semi合集-English.pdf - 第6809页

SEMI S2-0703a E © SEMI 1991, 2004 38 manifold b oxes, and seco ndary gas panel enclosures, are typically six-sided ful ly enclosed enclosures with access panels/doors on at least one side. These ventilated enclo sures ar…

100%1 / 7923
SEMI S2-0703a
E
© SEMI 1991, 2004 37
A2-4.1.6 Exhaust volume settings should consider
laminar air flow volumes and be balanced to minimize
turbulence and to ensure capture.
A2-4.1.7 The station design should consider airflow
patterns in the operating zone to minimize turbulent
horizontal airflow patterns into and across the work
deck.
A2-4.1.8 Additional considerations to reduce exhaust
demand include providing covered tanks, and recessing
tanks below deck level.
A2-4.2 Control Specifications
A2-4.2.1 Wet station specifications are complicated by
the fact that wet stations generally do not have an easily
definable face velocity to measure. A number of
methods have been used and are all acceptable if used
consistently and provided documentation indicates
chemical containment meets the 1% of the OEL at
distances beyond the plane of penetration at the exterior
of the wet station.
A2-4.2.2 Maintain an average capture velocity of 0.33
to 0.50 m/s (65–100 fpm) immediately above a bath.
A2-4.2.3 Calculate the total exhaust volume
requirement by determining the total volumetric flow of
laminar air hitting the deck and increasing this value by
20 to 25%.
A2-4.2.4 For some wet stations that are partially
enclosed from the top, an artificial plane opening
(“face”) can be defined where the downward laminar
air flow penetrates the capture zone (at “face velocity”)
of the wet station. Depending on the hood design and
laminar air flow provided, average face velocities can
range from 0.20 to 0.50 m/s (40 to 100 fpm). The
measurement location can greatly influence the
measured face velocity; therefore, this method should
be supplemented with at least one of the preceding
methods for greater accuracy and reproducibility at the
user’s facility.
A2-4.3 Recommended Measurement/Validation
Method
A2-4.3.1 Confirmation of capture using vapor
visualization.
A2-4.3.2 Confirmation of laminar flow of make up air
into the station using vapor visualization.
A2-4.3.3 Tracer gas testing may be used as
supplemental verification, provided an emission rate
can be accurately defined.
A2-5 Supplemental Exhaust
Supplemental exhaust, if not designed into the
equipment, can be provided by a flexible duct with a
tapered hood. This can be placed in the work area to
remove potential contaminants before they enter the
breathing zone. Supplemental exhaust is frequently
used during maintenance or service.
A2-5.1 Design Recommendations
A2-5.1.1 Retractable or movable non-combustible flex
ducting for easy reach and placement within 150 to 300
mm (6 to 12 inches) of potential emissions to be
controlled.
A2-5.1.2 Manual damper at hood to allow for local
control, i.e., shut off when not required.
A2-5.1.3 Tapered hood with a plane opening as a
minimum. The additional use of flanges or canopies to
enclose the process will result in improved efficiency.
A2-5.2 Control Specifications
NOTE A2-1: This is one equation that is most commonly
used. Other equations may be appropriate; see also ACGIH
Industrial Ventilation Manual, and Semiconductor Exhaust
Ventilation Guidebook.
A2-5.2.1 A minimum capture velocity of 0.50 m/s (100
fpm) is required at the contaminant generation point for
releases of vapor via evaporation or passive diffusion.
Ventilation should not be relied upon to prevent
exposures to hazardous substances with release
velocities (e.g., pressurized gases). For a plane open
ended duct without a flange, the air flow required at a
given capture velocity can be calculated by:
Q = V(10X
2
+ A)
Where: Q = required exhaust air flow in m
3
/s (cfm)
V = capture velocity in m/s (fpm) at distance X from
hood
A = hood face area in square meters (square feet)
X = distance from hood face to farthest point of
contaminant release in meters (feet). NOTE: This is
only accurate when X is within 1.5 diameters of a round
opening, or within 0.25 circumference of a square
opening.
A2-5.3 Recommended Measurement/Validation
Method
A2-5.3.1 Measurement of capture velocity at farthest
point of contaminant release. Measurements taken with
a velometer or anemometer.
A2-5.3.2 Confirmation by visualization check of
capture using vapor capture testing.
A2-6 Equipment Gas Panel Enclosures
Equipment gas panel enclosures, also known as gas
boxes, jungle enclosures, gas jungle enclosures, valve
SEMI S2-0703a
E
© SEMI 1991, 2004 38
manifold boxes, and secondary gas panel enclosures,
are typically six-sided fully enclosed enclosures with
access panels/doors on at least one side. These
ventilated enclosures are designed to contain and
remove hazardous gases from the work area in the
event of a gas piping failure or leak. Gas panel
enclosures are typically of two types, those requiring no
access while gas systems are charged, and those that
must be opened during processing while gas systems
are charged. There is also a distinct difference in
control specifications for those with pyrophorics or
other flammables vs. other HPMs, specifically in the
control of pocketing.
A2-6.1 Design Recommendations
A2-6.1.1 Compartmentalize potential leak points.
A2-6.1.2 Minimize the total size of the panel and its
enclosure.
A2-6.1.3 Minimize size and number of openings.
A2-6.1.4 Minimize static pressure requirements of the
enclosure; control has been shown to be achievable
with –1.3 to –2.5 mm ( –0.05 to –0.1 in.) w.g.
A2-6.1.5 Design for sweep. Minimize the number and
size of openings. Seal unnecessary openings (e.g.,
seams, utility holes).
A2-6.1.6 Where routinely used access doors are
required:
Make the access door as small as practical.
Place the openings to the enclosure in the access
door to minimize air flow requirements.
Provide baffles behind the door to direct leaks
away from the door and openings.
Compartmentalize the enclosure so that access to
one area does not affect air flow control in other
areas.
A2-6.2 Control Specifications
A2-6.2.1 Exhaust volumes as low as 4–5 air changes
per minute or less can be specified and meet the S2
criteria in Section 23.5 if the design principles listed
above are considered when designing equipment and
enclosures.
A2-6.2.2 Where there is potential for chemical
exposure during access which can be controlled by face
velocity, the enclosure should also provide a minimum
face velocity of 0.36 to 0.76 m/s (70 to 150 fpm) when
open. Face velocity should not be relied upon to control
emissions from a pressurized fitting.
A2-6.2.3 Enclosures for pyrophoric or flammable
gases should be designed to ensure adequately uniform
dilution (i.e., prevent “pocketing”) and to prevent
accumulation of pyrophoric and flammable gases above
their lower explosive limit. Uniform dilution can
generally be verified through exhaust vapor
visualization techniques. Ventilation flow rate should
be adequate to maintain concentrations below 25% of
the lower explosive limit for the gas with the lowest
LEL that is used in the enclosure. This can generally be
verified using engineering calculations to verify
dilution, and vapor visualization to verify mixing.
A2-6.3 Recommended Measurement/Validation
Method
A2-6.3.1 Preferred validation by tracer gas testing per
SEMI F15.
A2-6.3.2 Additional confirmation by visualization
check of air flow, mixing and sweep using smoke or
vapor testing.
A2-6.3.3 Measurement of average face velocity at
inlet(s), opening(s), or routinely used access doors.
Measurements should be taken with a velometer or
anemometer. For larger openings, multiple
measurements are taken in a grid, at least 10 to 40 per
square meter (1–4 per square foot) of open area. Useful
equation: V = 4.043 (VP/d)
0.5
, where V = velocity in
m/s, VP = velocity pressure in mm H
2
O, and d =
density correction factor (unitless).
A2-7 Equipment Exhaust Ventilation
Specifications and Measurements
A2-7.1 Specifications for equipment exhaust should be
provided by the supplier and define:
A2-7.1.1 The control specification or standard for the
hood or enclosure, i.e., face velocity or capture velocity
if applicable.
A2-7.1.2 The airflow in the duct required to maintain
the control volume or flow required. Measurements
should be made using the ACGIH pitot traverse method
described below.
A2-7.1.3 The location where the Pitot traverse
measurement in the duct was made.
A2-7.1.4 Static pressure requirements.
A2-7.1.5 Coefficient of Entry (C
e
) (see definitions and
Section 22.3).
A2-7.1.6 Hood Loss Factor (K or F
h
) (see definitions
and Section 22.3).
A2-8 Duct Traverse Method
A2-8.1 Because the air flow in the cross-section of a
duct is not uniform, it is necessary to obtain an average
by measuring velocity pressure (VP) at points in a
number of equal areas in the cross-section. The usual
SEMI S2-0703a
E
© SEMI 1991, 2004 39
method is to make two traverses across the diameter of
the duct at right angles to each other. Reading are taken
at the center of annular rings of equal area. Whenever
possible, the traverse should be made 7.5 duct
diameters downstream and 3 diameters upstream from
obstructions or directional changes such as an elbow,
hood, branch entry, etc. Where measurements are made
closer to disturbances, the results should be considered
subject to some doubt and checked against a second
location. If agreement within 10% of the two traverses
is obtained, reasonable accuracy can be assumed and
the average of the two readings used. Where the
variation exceeds 10%, a third location should be
selected and the two air flows in the best agreement
averaged and used. The use of a single centerline
reading for obtaining average velocity is a very coarse
approximation and is not recommended. If a traverse
cannot be done, then the centerline duct velocity should
be multiplied by 0.9 for a coarse estimate of actual
average duct velocity. Center line duct velocity should
not be used less than 5 duct diameters from an elbow,
junction, hood opening, or other source of turbulence.
A2-8.2 For ducts 150 mm (6 in.) and smaller, at least 6
traverse points should be used. For round ducts larger
than 150 mm (6 in.) diameter, at least 10 traverse points
should be employed. For very large ducts with wide
variation in velocity, 20 traverse points will increase the
precision of the air flow measurement.
A2-8.3 For square or rectangular ducts, the procedure
is to divide the cross-section into a number of equal
rectangular areas and measure the velocity pressure at
the center of each. The number of readings should not
be less than 16. Enough readings should be made so the
greatest distance between centers is less than 150 mm
(6 in.).
A2-8.4 The following data are required:
A2-8.4.1 The area of the duct at the traverse location.
A2-8.4.2 Velocity pressure at each point in the traverse
and/or average velocity and number of points measured.
A2-8.4.3 Temperature of the air stream at the time and
location of the traverse.
A2-8.4.4 The velocity pressure readings obtained are
converted to velocities, and the velocities (not the
velocity pressures) are averaged. Useful equation: V =
4.043 (VP/d)
0.5
, where V = velocity in m/s, VP =
velocity pressure in mm H
2
O, and d = density
correction factor (unitless). Some monitoring
instruments conduct this averaging internal to the
instrument.
A2-8.5 Flow measurement taken at other than standard
air temperatures should be corrected to standard
conditions (i.e., 21C [70F], 760 mm [29.92 in.] Hg).