Object
3 Alarm Enable NVI SbiA3 nviRequest input of the Sensor-BI-TH
Object
4 Warning Enable NVI SbiA4 nviRequest input of the Sensor-BI-TH
Object
16 Value NVO SbiA16 Typedef (*)
#4
SNVT_xxx
#2
17 ReportInhibitTimer CP SbiA17 SCPTminSendTime
18 EnableReportRate CP SbiA18 SCPTmaxSendTime
#1
19 ReportRate CP SbiA19 SCPTmaxSendTime
64 DebounceControl CP SbiA64 Typedef unsigned char SCPTname
(*)
#4
65 AlarmState CP SbiA65 nvoStatus output of the Sensor-BI-TH
Object
66 WarningState CP SbiA66 nviRequest input of the Sensor-BI-TH
Object
67 ReadingValid NVO sbithA64 SNVT_switch
#3
68 State NVO sbithA65 nvoStatus output of the Sensor-BI-TH
Object
69 Status NVO sbithA66 nvoStatus output of the Sensor-BI-TH
Object
#1
A SCPTmaxSendTime value of 0 is used to inhibit report rate reporting.
#2
The form and content of this SNVT is context-specific.
#3
An invalid value output is used to indicate an invalid reading.
#4
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
Table 20 Sensor-BI-TH Object Instance Network Services
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset SeiS1 Sensor-BI-TH Object
RQ_RESET
SEMI E54.16-0705 © SEMI 2005 22
Sensor-BI-TH Object (Sbith)
Profile ID = 180.19, Instance ID = 01 through s
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
2 Abort SeiS2 Sensor-BI-TH Object
RQ_ABORT (*)
#1
3 Recover SeiS3 Sensor-BI-TH Object
RQ_RECOVER (*)
#1
6 Operate SeiS4 Sensor-BI-TH Object
RQ_NORMAL
4 GetAttribute SeiS5 Read NV or CP NV or CP Value
5 SetAttribute SeiS6 Sensor-BI-TH Object
RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault SeiS7 Sensor-BI-TH Object
RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.10.1 Sensor-BI-TH Object Network Variables — A new functional profile is defined with the following
mandatory network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles
for SEMI SAN-compliant devices based on LONWORKS.
7.10.1.1 SNVT_xxx — The value of the sensor (associated with the object instance) that is to be made available on
the network. The form and content of this SNVT is context-specific.
7.10.2 Sensor-BI-TH Object Configuration Parameters — The Sensor-BI-TH object has configuration properties to
control exception reporting as shown in Table 19. These parameters are Standard Configuration Property Types
(SCPTs). Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.11 Actuator-AO Object (Aao) — The presentation of the Actuator Analog Output (Actuator-AO) object instance
attributes are as indicated in Table 21. The presentation of Actuator-AO object services is indicated in Table 22.
Table 21 Actuator-AO Object Instance Network Variables
Actuator-AO Object (Aao)
Profile ID = 180.31, Instance ID = 01 through n
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP AaoA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO AaoA2 nvoStatus output of the Actuator-AO Object
3 Alarm Enable NVI AaoA3 nviRequest input of the Actuator-AO Object
4 Warning Enable NVI AaoA4 nviRequest input of the Actuator-AO Object
16 Setting NVI AaoA16 Typedef (*)
#3
SNVT_xxx
#2
17 SafeState CP AaoA17 Typedef BOOL SCPTsafeState (*)
#3
18 WatchRate CP AaoA18 SCPTmaxRcvTime
19 Watchdog CP AaoA19 SCPTmaxRcvTime
#1
64 Offset CP AaoA64 SCPToffset
65 Gain CP AaoA65 SCPTgain
66 DataType CP AaoA66 SCPTnvType
67 DataUnits CP AaoA67 SCPTnvType
#1
A value of 0 is used to disable the watchdog timeout.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
SEMI E54.16-0705 © SEMI 2005 23
Table 22 Actuator-AO Object Instance Network Services
Actuator-AO Object (Aao)
Profile ID = 180.31, Instance ID = 01 through n
Service Request
Code
Service Name CDM Tag Request Parameters Result Parameters
1 Reset AaoS1 Actuator-AO Object
RQ_RESET
2 Abort AaoS2 Actuator-AO Object
RQ_ABORT (*)
#1
3 Recover AaoS3 Actuator-AO Object
RQ_RECOVER (*)
#1
6 Operate AaoS4 Actuator-AO Object
RQ_NORMAL
4 GetAttribute AaoS5 Read NV or CP NV or CP Value
5 SetAttribute AaoS6 Actuator-AO Object
RQ_RESTORE (*)
#1
NVO Value
7 RestoreDefault AaoS7 Actuator-AO Object
RQ_PROPAGATE (*)
#1
NVO Value
#1
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.
7.11.1 Actuator-AO Object Network Variables — A new functional profile is defined with the following mandatory
network variables and behaviors. This functional profile forms part of the LONMARK Functional Profiles for SEMI
SAN-compliant devices based on LONWORKS.
7.11.1.1 SNVT_xxx — The setting of the actuator (associated with the object instance) that is to be made available
on the network. The form and content of this SNVT is context-specific.
7.11.2 Actuator-AO Object Configuration Parameters — The Actuator-AO object has configuration properties to
control exception reporting as shown in Table 21. These parameters are Standard Configuration Property Types
(SCPTs). Extensions to the current SCPT list and Interoperability Guidelines are marked by an asterisk (*).
7.12 Actuator-EO Object (Aeo) — The presentation of the Actuator Enumerated Output (Actuator-EO) object
instance attributes are as indicated in Table 23. The presentation of Actuator-EO object services is indicated in Table
24.
Table 23 Actuator-EO Object Instance Network Variables
Actuator-EO Object (Aeo)
Profile ID = 180.34, Instance ID = 01 through o
Sequence
Number
Name Storage Class CDM Tag Standard NV or CP Data Type
1 Name CP AeoA1 Typedef unsigned char SCPTname (*)
#3
2 Status NVO AeoA2 nvoStatus output of the Actuator-EO Object
3 Alarm Enable NVI AeoA3 nviRequest input of the Actuator-EO Object
4 Warning Enable NVI AeoA4 nviRequest input of the Actuator-EO Object
16 Setting NVI AeoA16 Typedef (*)
#3
SNVT_xxx
#2
17 SafeState CP AeoA17 Typedef BOOL SCPTsafeState (*)
#3
18 WatchRate CP AeoA18 SCPTmaxRcvTime
19 Watchdog CP AeoA19 SCPTmaxRcvTime
#1
#1
A value of 0 is used to disable the watchdog timeout.
#2
The form and content of this SNVT is context-specific.
#3
(*) LonMark interoperability extension. Refer to §6.8.3 for further definition.