SEMI S22-1103a © SEMI 2003, 2005 6 5.1.34 hazardous electrical power — po wer levels equal to or greater than 240VA. 5.1.35 insulation — a layer of non-conductive material used as the outer surface of a c onductor for th…

100%1 / 7923
SEMI S22-1103a © SEMI 2003, 2005 5
5.1.14 disconnecting means — a device, or group of devices, or other means by which the conductors of a circuit
are intended to be disconnected from their source of supply.
5.1.15 door — a hinged enclosure panel.
5.1.16 double insulation — comprised of both supplementary insulation and basic insulation combined.
5.1.17 duct an enclosed channel designed expressly for holding and protecting electrical conductors, cables, and
bus bars. Conduits, wireways and under-floor channels are types of ducts.
5.1.18 earthing — see protective earthing system.
5.1.19 electrical enclosure — a panel, compartment, or other defined area housing electrical components used to
enhance the safety of the equipment containing those components.
5.1.20 electrical feed — (referenced from the equipment) a facility supply conductor that provides electrical energy
to a piece of equipment.
NOTE 4: Electrical wiring from enclosure to enclosure, routed through the facility, but provided with the equipment to power
subsystems, are not considered electrical feeds.
5.1.21 energized — electrically connected to a source of voltage.
5.1.22 equipment — a specific piece of machinery, apparatus, process module, or device used to execute an
operation. The term “equipment” does not apply to any product (e.g., substrates, semiconductors).
5.1.23 exposed (as applied to energized parts) — capable of being inadvertently touched or approached nearer than
a safe distance by a person. It is applied to parts that are not suitably guarded, isolated, or insulated.
5.1.24 fail-safe — designed so that a failure does not result in an increased risk.
NOTE 5: For example, a fail-safe temperature limiting device would indicate an out-of-control temperature if it were to fail.
This might interrupt a process, but would be preferable to the device indicating that the temperature is within the control limits,
regardless of the actual temperature, in case of a failure.
5.1.25 Fail-to-safe equipment control system (FECS) — a safety-related programmable system of control circuits
designed and implemented for safety functions in accordance with recognized standards such as ISO 13849-1 (EN
954-1) or IEC 61508, ANSI SP 84. These systems (e.g. safety Programmable Logic Controller (PLC), safety-related
Input and output (I/O) modules) diagnose internal and external faults and react upon detected faults in a controlled
manner in order to bring the equipment to a safe state.
NOTE 6: A FECS is a subsystem to a (PES) Programmable Electronic System as defined in IEC61508 –4.
5.1.26 failure — the termination of the ability to perform an intended function. Failure is an event, as distinguished
from “fault,” which is a state.
5.1.27 fault — the state of an item characterized by the inability to perform its intended function; excludes the
inability to perform required functions during preventive maintenance or other planned actions, or due to lack of
external resources.
5.1.28 fault-tolerant — designed so that a reasonably foreseeable single point failure does not result in an unsafe
condition.
5.1.29 ground fault an unintentional, electrically conducting connection between an ungrounded or grounded
conductor of an electrical circuit and the normally non-current-carrying conductors, metallic enclosures, metallic
raceways, or metallic equipment.
5.1.30 Ground-Fault-Circuit-Interrupter (GFCI) — a device intended for the protection of personnel that functions
to de-energize a circuit or portion thereof within an established period of time when a current to ground exceeds a
value in the range of 4 mA to 6 mA (for further information, see UL 943, Standard for Ground-Fault Circuit-
Interrupters).
5.1.31 grounding — see protective earthing system.
5.1.32 hazard — a condition that is a prerequisite to a mishap.
5.1.33 hazardous voltage — voltages greater than 30 Volts RMS, 42.4 Volts peak, or 60 Volts DC.
SEMI S22-1103a © SEMI 2003, 2005 6
5.1.34 hazardous electrical power — power levels equal to or greater than 240VA.
5.1.35 insulation — a layer of non-conductive material used as the outer surface of a conductor for the purpose of
protecting against electric shock.
5.1.36 interlock — a mechanical, electrical or other type of device or system, whose purpose is to prevent or
interrupt the operation of equipment subsystems under specified conditions.
5.1.37 interrupting capacity — the highest current at rated voltage that a device is intended to interrupt.
NOTE 7: Also known as amperes interrupting capacity (AIC).
5.1.38 isolated power system — a power system that has a high impedance between its conductors and the facilities
connection of the equipment. High impedance can be characterized by resistances of one meg-ohm or more.
Isolated power systems are supplied power by isolation transformers or power supplies that have no direct electrical
connection between their primary conductors and their secondary conductors.
NOTE 8: An isolation transformer with one leg of the secondary connected to ground is not an isolated power system.
5.1.39 main disconnecting means — a disconnecting means that is intended to be used to disconnect facilities
electrical power from the system.
5.1.40 maintenance — planned activities intended to keep equipment in proper working order (see also the
definition for service).
5.1.41 material group — a categorization of the Comparative Tracking Index (CTI) of an insulator as follows:
Material Group I: 600 <= CTI
Material Group II: 400 <= CTI < 600
Material Group IIIa: 175 <= CTI < 400
Material Group IIIb: 100 <= CTI < 175
5.1.42 maximum nominal load — the maximum continuous power a circuit will draw under operating conditions
prescribed by the manufacturer. Non-periodic power variations of less than a second in duration are not considered
continuous.
5.1.43 multi-outlet assemblies — assemblies whose primary function is to provide electrical connections and that
have multiple receptacles which are intended for electrical connections.
5.1.44 neutral conductor — an earthed (grounded) AC current carrying conductor.
NOTE 9: It is distinct from protective earthing which is an earthed (grounded) non-current carrying conductor or a non-earthed
(non-grounded) current carrying conductor.
5.1.45 normal operating conditions — the condition of the equipment reasonably foreseen by the manufacturer,
including specified conditions of use, during operation, maintenance and servicing while the equipment is operated,
maintained and serviced according to the manufacturer’s instructions and with no unauthorized equipment
modifications. Normal operating conditions should include consideration of reasonably foreseeable misuse.
5.1.46 operator — a person who interacts with the equipment only to the degree necessary for the equipment to
perform its intended function.
5.1.47 operator access — an area to which, under normal operating conditions, one of the following applies: access
may be gained without the use of a tool, the means of access is deliberately provided to the operator, or the operator
is instructed to enter regardless of whether or not a tool is needed to gain access (if the operator is so instructed, this
area becomes evaluatable as an operator accessible area).
5.1.48 overcurrent — any current in excess of the rated current of the equipment or the rated ampacity (current-
carrying capacity) of the conductor; it may result from overload, short circuit, or ground fault.
5.1.49 overload — operation of equipment in excess of normal, full-load rating, or of a conductor in excess of rated
ampacity that, when it persists for a sufficient length of time, would cause damage or dangerous overheating. A
fault, such as a short circuit or ground fault, is not an overload (see short circuit and ground fault).
SEMI S22-1103a © SEMI 2003, 2005 7
5.1.50 permanently connected equipment — equipment that is electrically connected to a supply by means of a
connection that may be detached only by the use of a tool.
5.1.51 pollution — any addition of foreign matter, solid, liquid or gas, that may produce a reduction of dielectric
strength or increase of surface resistivity.
5.1.52 pollution degree — for the purpose of evaluating clearances the following two degrees of pollution in the
micro-environment are recognized for use with this document:
5.1.52.1 pollution degree 1 — no pollution or only dry, non-conductive pollution occurs. The pollution has no
influence. Cleanroom Class 1000 or less.
NOTE 10: Cleanroom Class 1000 or less is pollution degree 1, however the pollution degree in a particular area in a given piece
of equipment may exceed pollution degree 1, even if the equipment is installed in a cleanroom class 1000 or less.
5.1.52.2 pollution degree 2 — normally only non-conductive pollution occurs. Occasionally, however, a temporary
conductivity caused by condensation is expected. Cleanroom Class greater than 1000.
NOTE 11: Cleanroom Class greater than 1000 is pollution degree 2, however the pollution degree in a particular area in a given
piece of equipment may exceed pollution degree 2, even if the equipment is installed in a cleanroom greater than 1000.
5.1.53 protective conductor — a conductor that provides electrical continuity between conductive components that
are not intended to be energized during normal operations and the equipment’s protective earthing conductor
terminal.
5.1.54 protective earthing conductor — a normally non-current carrying conductor connected between earth
(ground) at the source of supply and the protective earthing (grounding) terminal on the equipment enclosure.
5.1.55 protective earthing conductor terminal — a terminal bonded to conductive parts of an equipment enclosure
for safety purposes and intended to be connected to an external protective earthing (grounding) conductor (the
protective earthing conductor).
5.1.56 protective earthing system — the earthing (grounding & bonding) system connecting accessible conductive
parts of the equipment to an external earth (ground) at the source of supply. The protective earthing system may
include bonded structural members, bonding jumpers, the protective earthing conductor terminal on the equipment
and the protective earthing conductor in the incoming supply wiring to the equipment.
5.1.57 raceway — an enclosed channel of metal, or nonmetallic materials, designed expressly for holding wires,
cables, or busbars.
5.1.58 readily accessible — capable of being reached quickly for operation or inspection, without requiring
climbing over or removing obstacles or using portable ladders, chairs, etc.
5.1.59 reinforced insulation — a single layer of insulation that provides a degree of protection against electric shock
equivalent to double insulation.
5.1.60 risk — the expected losses from a mishap, expressed in terms of severity and likelihood.
5.1.61 safe shutdown condition — a condition in which all hazardous energy sources and hazardous production
materials are removed or suitably contained, unless this results in additional hazardous conditions.
5.1.62 safety circuit — a circuit whose intended function is to make the equipment safer. Interlocks, EMO circuits,
and other protective circuits are safety circuits.
5.1.63 service — unplanned activities intended to return equipment that has failed to proper working order (see also
maintenance).
5.1.64 severity — the extent of the worst credible loss (damage, injury, or release) from a mishap caused by a
specific hazard.
5.1.65 supplementary insulation — applied to basic insulation in order to ensure protection against electric shock in
the event of the failure of basic insulation.
5.1.66 testing — measurements or observations used to validate and document conformance to designated
criteria.
5.1.67 tool — an external device used to aid a person to perform a mechanical function.