semi合集-English.pdf - 第6797页

SEMI S2-0703a E © SEMI 1991, 2004 26  where segregation facilitates recycling or reuse; or  where separate abatement or t reatment met hods are required. NOTE 103: It is recommended that the equipment design documentat…

100%1 / 7923
SEMI S2-0703a
E
© SEMI 1991, 2004 25
reduced use of resources during maintenance
procedures (e.g., parts cleaning procedures could
include minimum rinse rates and rinse times);
recycling or reusing chemicals in the equipment,
rather than consuming only new materials;
reducing volume of packaging, increasing recycled
content of packaging, and/or designing reusable
packaging.
21.2.3 Chemical Selection
21.2.3.1 Chemical selection for process, maintenance,
and utility uses (e.g., gases, etchants, strippers, cleaners,
lubricants, and coolants) should take into account
effectiveness, environmental impacts, volume, toxicity,
by-products, decommissioning, disposal, and
recyclability; use of the least hazardous chemical is
preferred. To the extent practicable, the utilities,
maintenance, and process should be designed so that
the equipment operates without the use of:
ozone depleting substances (ODSs) as identified by
the Montreal Protocol, such as chlorofluorocarbons
(CFCs), methylchloroform, hydrochlorofluoro-
carbons (HCFCs), and carbon tetrachloride, or
perfluorocompounds (PFCs), including CF
4
, C
2
F
6
,
NF
3
, C
3
F
8
, and SF
6
, and CHF
3
due to their global
warming potential.
21.2.4 Prevention and Control of Unintended Releases
21.2.4.1 Equipment design, including feed, storage,
and waste collection systems, should prevent potential
unintended releases. At a minimum:
21.2.4.2 Secondary containment for liquids should be
capable of holding at least 110% (see first row of Table
A3-1 of Appendix 3) of the volume of the single largest
container, or the largest expected volume for any single
point failure.
NOTE 99: In some circumstances secondary containment
may be specified by the equipment supplier, but provided by
the user.
21.2.4.3 Chemical storage containers and secondary
containment should be designed for accessibility and
easy removal of collected material.
21.2.4.4 Secondary containment should have alarms
and gas detection or liquid sensing, as appropriate, or
have recommended sensing points identified in the
equipment installation instructions.
21.2.4.5 Equipment design should allow personnel to
determine all in-equipment container levels
conveniently without having to open the containers,
where ignorance of the level could result in an
inadvertent release.
21.2.4.6 Overfill level detectors and alarms should be
provided for in-equipment containers.
21.2.4.7 Secondary containment and other control
systems should be designed to ensure that chemicals
cannot be combined, where the combination could
result in an inadvertent release.
21.2.4.8 Equipment components should be compatible
with chemicals used in the manufacturing process.
Chemical systems should be designed for the specified
operating conditions, and have sufficient mechanical
strength and corrosion resistance for the intended use.
21.2.4.9 Equipment should be able to accept a signal
from a monitoring device and stop the supply of
chemical, at the first non-manual valve within the
affected system.
21.2.4.10 Chemical distribution systems should be
capable of automatic shutoff and remote shutdown.
21.2.5 Effluents, Wastes, and Emissions
NOTE 100: It is recommended that the manufacturer
document its efforts to minimize the equipment’s generation
of hazardous wastes, solid wastes, wastewater, and air
emissions.
NOTE 101: It is recommended that SEMI F5 be used for
guidance in gaseous effluent handling.
21.2.5.1 Equipment design that allows connection to a
central waste collection system is preferred, except
where collection at the equipment may facilitate
recycling or reuse opportunities or otherwise reduce
environmental impacts.
NOTE 102: It is recommended that individual drains and
exhausts be kept separate (e.g., separate outlets for acid drain,
solvent drain, deionized (DI) water drain; acid exhaust,
solvent exhaust).
21.2.5.1.1 Point-of-use collection containers should be
designed for accessibility as well as the possible reuse
and recycling of the collected materials.
21.2.5.2 Equipment should use partitions, double-
contained lines, or other similar design features to
prevent the mixing of incompatible waste streams.
21.2.5.3 The manufacturer should evaluate the
feasibility of including integrated controls for effluent
and emission treatment.
21.2.5.4 Dilution in excess of process or safety
requirements should not be used to reduce contaminant
discharge concentrations.
21.2.5.5 Segregation of effluents, wastes, and
emissions should be provided in the following cases:
where chemically incompatible;
SEMI S2-0703a
E
© SEMI 1991, 2004 26
where segregation facilitates recycling or reuse; or
where separate abatement or treatment methods are
required.
NOTE 103: It is recommended that the equipment design
documentation show evidence of consideration of by-products
generated during equipment operation, clean-up, maintenance,
and repair. By-products can include deposits in drains or
ducts, and replaceable parts (e.g., batteries, vapor lamps,
contaminated parts).
21.2.6 Decommissioning and Disposal
21.2.6.1 Equipment design should address (see Section
8.5.3 for documentation provisions) construction
material and component reuse, refurbishment, and
recycling.
21.2.6.2 The equipment should be designed to facilitate
equipment decontamination and disposal, e.g., by use of
removable liners or replaceable modules. This includes
minimizing the number of parts that become
contaminated with hazardous materials.
NOTE 104: It is recommended that SEMI S12 “Guidelines
for Equipment Decontamination” be used for guidance during
equipment decontamination.
22 Exhaust Ventilation
22.1 Equipment exhaust ventilation should be designed
to prevent potentially hazardous chemical exposures to
employees as follows:
22.1.1 As primary control when normal operations
present potentially hazardous chemical exposures to
employees by diffusive emissions that cannot be
otherwise prevented or controlled (e.g., wet decks, spin
coaters).
NOTE 105: In the context of this section, “primary control”
means that it is the control of first choice (e.g., rather than
personal protective equipment).
22.1.2 As supplemental control when intermittent
activities (e.g., chamber cleaning, implant source
housing cleaning) present potentially hazardous
chemical exposures to employees which cannot
reasonably be controlled by other means. Supplemental
exhaust hoods or enclosures may be integrated into the
equipment design, or supplied completely by the
equipment user.
22.1.2.1 When a procedure (e.g., cleaning) specified by
the supplier requires exhaust ventilation, the supplier
should include the minimum criteria for exhaust during
the procedure.
22.1.3 As secondary control when a single-point
failure presents the potential for employee exposures to
hazardous materials, and this exposure cannot be
controlled by other means (e.g., use of all welded
fittings).
EXCEPTION: Secondary exhaust control enclosures
for non-welded connections (e.g., valve manifold boxes
that enclose piping jungles) are not included in this
guideline for those hazardous gases that are transported
below atmospheric pressure (e.g., via vacuum piping
systems) if it can be demonstrated that equivalent leak
protection is provided. Equivalent protection may
include such things as equipping the vacuum delivery
system with a fail-safe (e.g., to close) valve
automatically activated by a loss of vacuum pressure.
Loss of vacuum pressure should also activate a visual
and audible alarm provided in visual or audible range of
the operator.
22.2 Equipment exhaust ventilation should be designed
and a ventilation assessment conducted (see Section
23.5, Appendix 2, and SEMI S6) to control, efficiently
and safely, for potential worst-case, realistic employee
exposures to chemicals during normal operation,
maintenance, or failure of other equipment components
(hardware or software). All design criteria and test
protocols should be based on recognized methods. See
also Section 23.3.
22.3 Documentation should be developed showing the
equipment exhaust parameters and relevant test
methods, and should include (see also Appendix 2):
duct velocity (where needed to transport solid
particles);
volumetric flow rate Q;
capture velocity (where airborne contaminants are
generated outside an enclosure);
face velocity (where applicable);
hood entry loss factor F
h
or K;
coefficient of entry C
e.
;
hood static pressure SP
h
;
duct diameter at the point of connection to
facilities; and
location(s) on the duct or hood where all
ventilation measurements were taken.
22.4 Exhaust flow interlocks should be provided by the
manufacturer on all equipment that uses hazardous
production materials (HPMs) where loss of exhaust
may create a hazard. Flow (e.g., pitot probe) or static
pressure (e.g., manometer) switches are the preferred
sensing methods.
SEMI S2-0703a
E
© SEMI 1991, 2004 27
NOTE 106: Sail switches (switches that are connected to a
lever that relies upon air velocity to activate) are generally not
recommended.
NOTE 107: It is recommended that the pressure or flow
measuring point be located upstream of the first damper.
NOTE 108: Section 11 contains provisions for safety
interlocks.
22.4.1 When the exhaust falls below the prescribed set
point, an alarm should be provided within audible or
visible range of the operator, and the process equipment
should be placed in a safe stand-by mode. A time delay
and exhaust setpoint for the equipment to go into
standby mode may be allowable, based on an
appropriate risk assessment. The system should be
capable of interfacing with the facility alarm system.
NOTE 109: It is recommended that non-HPM chemical
process exhaust be equipped with audible and visible
indicators only.
22.4.2 Exhaust flow interlocks and alarms should
require manual resetting.
22.4.3 Exhaust flow interlocks should be fault-tolerant.
22.5 Equipment and equipment components should be
designed using good ventilation principles and practices
to ensure chemical capture and to optimize exhaust
efficiency (see Appendix 2).
NOTE 110: It is recommended that exhaust optimization be
achieved with total equipment static pressure requirements of
–1 to –38 mm (–0.05 to –1.5") H
2
O (see also Section A2-1 of
Appendix 2, and Section 8.3.6.1 of SEMI S6-93).
23 Chemicals
23.1 The manufacturer should generate a chemical
inventory identifying the chemicals anticipated to be
used or generated in the equipment. At a minimum, this
should include chemicals in the recipe used for
equipment qualification or “baseline” recipe, as well as
intended reaction products and anticipated by-products.
Chemicals on this list that can be classified as
hazardous production materials (HPMs), or odorous
(odor threshold < 1 ppm) or irritant chemicals
(according to their material safety data sheets), should
also be identified.
23.2 A hazard analysis (see Section 6.8) should be
used as an initial determination of chemical risk as well
as to validate that the risk has been controlled to an
appropriate level.
23.2.1 The hazard analysis, at a minimum, should
address the following conditions:
potential mixing of incompatible chemicals;
potential chemical emissions during routine
operation;
potential chemical emissions during maintenance
activities; and
potential key failure points and trouble spots (e.g.,
fittings, pumps).
23.2.2 All routes of exposure (e.g., respiratory, dermal)
should be considered in exposure assessment.
23.3 The order of preference for controls in reducing
chemical-related risks is as follows:
23.3.1 substitution or elimination (see also Section
21.2.2);
23.3.2 engineering controls (e.g., enclosure,
ventilation, interlocks);
23.3.3 administrative controls (e.g., written warnings,
standard operating procedures);
23.3.4 personal protective equipment.
23.4 The design of engineering controls (e.g.,
enclosure, ventilation, interlocks) should include
consideration of (see also Appendix 3):
pressure requirements;
materials incompatibility;
equipment maintainability;
chemical containment; and
provisions for exhaust ventilation (see Section 22).
23.5 During equipment development, the supplier
should conduct an assessment that documents
conformance to the following airborne chemical control
criteria (see also Appendix 2). All measurements should
be taken using recognized methods with documented
sensitivities and accuracy. A report documenting the
survey methods, equipment operating parameters,
instrumentation used, calibration data, results, and
discussion should be available.
23.5.1 There should be no chemical emissions to the
workplace environment during normal equipment
operation. Conformance to this section can be shown by
demonstrating ambient air concentrations to be less
than 1% of the Occupational Exposure Limit (OEL) in
the worst-case personnel breathing zone. Where a
recognized method does not provide sufficient
sensitivity to measure 1% OEL, then the lower
detection limit of the method may be used to satisfy this
criterion.
23.5.2 Chemical emissions during maintenance
activities should be minimized. Conformance to this