semi合集-English.pdf - 第849页
SEMI E114-0302 E © SEMI 2002 3 9 Test Procedure for Determ ining Electrical Length 9.1 Two test procedures ca n be used to dete rmine the electrical length of a cable assembly. One method measures it directly at the oper…

SEMI E114-0302
E
© SEMI 2002 2
5 Terminology
5.1 Abbreviations and Acronyms
5.1.1 CVD — Chemical Vapor Deposition
5.1.2 PVD — Physical Vapor Deposition
5.1.3 VSWR — Voltage Standing Wave Ratio
5.2 Definitions of Terms
5.2.1 cable assembly — the section of cable
(transmission line), including the connectors, used to
connect various parts of the RF power delivery system.
5.2.2 device under test (DUT) — the cable assembly
intended to be tested.
5.2.3 electrical length — the length of the cable
assembly at the operating frequency expressed in terms
of degrees, where one wavelength at the nominal
operating frequency is equal to 360 degrees.
5.2.4 half wave resonant frequency — the frequency of
the cable assembly where the electrical length of the
assembly is equal to one half (0.5) of a wavelength.
For example, the half wave resonant frequency of a
cable assembly with an electrical length of 2 meters
would be 74.95 MHz ((c/2-meters)/2).
5.2.5 harmonic frequency — the harmonic frequencies
are defined as integer multiples of the fundamental
frequency. For example, the second harmonic of 13.56
MHz is 27.12 MHz.
5.2.6 quarter wavelength — the length equal to one
quarter of the wavelength at a given frequency, where
the wavelength is equal to the speed of light divided by
the frequency.
5.2.7 S-parameters — the scattering matrix used to
describe a network. The reflection coefficient is the
S11 parameter and the transmission coefficient is the
S21 parameter.
5.2.8 speed of light (c) — the speed of light in free-
space is assumed to be 2.9979 × 10
8
meters/second.
5.2.9 velocity of propagation (VP) — the velocity of
propagation, VP, is defined as the ratio of the speed of
an electrical signal down a length of cable divided by
the speed in free space. It is the reciprocal of the square
root of the relative dielectric constant of the dielectric
material between the inner and outer conductor of a
coaxial assembly. For example, the VP for cable type
RG-217 is nominally 0.66.
6 Test Apparatus
6.1 RF Vector Network Analyzer — The network
analyzer is used to measure the electrical length and can
also be used to determine the attenuation (power
losses). The network analyzer requires vector
capability so that both the magnitude and phase of the
reflection coefficient and transmission coefficient can
be measured as a function of frequency. The frequency
range shall include the operating frequency and the
quarter-wave resonant frequency of the RF cable
assembly.
6.2 Time Domain Reflectometer (TDR) — The TDR is
used to measure and verify the characteristic impedance
as a function of distance along the transmission line.
6.3 RF Adapters and Terminations — Various adapters
may be necessary to convert between different types of
coaxial connectors (e.g., type N to type HN adapters,
etc.). All adapters used shall have the same nominal
characteristic impedance as the cable assembly to be
tested (DUT), which is typically 50 ohms. For some
measurements, additional coaxial cable assemblies may
be necessary. These cable assemblies, which should
not be confused with the DUT cable assembly, shall be
of the same nominal characteristic impedance as the
DUT cable assembly. Standard terminations will also
be used, such as shorts, opens, and precision 50-ohm
loads.
7 Safety Precautions
7.1 Work should be conducted in accordance with local
safety requirements and test device manufacturer
recommended safety procedures. The tests described in
this document involve using low output power test
instrumentation (typically less than 10 milli-Watt).
7.2 The area immediately surrounding the Test Setup
should be keep free and clear of unnecessary equipment
and materials. Some of the cable assemblies to be
tested may be long and can be trip and lift/weight
hazards.
8 Test Setup for Electrical Length Test
8.1 The Test Setup for the electrical length test consists
of the Network Analyzer, the cable assembly to be
tested (DUT), the appropriate adapter (if any) to
connect the DUT to the network analyzer, and the
appropriate adapter (if any) to connect a coaxial short
circuit termination to the output of the DUT. A
schematic of the Test Setup is shown in Figure 1. Care
should be taken to ensure that the cable assemblies to
be tested do not exceed the vendor specified bending
radius, which is typically 5 times the outer diameter of
the cable.
8.2 Prior to making any measurements, the Network
Analyzer shall be turned on and allowed to warm up
before the testing is to take place. This time allows for
electronics to come to a stable operating condition for
the measurements.

SEMI E114-0302
E
© SEMI 2002 3
9 Test Procedure for Determining Electrical
Length
9.1 Two test procedures can be used to determine the
electrical length of a cable assembly. One method
measures it directly at the operating frequency and the
other measures the half-wave resonant frequency to
determine the electrical length. Each method has
advantages, depending on the length of the cable
assembly. Prior to choosing a method, the equivalent
free-space length of the DUT shall be estimated in units
of distance (i.e., meters). This length can be estimated
by dividing the physical length of the DUT by the
velocity of propagation for the particular type of cable.
For example, a DUT made from RG-217 cable with a
physical length of 20 meters and a velocity of
propagation of 0.66 would have an equivalent free-
space length of 30.303 meters (20/0.66 = 30.303). A
flow chart showing the steps for choosing which test
method to use is shown in Figure 2.
9.2 The equivalent free-space length of the DUT shall
be compared with the wavelength of the nominal
operating frequency. Test Method 1 (Section 9.3) shall
be used if the equivalent free-space length is less than a
quarter wavelength of the nominal operating frequency.
Test Method 2 shall be used if it is equal to or greater
than a quarter wavelength of the nominal operating
frequency. For example, if the estimated free-space
length is 3 meters and the nominal operating frequency
is 13.56 MHz (quarter wavelength = 0.25 × c/13.56 ×
10
6
= 5.527 meters), then Test Method 1 is
recommended. If the estimated free-space length is 25
meters, then Test Method 2 is recommended.
9.3 Test Method 1 for Determining Electrical Length
9.3.1 This test method measures the phase angle of the
reflection coefficient at the nominal operating
frequency of the DUT when the DUT is terminated by a
short circuit.
9.3.2 Calibrate the Network Analyzer at the desired
operating frequency (e.g., 13.56 MHz). If adapters are
to be used to connect the DUT to the Network Analyzer
and/or to the short circuit termination, then the
calibration shall be made with the adapters in place.
The Network Analyzer shall be calibrated for
measuring the reflection coefficient at test Port 1 (see
Figure 1) using the calibration kit provided with the
Network Analyzer. This measurement is equivalent to
measuring the S11 S-parameter. The calibration shall
be performed at fixed frequency (continuous-wave
operation) using the lowest bandwidth possible
(typically 10 Hz).
9.3.3 After calibration, the cable assembly to be tested
(DUT) shall be attached to Port 1 on the Network
Analyzer. The other end of the DUT shall be
terminated with a short circuit. After all connections
have been visually inspected to ensure proper contact
and the Network Analyzer measurement has stabilized,
the value of the reflection coefficient phase angle shall
be recorded.
9.3.4 If the indicated phase angle of the reflection
coefficient is positive, then the electrical length of the
DUT is equal to one half of the value of the difference
between 180 and the measured phase angle. For
example, if the measure reflection coefficient phase
angle is 120 degrees, then the electrical length is 30
degrees ((180-120)/2).
9.3.5 If the indicated phase angle of the reflection
coefficient is negative, then the electrical length of the
DUT is greater than a quarter wavelength. For this
case, the electrical length is equal to one half of the
absolute value of the measured value of the reflection
coefficient phase angle plus 90. For example, if the
measure reflection coefficient phase angle is -10
degrees, then the electrical length is 95 degrees (90 +
10/2).
9.4 Test Method 2 for Determining Electrical Length
9.4.1 This test method determines the electrical length
of the cable assembly DUT by measuring the half wave
resonant frequency when the DUT is terminated by a
short circuit. For this measurement, the frequency of
the network analyzer is swept. The frequency range of
the sweep is determined from the estimated free-space
length of the DUT.
9.4.2 Estimate the half wave resonant frequency of the
DUT. This frequency is equal to one half of the ratio of
the speed of light divided by the estimated free space
length determined in Section 9.2. For example, if the
estimated free space length of the DUT is 25 meters,
then the estimated half wave resonant frequency is
5.996 MHz (0.5 × c/25).
9.4.3 Calibrate the Network Analyzer. If adapters are
to be used to connect the DUT to the Network Analyzer
and/or to the short circuit termination, then the
calibration shall be made with the adapters in place.
The center frequency of the frequency sweep shall be at
the estimated half wave resonant frequency calculated
in Section 9.4.2, and the frequency span of the sweep
shall be no greater than 10% of the estimated
frequency. For example, if the estimated half wave
resonant frequency is 6.0 MHz, then the frequency span
shall be no greater than 0.6 MHz. The Network
Analyzer shall be calibrated for measuring the
reflection coefficient at test Port 1 (see Figure 1) using
the calibration kit provided with the Network Analyzer.
This measurement is equivalent to measuring the S11
S-parameter. The calibration shall be performed using
the lowest bandwidth possible (typically 10 Hz).

SEMI E114-0302
E
© SEMI 2002 4
9.4.4 After calibration, the cable assembly to be tested
(DUT) shall be attached to Port 1 on the Network
Analyzer. The other end of the DUT shall be
terminated with a short circuit. After all connections
have been visually inspected to ensure proper contact
and the Network Analyzer measurement has stabilized,
the value of the reflection coefficient phase angle can
be examined.
9.4.5 The indicated frequency where the reflection
coefficient phase angle is ± 180 degrees shall be
recorded. The electrical length of the DUT at the
desired nominal operating frequency (for example,
13.56 MHz) is equal to 180 degrees multiplied by the
ratio of the nominal operating frequency divided by the
measured frequency where the phase angle of the DUT
is equal to ± 180 degrees. For example, if the measured
frequency where the reflection coefficient is ± 180
degrees is 6.1 MHz, then the electrical length of the
DUT at 13.56 MHz is 400.13 degrees (180 × 13.56 /
6.1).
10 Test Setup for Power Dissipation (Loss)
Test
10.1 The Test Setup for the power dissipation (loss)
test consists of the Network Analyzer, the cable
assembly to be tested (DUT), an additional short test
cable (for transmission calibration), the appropriate
adapter (if any) to connect the DUT input to the
network analyzer, and the appropriate adapter (if any)
to connect the DUT output to the network analyzer. A
schematic of the Test Setup is shown in Figure 3.
11 Test Procedure for Determining Power
Dissipation
11.1 The test procedure for determining power
dissipation in cable assemblies will also use a Network
Analyzer. In this case, both Ports of the Network
Analyzer will be used. The transmission coefficient
will be measured (also called the S21 S-parameter).
11.2 Calibrate the Network Analyzer at the desired
operating frequency (for example, 13.56 MHz). If
adapters are to be used to connect the DUT to the
Network Analyzer and/or to the short circuit
termination, then the calibration shall be made with the
adapters in place, along with the additional section of
test cable needed for the calibration. The Network
Analyzer shall be calibrated for measuring the
transmission coefficient, S21 (see Figure 3). The
calibration shall be performed at fixed frequency
(continuous-wave operation) using the lowest
bandwidth possible (typically 10 Hz).
11.3 Connect the cable assembly DUT between the two
test Ports on the Network Analyzer (including the
additional test cable used for calibration). After
visually inspecting the connections to ensure proper
contact and the Network Analyzer measurement has
stabilized, the value of the transmission coefficient
(S21) shall be recorded.
11.4 The recorded number shall be expressed in terms
of dB (decibels) and percentage of power transferred in
the DUT. The conversion between dB and percentage
is expressed as:
)10/dBin loss(
10100% ×=TransferPower
For example, if the transmission coefficient is measured
to be –0.4 dB, then the power transfer percentage would
be 91.2%. In other words, 8.8% of the power is lost in
the DUT.
12 Test Setup for Characteristic Impedance
Variation Measurement
12.1 The Test Setup for the Characteristic Impedance
variation measurement consists of a Time Domain
Reflectometer (TDR), the cable assembly to be tested
(DUT), the appropriate adapter (if any) to connect the
DUT input to the TDR, and a standard 50-ohm load
termination (see Figure 4).
12.2 Prior to making any measurements, the TDR shall
be turned on and allowed to warm up. This time allows
for electronics to come to a stable operating condition
for the measurements.
13 Test Procedure for Determining
Characteristic Impedance
13.1 Connect a standard 50-ohm load termination to
the input of the TDR and measure the impedance. This
measurement determines the normalization factor for
the measured impedances. All reported measurements
shall be scaled by this factor by multiplying subsequent
measurements by the ratio of 50 divided by the
impedance value measured with the 50-ohm standard
load.
13.2 Prior to measuring the DUT, the nominal velocity
of propagation of the cable shall be entered into the
TDR. For example, the velocity of propagation is 0.66
for cable type RG-217.
13.3 Connect one end of the DUT to the TDR and
terminate the other end of the DUT with a short circuit.
Measure the characteristic impedance as a function of
distance along the DUT by moving the measurement
distance indicator of the TDR. Record the minimum
and maximum impedance measured over the length of
the cable assembly. The measurement shall be made
throughout the length of the DUT, including the
connectors, up to the short circuit termination.